background image

Recommended

Rack

Configurations

Ultrastar® Data102

Regulatory Model:  H4102-J

December 2020

Rev. 1.3

1ET1639

Summary of Contents for H4102-J

Page 1: ...Recommended Rack Configurations Ultrastar Data102 Regulatory Model H4102 J December 2020 Rev 1 3 1ET1639 ...

Page 2: ...ecommended Racks 5 Vertical Rack Rail Settings 6 Recommended PDUs and Available Installation Space 7 Chapter 2 CMA Standard Rack Specifications 10 CRENLO EMCOR 11 AFCO Legrand 11 TRIPP LITE 12 APC Schneider 13 Chapter 3 CMA Lite Rack Specifications 14 CRENLO EMCOR 15 AFCO Legrand 15 TRIPP LITE 16 APC Schneider 17 Chapter 4 Installation 18 PDU Mounting Bracket Installation KIT MBVPT 1B 19 PDU Mount...

Page 3: ... Revision History Date Revision Comment March 2018 Revision 1 0 Initial Release February 2019 Revision 1 1 Added CMA Lite December 2019 Revision 1 2 Rebranded document to WD design December 2020 Revision 1 3 Added UK Import Representation Contact ii ...

Page 4: ...e be prepared to provide the following information part number P N serial number S N product name and or model number and a brief description of the issue Email support wdc com Website https portal wdc com Support s UK Import Representation Contact Western Digital UK Limited Hamilton House Regent Park Kingston Road Leatherhead Surrey KT22 7PL GB United Kingdom Telephone 44 1372 366000 iii ...

Page 5: ...se or non infringement Each user of this document or any product referred to herein also expressly agrees Western Digital shall not be liable for any incidental punitive indirect special or consequential damages including without limitation physical injury or death property damage lost data loss of profits or costs of procurement of substitute goods technology or services arising out of or related...

Page 6: ...ew of rack requirements and recommendations In This Chapter Ultrastar Data102 Rack Requirements 2 Rack Safety 3 CMA Standard Recommended Racks 4 CMA Lite Recommended Racks 5 Vertical Rack Rail Settings 6 Recommended PDUs and Available Installation Space 7 1 ...

Page 7: ...d This may be a potential tipping hazard depending on the configuration of the rack Ensure that leveling feet anti tilt and any other safety features recommended by the specific rack manufacturers have been deployed before servicing The following section provides specific information necessary to install service and remove the Ultrastar Data102 The installation of the Ultrastar Data102 requires tw...

Page 8: ...ployed before servicing The handles on the front of the chassis are not intended to be used to support the weight of the Ultrastar Data102 Lifting the unit by the chassis handles or trying to support the unit on the handles can cause them to fail This can cause serious damage to the unit or serious bodily harm to those handling the unit Always team lift the chassis by gripping the underside of the...

Page 9: ...ons Notes AS 160099 03 42 H 2060mm x W 600mm x D 1200mm H 81 1in x W 23 6in x D 47 2in N A EMCOR CRENLO DC 42U2448 G 42 H 2057mm x W 600mm x D 1270mm H 80 98in x W 23 6in x D 50in N A WEDIT602 52 H 2989 2mm x W 609 6mm x D 1317 6mm H 98in x W 24in x D 51 9in N A WEDIT603 48 H 2311 4mm x W 609 6mm x D 1317 6mm H 91in x W 24in x D 51 9in N A WEDIT604 45 H 2178 1mm x W 609 6mm x D 1317 6mm H 85 75in ...

Page 10: ... Recommended Racks The following is a list of racks that are recommended for the Ultrastar Data102 using CMA Lite Table 3 Recommended Racks Vendor Part Number Rack Units Dimensions Notes AS 160099 03 42 H 2060mm x W 600mm x D 1200mm H 81 1in x W 23 6in x D 47 2in N A EMCOR CRENLO DC 42U2448 G 42 H 2057mm x W 600mm x D 1270mm H 80 98in x W 23 6in x D 50in N A WEDIT602 52 H 2989 2mm x W 609 6mm x D ...

Page 11: ...x D 1317 6mm H 80 5in x W 24in x D 51 8in The enclosure cannot be installed into the U spaces that are in line with the front door stiffeners or the door latch in the CMA Lite configuration WEDIT606 51 H 2444 8mm x W 609 6mm x D 1317 6mm H 96 25in x W 24in x D 51 8in The enclosure cannot be installed into the U spaces that are in line with the front door stiffeners or the door latch in the CMA Lit...

Page 12: ...sure rails can be extended or retracted to best fit these adjustments Refer to the specific rack manufacturer documentation for instructions on how to adjust the vertical rack rails on the chosen rack Both front vertical rack rails should be adjusted to a depth of 41mm 1 61in from the front of the rack frame as shown in the image below Figure 3 Front Vertical Rack Rails Both rear vertical rack rai...

Page 13: ...ng W 56mm x D 190mm W 2 2in x D 7 5in WEDIT602 WEDIT603 WEDIT604 WEDIT605 AFCO Legrand WEDIT606 Rear or Inward Facing W 67mm x D 200mm W 2 6in x D 7 9in APC Schneider AR3300 Rear Facing W 60mm x D 113mm W 2 4in x D 4 4in TRIPP LITE w Rack Extender Rack SR42UBDP Extender SREXTENDER Rear or Inward Facing W 60mm x D 120mm W 2 4in x D 4 7in The following image displays the available zero space for mou...

Page 14: ...Recommended Rack Configurations 1 Overview 1 6 Recommended PDUs and Available Installation Space Figure 5 PDU in the Zero Space 9 ...

Page 15: ...ommended rack models compatible PDUs and required accessories and hardware using CMA Standard Each rack recommendation comes with information specific to what PDUs are approved and what hardware is required to mount them In This Chapter CRENLO EMCOR 11 AFCO Legrand 11 TRIPP LITE 12 APC Schneider 13 10 ...

Page 16: ...5mm 2 18in 86 15mm 3 39in Rear Table 7 Required Accessories and Hardware Supplier Part Number QTY Description Server Technology KIT MBVPT 1B 1 PDU Mounting Bracket M6 x 16 Hex Cap Screws 4 N A M6 Fender Washers 8 N A Generic Various M6 Hex Nut with Nylon Lock 4 N A 2 2 AFCO Legrand Table 8 Recommended AFCO Legrand Rack Models Model Number Rack Units Dimensions WEDIT602 52 H 2989 2mm x W 609 6mm x ...

Page 17: ...ommended TRIPP LITE Rack Models Model Number Rack Units Dimensions SR42UBDP 42U H 1111 25mm x W 601 98mm x D 1200mm H 43 75in x W 23 7in x D 47 2in Table 12 Recommended TRIPP LITE Rack Extender Models Model Number Rack Units Dimensions SREXTENDER 42U Shipping Dimensions H 236 22mm x W 1206 5mm x D 203 2mm H 9 3in x W 47 5in x D 8 in Assembled Dimensions H 1866 9mm x W 601 98mm x D 200 66mm H 73 5i...

Page 18: ...ENDER 1 Rack Extension 2 4 APC Schneider Table 15 Recommended APC Schneider Rack Models Model Number Rack Units Dimensions AR3300 42 H 1991mm x W 600mm x D 1222mm H 78 4in x W 23 6in x D 48 18in Table 16 Compatible PDUs PDU Model Number Width Depth Orientation STV 4501 55 5mm 2 18in 86 15mm 3 39in Rear STV 4502 55 5mm 2 18in 86 15mm 3 39in Rear Server Technology STV 4503 55 5mm 2 18in 86 15mm 3 39...

Page 19: ...ommended rack models compatible PDUs and required accessories and hardware using CMA Lite Each rack recommendation comes with information specific to what PDUs are approved and what hardware is required to mount them In This Chapter CRENLO EMCOR 15 AFCO Legrand 15 TRIPP LITE 16 APC Schneider 17 14 ...

Page 20: ...m 2 18in 86 15mm 3 39in Rear Table 20 Required Accessories and Hardware Supplier Part Number QTY Description Server Technology KIT MBVPT 1B 1 PDU Mounting Bracket M6 x 16 Hex Cap Screws 4 N A M6 Fender Washers 8 N A Generic Various M6 Hex Nut with Nylon Lock 4 N A 3 2 AFCO Legrand Table 21 Recommended AFCO Legrand Rack Models Model Number Rack Units Dimensions WEDIT602 52 H 2989 2mm x W 609 6mm x ...

Page 21: ...mended TRIPP LITE Rack Models Model Number Rack Units Dimensions SR42UBDP 42U H 1111 25mm x W 601 98mm x D 1200mm H 43 75in x W 23 7in x D 47 2in Table 25 Recommended TRIPP LITE Rack Extender Models Model Number Rack Units Dimensions SREXTENDER 42U Shipping Dimensions H 236 22mm x W 1206 5mm x D 203 2mm H 9 3in x W 47 5in x D 8 in Assembled Dimensions H 1866 9mm x W 601 98mm x D 200 66mm H 73 5in ...

Page 22: ...DER 1 Rack Extension 3 4 APC Schneider Table 28 Recommended APC Schneider Rack Models Model Number Rack Units Dimensions AR3300 42 H 1991mm x W 600mm x D 1222mm H 78 4in x W 23 6in x D 48 18in Table 29 Compatible PDUs PDU Model Number Width Depth Orientation STV 4501 55 5mm 2 18in 86 15mm 3 39in Rear STV 4502 55 5mm 2 18in 86 15mm 3 39in Rear Server Technology STV 4503 55 5mm 2 18in 86 15mm 3 39in...

Page 23: ...Western Digital Installation In This Chapter PDU Mounting Bracket Installation KIT MBVPT 1B 19 PDU Mounting Bracket Installation KIT MB 40 25 18 ...

Page 24: ...k Rail Settings page 6 Table 31 Procedure Info Required Tools Required Parts of People Required Torx T15 Screwdriver Two Flat Brackets Two Right Angle Brackets Two Backer Plates M6 x 16 Hex Cap Screws M6 Fender Washers M6 Hex Nut with Nylon Lock 1 Step 1 Install the bottom side bracket using the provided hardware a Locate the two screw holes at the bottom of the back side of the PDU b Align the fl...

Page 25: ...hind the flat bracket over the holes on the left hand side of the flat bracket e Slide the washers onto the mounting bolts and secure the right angle bracket to the backer plate through the flat bracket Before fully tightening the bolts ensure that the right angle bracket is flush with the edge of the PDU before tightening Figure 8 Right Angle Bracket Installation bottom 20 ...

Page 26: ...T 1B Figure 9 Right Angle Bracket Installed bottom Figure 10 Flush Right Angle Bracket bottom Step 2 Install the top side bracket using the provided hardware a Locate the two screw holes at the top of the back side of the PDU b Align the flat bracket with the two top PDU screw holes as shown 21 ...

Page 27: ...wn in the image below Figure 12 Flat Bracket Installation top d Align the right angle bracket behind the flat bracket over the holes on the left hand side of the flat bracket e Slide the washers onto the mounting bolts and secure the right angle bracket to the backer plate through the flat bracket Before fully tightening the bolts ensure that the right angle bracket is flush with the edge of the P...

Page 28: ...Recommended Rack Configurations 4 Installation 4 1 PDU Mounting Bracket Installation KIT MBVPT 1B Figure 13 Right Angle Bracket Installation top Figure 14 Right Angle Bracket Installed top 23 ...

Page 29: ...he top vertical rail with the provided bolts and nuts Before fully tightening the bolts ensure that the plug side of the PDU is 145mm 5 7in away from the rear rack rail Figure 16 PDU Distance from Rack Rear Rail c Locate the bottom row of holes on the bottom vertical rail d Secure the right angle bracket on the top vertical rail with the provided bolts and nuts Before fully tightening the bolts en...

Page 30: ...k Rear Rail 4 2 PDU Mounting Bracket Installation KIT MB 40 The installation of PDU mounting bracket kit KIT MB 40 for the AFCO TRIPPLITE and CRENLO racks extends the PDUs farther back in the rack to allow for more room for the CMA and enclosure The PDU Bracket Installation procedure should be completed after the installation of the system rails and cables 25 ...

Page 31: ...ttings page 6 Table 32 Procedure Info Required Tools Required Parts of People Required 2 Philips Screwdriver Torx T10 Screwdriver Two 90 degree angle brackets for 56 mm wide PDUs Four M4 x 6mm screws 1 Step 1 Remove the PDU mounting buttons from the back of the PDU a Locate the PDU mounting buttons on the rear of the PDU There is one at the top and one at the bottom 26 ...

Page 32: ...T MB 40 Figure 19 Locate PDU Mounting Buttons b Remove the screws that secure the PDU mounting buttons using the 2 Philips Screwdriver Step 2 Mount the PDU mounting buttons onto the angle bracket a Secure the PDU mounting button to the center hole of the long side of the angle bracket 27 ...

Page 33: ...ep 3 Install the angle bracket to the bottom of the PDU using the provided hardware a Locate the middle set of holes on the back side of the PDU b Align the short side of the angle bracket over the two middle PDU mounting holes on the rear of the PDU The long side of the right angle bracket should be on the left back side of the PDU c Secure the angle bracket to the PDU by using the screws provide...

Page 34: ... using the provided hardware a Locate the two screw holes at the top of the back side of the PDU b Align the short side of the angle bracket over the two top PDU mounting holes on the rear of the PDU The long side of the right angle bracket should be on the left back side of the PDU c Secure the angle bracket to the PDU by using the screws provided in the PDU mounting kit as shown in the image bel...

Page 35: ...0 Figure 22 Install the Angle Bracket on the PDU Top Step 5 Install the PDU into the rear of the rack a Locate the middle set of keyholes on the rear vertical rack rails b Align the PDU mounting buttons with the keyholes on the rear vertical rack rails and slide down until the PDU is secure 30 ...

Page 36: ...Recommended Rack Configurations 4 Installation 4 2 PDU Mounting Bracket Installation KIT MB 40 Figure 23 Align PDU with Keyholes 31 ...

Page 37: ...stallation KIT MB 40 Figure 24 PDU Installed into Keyholes c Verify that the PDU is secure by pressing on the front of the PDU If the PDU does not shift it is properly mounted If the PDU does shift remove the PDU and repeat the PDU installation step to ensure it is secure 32 ...