WEG is not liable for the misapplication or incorrect
installation of its products.The user is cautioned to
observe all recommendations, warnings and cautions
relating to the safety off personal and equipment as
well as general and local health and safety laws,
codes and procedures.
1. CIRCUIT BREAKER INSTALLATION
Make sure that the equipment is suitable for the installation by
comparing nameplate ratings with system requirements. Inspect the
equipment for completeness and check for any damage.
Dimensions for electrical and mechanical clearance to respect
minimum distance from enclosure or compartment walls.
3. WIRE INSTALLATION
See circuit breaker nameplate label for wire size and torque.
5. ACCESSORIES INSTALLATION (IF REQUIRED)
1) Turn off all power supplying this equipment before working on
or inside equipment.
Handle must be in TRIP position before opening cover.
2) Loosen two screws from the auxiliary cover and open it.
3) Install field-installable accessories according to instructions
supplied with them.
4) Close the breaker cover and secure with screws.
6. OTHER SAFETY INSTRUCTIONS
Check area where circuit breaker is installed for any safety hazards
including personel safety and fire hazards. Exposure to certain
types of chemicals can cause deterioration of electrical connections.
CAUTION
1) Each terminal connector or conductor should be connected as
shown in the Fig. 5.
2) Do not allow conductor strands to interface with threads of wire
binding screw.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT
IN EQUIPMENT DAMAGE.
CAUTION
1) No circuit breaker should be reset until the cause of trip is known
and the situation rectified.
2) Be careful not do damage the equipment during transportation or
installation.
3) Periodically check terminals and connectors for looseness or
signs of overheating.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT
IN EQUIPMENT DAMAGE.
Circuit breaker mounting steps:
1) For individual surface mounting, drill and tap mounting bolts holes
according to the drilling plan shown in Fig. 2. For front mounted
applications, refer to Fig. 3 for correct dimensions.
2) If circuit breaker includes factory or field-installed internal
accessories, make sure that accessory wiring can be reached
when the circuit breaker is mounted.
3) Position circuit breaker on mounting surface.
4) Install circuit breaker using mounting screws provided with the
product. Tighten hardware to 44 lb.in (5 N.m).
2. MANUAL OPERATION
Manual Operation of the circuit breaker is controlled by the circuit
breaker handle and the TEST button. The circuit breaker has three
positions, two of which are shown on the cover with raised lettering
to indicate ON and OFF. The third position indicates a TRIP position
and is between the ON and OFF positions. (See Fig. 4)
Circuit Breaker Reset
After an automatic, accessory initiated trip, or manual TEST
operation, the circuit breaker is reset by moving the circuit breaker
handle to the OFF position.
NOTE) In the event of a thermal trip, the circuit breaker cannot be
reset until the thermal element in the trip unit cools.
TEST button
The TEST button checks the tripping function and is used to
manually trip the operating mechanism.
NOTE) Press TEST button once a year to trip circuit breaker.
90º
90º
1
4. CIRCUIT BREAKER REMOVAL
1) Turn off all power supplying this equipment before working on
or inside equipment.
2) Remove circuit breaker in reverse order of installation.
If any questions arise, contact WEG or refer to the catalog for
further information or instructions.
<FIG. 1> Clearence for Circuit Breaker
<FIG. 2> Circuit Breaker
Drilling Template
<FIG. 3> Circuit Breaker
Front view cut out
<FIG. 4> Circuit Breaker Manual controls
<FIG. 5>
<FIG. 6> Operating Positions
mm
in
mm
in
1,5 A/mm²
967.74 A/in²
Ø9
Ø0.35
28
1.1"
2
95...240 mm
3/0 AWG...400 kcmil
DWB600 UL : Suitable for continuous operation
at 100 percent of rating only in used in a circuit
breaker enclosure in a cubicle space 1200 mm
x 600 mm x 400 mm (High x Width x Depth) or
equivalent.
DWB600
DANGER
RISK OF ELECTRIC SHOCK,
BURN OR EXPLOSION
FAILURE TO FOLLOW THESE
INSTRUCTIONS WILL RESULT
IN DEATH OR SEVERE INJURY.
DANGER
RISK OF ELECTRIC SHOCK,
BURN OR EXPLOSION
UL 489
10005143392
www.weg.net
WEG Automação
GARANTIA / WARRANTY / GARANTÍA /
GEWÄHRLEISTUNG:
A WEG oferece garantia limitada contra defeitos de
fabricação ou de materiais de seus produtos. Para mais
informações acesse nosso site:
WEG provides a limited warranty for its products against
defects in materials and workmanship. For more information
access our site:
WEG ofrece garantía limitada contra defectos de fabricación
o de materiales de sus productos. Para más informaciones
acceda al WEB sitio:
WEG bietet eine beschränkte Gewährleistung für ihre
Produkte gegen Herstellungs- und Materialfehler. Für
weitere Informationen besuchen Sie bitte unsere Webseite:
www.weg.net/warranty-automation
B
C
D
A
Phillips #2
M5 (5 N.m)
(44 lb.in)
DWB600 - 3P
70
2.76
230
9.05
120mm / 4.72”
Ø6mm / 0.24”
1
10mm / 4.33”
84mm / 3.30”
TRIP
CLACK
ON
1
OFF
3
2
1
3
0,7 N.m
6.2 lb.in
PHILLIPS #1
20 N.m
177 lb.in
ALLEN 15/64
Allen 3/8
55 N.m - 487 lb.in
Allen 3/16
20 N.m - 177 lb.in
30
1.18
13 (MAX)
0.51
50
1.97
25
70
2.76
70
2.76
66,5
2.62
77,1
3.04
24,7
0.97
210
8.27
323
12.72
107,7
4.24
97,7
3.85
1
12,6
4.43
145
5.71
104
4.09
103
4.06
ATENÇÃO:
- Desconecte da rede elétrica antes de proceder qualquer
trabalho neste equipamento.
- Somente profissionais qualificados podem efetuar a
instalação e manutenção.
- Obedecer normas nacionais, estaduais, locais e
instruções de operação.
WARNING:
- Installation and maintence to be performed by
authorized personnel only.
- User is cautioned to observe all recommendations,
warnings and cautions relating to safety of personnel
and equipment as well as general and local health and safety
laws, codes and procedures.
0.98
Minimum distance
A
50 mm / 1.97"
B
20 mm / 0.79"
C
20 mm / 0.79"
D
20 mm / 0.79"