background image

WEG  is  not  liable  for  the  misapplication  or  incorrect 
installation  of  its  products.The  user  is  cautioned  to 
observe all recommendations, warnings and cautions 
relating  to  the  safety  off  personal  and  equipment  as 
well  as  general  and  local  health  and  safety  laws, 
codes and procedures.

1. CIRCUIT BREAKER INSTALLATION

Make sure that the equipment is suitable for the installation by 
comparing nameplate ratings with system requirements. Inspect the 
equipment for completeness and check for any damage.

Dimensions for electrical and mechanical clearance to respect 
minimum distance from enclosure or compartment walls.

3. WIRE INSTALLATION 

See circuit breaker nameplate label for wire size and torque.

5. ACCESSORIES INSTALLATION (IF REQUIRED)

1) Turn off all power supplying this equipment before working on 
or inside equipment. 
Handle must be in TRIP position before opening cover.
2) Loosen two screws from the auxiliary cover and open it.
3) Install field-installable accessories according to instructions 
supplied with them.
4) Close the breaker cover and secure with screws.

6. OTHER SAFETY INSTRUCTIONS

Check area where circuit breaker is installed for any safety hazards
including personel safety and fire hazards. Exposure to certain 
types of chemicals can cause deterioration of electrical connections.

CAUTION

1) Each terminal connector or conductor should be connected as 
shown in the Fig. 5.
2) Do not allow conductor strands to interface with threads of wire 
binding screw.

FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT 
IN EQUIPMENT DAMAGE.

CAUTION

1) No circuit breaker should be reset until the cause of trip is known 
and the situation rectified.
2) Be careful not do damage the equipment during transportation or 
installation. 
3) Periodically check terminals and connectors for looseness or 
signs of overheating.

FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT 
IN EQUIPMENT DAMAGE.

Circuit breaker mounting steps:

1) For individual surface mounting, drill and tap mounting bolts holes 
according to the drilling plan shown in Fig. 2. For front mounted
applications, refer to Fig. 3 for correct dimensions.

2) If circuit breaker includes factory or field-installed internal 
accessories, make sure that accessory wiring can be reached 
when the circuit breaker is mounted.

3) Position circuit breaker on mounting surface.

4) Install circuit breaker using mounting screws provided with the 
product. Tighten hardware to 44 lb.in (5 N.m).

2. MANUAL OPERATION

Manual Operation of the circuit breaker is controlled by the circuit 
breaker handle and the TEST button. The circuit breaker has three 
positions, two of which are shown on the cover with raised lettering 
to indicate ON and OFF. The third position indicates a TRIP position 
and is between the ON and OFF positions. (See Fig. 4) 

Circuit Breaker Reset
After an automatic, accessory initiated trip, or manual TEST 
operation, the circuit breaker is reset by moving the circuit breaker 
handle to the OFF position.
NOTE) In the event of a thermal trip, the circuit breaker cannot be 
reset until the thermal element in the trip unit cools.

TEST button
The TEST button checks the tripping function and is used to 
manually trip the operating mechanism.
NOTE) Press TEST button once a year to trip circuit breaker.

90º

90º

1

4. CIRCUIT BREAKER REMOVAL

1) Turn off all power supplying this equipment before working on 
or inside equipment.
2) Remove circuit breaker in reverse order of installation.

If any questions arise, contact WEG or refer to the catalog for 
further information or instructions.

<FIG. 1> Clearence for Circuit Breaker

<FIG. 2> Circuit Breaker 
               Drilling Template

<FIG. 3> Circuit Breaker 
               Front view cut out

<FIG. 4> Circuit Breaker Manual controls

<FIG. 5> 

<FIG. 6> Operating Positions 

mm

in

mm

in

1,5 A/mm²

967.74 A/in²

Ø9

Ø0.35

 

28

1.1"

2

95...240 mm

3/0 AWG...400 kcmil

DWB600 UL : Suitable for continuous operation 
at 100 percent of rating only in used in a circuit 
breaker enclosure in a cubicle space 1200 mm 
x 600 mm x 400 mm (High x Width x Depth) or 
equivalent.

DWB600

DANGER

RISK OF ELECTRIC SHOCK, 
BURN OR EXPLOSION

FAILURE  TO  FOLLOW  THESE 
INSTRUCTIONS  WILL  RESULT 
IN DEATH OR SEVERE INJURY.

DANGER

RISK OF ELECTRIC SHOCK, 
BURN OR EXPLOSION

UL 489

10005143392

www.weg.net

WEG Automação

GARANTIA  /  WARRANTY  /  GARANTÍA  / 
GEWÄHRLEISTUNG:

A  WEG  oferece  garantia  limitada  contra  defeitos  de 
fabricação  ou  de  materiais  de  seus  produtos.  Para  mais 
informações acesse nosso site:
WEG  provides  a  limited  warranty  for  its  products  against 
defects in materials and workmanship. For more information 
access our site:
WEG ofrece garantía limitada contra defectos de fabricación 
o de materiales de sus productos. Para más informaciones 
acceda al WEB sitio:
WEG  bietet  eine  beschränkte  Gewährleistung  für  ihre 
Produkte  gegen  Herstellungs-  und  Materialfehler.  Für 
weitere Informationen besuchen Sie bitte unsere Webseite:

www.weg.net/warranty-automation

B

C

D

A

Phillips #2

M5 (5 N.m)

(44 lb.in)

DWB600 - 3P

70

2.76

230

9.05

120mm / 4.72”

Ø6mm / 0.24”

1

10mm / 4.33”

84mm / 3.30”

TRIP

CLACK

ON

1

OFF

3

2

1

3

0,7 N.m
6.2 lb.in

PHILLIPS #1

20 N.m
177 lb.in

ALLEN 15/64

Allen 3/8

55 N.m - 487 lb.in

Allen 3/16

20 N.m - 177 lb.in

30

1.18

13 (MAX)

0.51

50

1.97

25

70

2.76 

70

2.76 

66,5

2.62 

77,1

3.04

24,7
0.97 

210

8.27

323

12.72

107,7

4.24

97,7

3.85

1

12,6

4.43

145

5.71

104

4.09

103

4.06

ATENÇÃO:

- Desconecte da rede elétrica antes de proceder qualquer
trabalho neste equipamento.
- Somente profissionais qualificados podem efetuar a 
instalação e manutenção.
- Obedecer normas nacionais, estaduais, locais e
instruções de operação.

WARNING:

- Installation and maintence to be performed by
authorized personnel only.
- User is cautioned to observe all recommendations,
warnings and cautions relating to safety of personnel
and equipment as well as general and local health and safety
laws, codes and procedures.

0.98

Minimum distance

A

50 mm / 1.97"

B

20 mm / 0.79"

C

20 mm / 0.79"

D

20 mm / 0.79"