background image

the PM series sensor to the terminal block  terminals 

24VAC, COMMON, 

and PM

 and also to the grounding bar. This will be a Class 2, 24 VAC 

circuit. See 

"Terminal Block Wire Insertion Detail"

 on reverse.

5.   Make wire connection between the contactor 

T1 and T2

 terminals and 

the ProMelt mats/cables.

Wiring CP series panels to be "Extension Panels".

A CP series panel can be used in conjunction with another CP series 
panel to serve as an "extension panel". Follow the steps below for 
proper installation:
1.   Provide 120, 208, 240, or 277 VAC circuits to the panel contactor(s)  

L1 and L2

 terminals as required by the rating of the ProMelt snow 

melting mats/cables connected to this circuit.

2.  For 120, 208, and 240 VAC systems, the COM lead from the transformer 

comes prewired to contactor 

C1

 terminals 

L1

. Connect the transformer 

lead wire matching the contactor voltage supplied to 

C1

 terminal 

L2

Please see transformer color chart below.

3.   Use a 2-conductor cable to make connections between terminals 

24VAC and PM

 in the "extension" panel and terminals 

X1 and X2

 in the 

"main" CP series panel.. This will be a Class 2, 24 VAC circuit.

4.   Make wire connection between the contactor 

T1 and T2

 terminals and 

the ProMelt mats/cables.

Note:  Do not connect a sensor to the "extension" panel.  The sensor 

connected to the "main" panel will operate both panels.

Instructions for Installing ProMelt

Contactor Pro Relay Panels

For ProMelt CP-50, CP-100, and CP-200 Panels

The CP-50, CP-100, and CP-200 are turn-key panels for activating a 

ProMelt snow melting system when used in conjunction with the ProMelt 

series of controls. They allow simple connection from the circuit breaker 

panel and have a manual override timer and heating indicator. Any CP 

series panel can be used as an "extension" panel that connects to another 

CP series panel and allows additional circuits to be controlled.

The ProMelt Contactor Pro Relay Panel is available in three configurations. 

CP-50 (single contactor), CP-100 (dual contactors), and CP-200 (quad con-

tactors).

Installation 

General

   These panels must be installed in accordance with local building  

codes, the National Electrical Code, or Canadian Electrical Code by  
qualified persons. 

   Disconnect power from all circuits prior to making  

any connections.

   Do not energize circuits until all connections are made and all 

ProMelt mats/cables are fully installed and covered as required.

   Read and follow the installation instructions for both the ProMelt 

snow melt mat/cable and the ProMelt sensor for additional information.

   Mount the panel indoors on a wall or equivalent. Do not place in a con-

fined air space where heat is not able to escape, such as a small closet.

   Properly secure the panel to the wall using the mounting holes provided.
  Wire the panel according to the provided schematics.
   A GFEP (Ground Fault Equipment Protection) type circuit breaker 

must be used 

to protect each ProMelt circuit. Size circuits for 125% 

of the load.

   This panel must be bonded to ground, as well as all conduit, junction 

boxes and other associated items per local code.

Wiring CP series panels

1.   Provide 120, 208, 240, or 277 VAC circuits to the panel contactor(s)  

L1 and L2

 terminals as required by the rating of the ProMelt snow 

melting mats/cables connected to this circuit. As shown in the wiring 
schematics, the panel draws internal power from Contactor 

C1

  

terminals, so make sure power is supplied to this contactor.

2.   For 120, 208, and 240 VAC systems, the COM lead from the transformer 

comes prewired to contactor 

C1

 terminal 

L1

. Connect the transformer 

lead wire matching the contactor voltage supplied to 

C1

 terminal 

L2

Please see transformer color chart, below right.

3.   For 277 VAC systems, a separate 120 VAC circuit will need to be  

supplied to the transformer 120 VAC and 

COM

 lead wires directly. This 

may be a standard 15 A or 20 A circuit.

4.   Use outdoor rated 4-conductor cable to make connections between  

this panel and the sensor selected. See the wiring schematic and 
instructions provided with the sensor for proper connections. Connect 

Control Descriptions

Control

No. Contactors Max. Amp Load

Contactor Pro CP-50

1

50

Contactor Pro CP-100

2

100

Contactor Pro CP-200

4

200

!  

CAUTION: 

  Incorrect voltage supplied to the transformer  
may cause damage, fire, or shock.

IS-WR-PM-Contactor-Pro-Panels

Transformer Colors

Primary Voltage

Lead Colors

120 Volts

Black & White

208 Volts

Black & Red

240 Volts

Black & Orange

*277 Volts

No Transformer Connections

*  

See "Wiring CP series panels" Section, Step 3 for 277VAC connections. 

Reviews: