background image

WATLOW IND.

 WATROD

 Modular Duct Heater Installation & Maintenance Manual

    

I&M NUMBER: 316-42-15-1 

 

                      Page: 1               

Date:6/11/2008  

Rev: 

_________________________________________________________________________________________________________________________________________________________________________________________________________________________
______

 

WATLOW IND.n  # 6 INDUSTRIAL LOOP RD. n HANNIBAL MO, 63401n PHONE 314-221-2816 n FAX 314-221-3723 

 

 

Pre Installation

 

 

Check to make sure that heater received is the same as that ordered.  

 

Elements may come in contact with each other during shipment. Minor adjustments to elements may be 
required prior to installation to separate them. Extensive bending of elements should be avoided since 
dielectric strength between coil and sheath may be compromised. 

 

Watlow heaters are built to comply with UL and CSA  dielectric requirements, it may be necessary due to 
atmospheric conditions / humidity, to perform a dielectric test prior to startup. (Refer to 

megohm test 

under 

Installation

 section)        

 

Safety 

 

Electric heaters are inherently dangerous!! 

Care should be taken to read and completely understand the 

Installation and Maintenance manual before installing and wiring the heater. Any installation and 
maintenance performed on the heater shall be done by a qualified electrician, in accordance with the 
"National Electric  Code" and other electrical codes as they apply. It is the users responsibility to ensure that 
the heater being used is properly selected and installed in the application. 

 

The Caution Symbol (exclamation point) alerts you to a 

"CAUTION"

, a safety or functional  hazard which 

 

could affect your equipment or its performance. 

 

 

 

The warning symbol (lightning bolt) alerts you to a 

"WARNING"

,  a safety hazard which could affect you and 

the equipment 

  

 Installation

 

Proper heater selection and installation will result in efficient heat transfer, safe operation, and long heater 
life. 

 
1.  Megohm precheck  

 

During shipping and/or storage, the possibility of moisture absorption by the insulation material within the 
element is possible. To ensure proper megohm values a minimum  500 VDC megohm meter (Megger) 
should be used to ensure that the megohm reading between the heater terminal and the heater sheath is 
more than 10 megohms when the unit is at room temperature.  

 
 

If several units are interconnected, the megohm of the heater is obtained by taking the reading and 
dividing by the number of interconnected elements. This reading should be greater than 10 megohms. 

 
 

If a low megohm value exists, two alternative methods can be used to remedy the situation. The best 
method is to remove all terminal hardware, and bake out the heater at no higher than 250°F (120

°

C)  

overnight or until an acceptable reading is reached. The second method is to energize the unit at low 
voltage in air until the megohm is at an acceptable reading. Care should be taken to prevent the heater 
sheath from exceeding 750°F (398

°

C)  for Incoloy

®

.  

 

2.   Protection of heater elements from over temperature 
 

The use of temperature controls to regulate heating process and prevent heater over temperature is 
highly recommended to ensure safe heater operation.  It is the users responsibility to ensure safety of 
the installation. Individual heater modules are designed to accommodate optional high limit 
thermocouple kit. 

 
 

WARNING: Install high temperature control protection in systems where an over temperature 
fault condition could present a fire hazard or other hazard. Failure to install temperature control 
protection where a potential hazard exists could result in damage to equipment and property, 
and injury to personnel. 

 

Summary of Contents for 316-42-15-1

Page 1: ...rts you to a WARNING a safety hazard which could affect you and the equipment Installation Proper heater selection and installation will result in efficient heat transfer safe operation and long heater life 1 Megohm precheck During shipping and or storage the possibility of moisture absorption by the insulation material within the element is possible To ensure proper megohm values a minimum 500 VD...

Page 2: ... use a compatible enclosure could result in heater damage and personnel danger Standard terminal enclosures are designed for general purpose use and are rated NEMA 1 These enclosures should be applied where there will be no danger of spilled liquids dampness dirt and gaseous conditions Enclosures for wet or hazardous locations are also available but must be installed at the factory Although enclos...

Page 3: ...___________________________________________________________________________________________________________________ ______ WATLOW IND n 6 INDUSTRIAL LOOP RD n HANNIBAL MO 63401n PHONE 314 221 2816 n FAX 314 221 3723 OVERHEATING OVERHEATING OVERHEATING OVERHEATING OVERHEATING OVERHEATING Heater too close to elbow Heater too close to transition Heater too close to blower Heater blocked by filter and...

Page 4: ...ower rating ambient temperature and type of environment Feeder wire should also be housed in either rigid or flexible conduit which carries the same classification as the heater enclosure It is the users responsibility to properly size and install feeder wire Feeder wire line connections may be made directly to stud terminals or box type compression fittings Box type compression fittings will acce...

Page 5: ...current is lower the heater may be wired wrong or has open elements Air not heating to desired Not enough Kw or incorrect voltage being applied temperature Too much heat loss higher wattage heater may be required High limit tripping alarm Not enough fluid flow Too much Kw Line voltage higher than designed allowable Preventative Maintenance CAUTION HAZARD OF ELECTRIC SHOCK TURN ALL POWER TO HEATER ...

Page 6: ...XXXXXXXXX XXXX W XXX V XPH XXXX TOP c Use a 1 8 NPT tap to thread the hole drilled in step b Make certain that the hole being tapped is perpendicular to the flange If it is not perpendicular electrical shorting may occur between the compression fitting and the nearby electrical jumpers d Thread the lower portion of the compression fitting in the hole tapped above e Insert thermocouple through lowe...

Page 7: ...her than this warranty Watlow is not liable for incidental or consequential damages resulting from use of the product whether a claim for such damages is based upon warranty contract negligence or other fault Should any product fail under these warranty conditions it will be repaired or replaced at no charge Advanced authorization must be obtained within 30 days of failure Return Policy 1 Call Wat...

Page 8: ...____________________________________________________________________________________________________________________________________________________________________________ ______ WATLOW IND n 6 INDUSTRIAL LOOP RD n HANNIBAL MO 63401n PHONE 314 221 2816 n FAX 314 221 3723 REVISIONS LEVEL DESCRIPTION INITIALS DATE 1 00 SEE PART COMMENTS 1 98 2 00 HAN2838 TBR 06 11 08 ...

Reviews: