Installation, Maintenance, & Repair  

Series 008QT, LF008QT, 008PCQT, LF008PCQT

Spill-Resistant Pressure Vacuum Breaker

Sizes: 

3

8

", 

1

2

", 

3

4

" and 1" (10, 15, 20, and 25mm)

008QT/LF008QT

Min. 

of 1"

Watts P60 

Pressure Reducing Valve

Solenoid Valve

Shutoffs

Test 

Cock

3

4

" Hose Adapter 

with strainer washer

Dispensing Inducers

Supply Hose

Strainer

Supply Line

008QT/LF008QT

Flood Rim Level

008QT/LF008QT 

to be installed a 

minimum of 6" 

above the flood 

rim if applied for 

general plumbing 

applications.

6"

Strainer  

recommended to 

prevent fouling of 

the check assembly 

and resultant spillage 

during start up and  

repressurizing.

Installations

Installation Requirements

1.

  Install a minimum of 1" above flood level of fixture if factory deck 

mounted or a minimum of 6" if general plumbing application.

2.

  Install bonnet side up and allow for accessibility for testing/ser-

vice. Do not install in concealed locations or areas where water 

leakage can cause damage due to normal wear of the internal 

parts.

3.

  Do not undersize supply or oversize the valve in relation 

to demand.

4.

 Do not install where backpressure can occur.

5.

  Protect assembly from freezing. 

Note: Use “L” suffix for left-hand outlet.

6.

  The installation of a strainer ahead of the backflow preventer 

is recommended to prevent fouling of the check assembly and 

resultant spillage from the valve during start up and repressuring.

Testing

For field testing procedure, refer to Watts installation sheets  

IS-TK-DP/DL, IS-TK-9A, IS-TK-99E and IS-TK-99D found on 

www.watts.com.

For other repair kits and service parts, refer to our Backflow 

Prevention Products Repair Kits & Service Parts price list  

PL-RP-BPD found on 

www.watts.com.

For technical assistance, contact your local Watts representative.

Local building or plumbing codes may require modifications to 

the information provided.  You are required to consult the local 

building and plumbing codes prior to installation.  If this informa-

tion is not consistent with local building or plumbing codes, the 

local codes should be followed.

Need for Periodic Inspection/Maintenance:

  This product 

must be tested periodically in compliance with local codes, but 

at least once per year or more as service conditions warrant.  

Corrosive water conditions, and/or unauthorized adjustments 

or repair could render the product ineffective for the service in-

tended.  Regular checking and cleaning of the product’s internal 

components helps assure maximum life and proper product 

function. 

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Summary of Contents for 008QT Series

Page 1: ...f the backflow preventer is recommended to prevent fouling of the check assembly and resultant spillage from the valve during start up and repressuring Testing For field testing procedure refer to Watts installation sheets IS TK DP DL IS TK 9A IS TK 99E and IS TK 99D found on www watts com For other repair kits and service parts refer to our Backflow Prevention Products Repair Kits Service Parts p...

Page 2: ...mpany shall not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other cir...

Page 3: ...stallation d un filtre en amont du dispositif anti refoulement est recommandée pour éviter les déversements dans la vanne anti retour et la contamination qui en résulterait lors de la repres surisation Essais Pour la procédure d essais sur le terrain reportez vous aux fiches d installation Watts IS TK DP DL IS TK 9A IS TK IS TK 99E et IS TK 99D disponibles sur www watts com Pour les autres kits de...

Page 4: ...eraient endommagés par suite du fonctionnement incorrect dudit produit d autres coûts résultant de frais de main d oeuvre de retards de vandalisme de négligence d une obstruction causée par des corps étrangers de dommages causés par une eau impropre des produits chimiques ou par tout autre événement échappant au contrôle de la Société La présente garantie est déclarée nulle et non avenue en cas d ...

Reviews: