Thank you for using our products.

 

Long 

Branch, 

NJ 

 

07740 

         

 

INSTALLATION 

INSTRUCTIONS 

(800)  631-2148 (USA)         SERIES HS4-24MCW MULTI-CANDELA FOUR WIRE APPLIANCES 
(800) 

 

397-5777 

(CANADA) 

        (WALL 

MOUNT 

VERSIONS) 

www.wheelockinc.com          

   

 

Use this product according to this instruction manual.  Please keep this instruction manual for future reference. 

GENERAL: 

Wheelock’s Series HS4-24MCW Multi-Candela Horn Strobe provides four selectable candela settings (15, 30, 75, 110).  The HS4-24MCW allows for independent 
operation of the strobe circuit and the horn circuit.  It is the ideal choice for retrofit applications as well as new installations.  The HS4-24MCW appliance is UL Listed 
under Standard 1971 for Signaling Applicances for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. The HS4-24MCW is also ULC Listed 
under Standard CAN/ULC-S526-02 for Visual Signaling Appliances and Standard CAN/ULC-S525-99 for Audible Signaling Appliances for Fire Alarm Systems.  It is 
listed for 

indoor use only

 and can be mounted to double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See wiring and mounting 

information).  This appliance is listed for 

wall mounting only

.  The HS4-24MCW appliance uses a xenon flashtube with solid state circuitry enclosed in a polycarbonate 

lens to provide maximum visibility and reliability for effective visible signaling. 

 

The horn portion of the HS4-24MCW appliance can be field set to provide either a continuous horn when connected directly to the fire alarm control panel (FACP), or a 
synchronized code 3 horn when used in conjunction with the Sync Module (SM), Dual Sync Module (DSM) or Wheelock power supplies.  The horn can be field set to 
provide either high (HI) dBA, medium (MED) dBA or low (LO) dBA sound output.   

NOTE:

  The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and 

NFPA 72 for standard emergency evacuation signaling.  

The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose. 

 

The HS4-24MCW is designed for use with either filtered DC or unfiltered full-wave-rectified (FWR) input voltage.  All inputs are polarized for compatibility with 
standard reverse polarity supervision of circuit wiring by an FACP. 

 

NOTE:  

All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems – CAN/ULC-S524-01 and Canadian 

Electrical Code, Part 1.  Final acceptance is subject to authorities having jurisdiction (AHJ). 

WARNING:  PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION OF 
THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR 
OTHERS. 

 

SPECIFICATIONS: 

Table 1: UL/ULC Listed Models and Ratings

 

 

Model 

Regulate 

Voltage 

(VDC/VRMS) 

Voltage Range 

Limit Per UL 1971 

(VDC/VRMS) 

Voltage Range Per 

CAN/ULC-S526-02 

(VDC/VRMS) 

Strove  

Candela 

(cd) 

HS4-24MCW 24 

16.0-33.0 

20.0-31.0  15/30/75/110 

 

Table 2:  dBA Sound Output for 24VDC Models 

Reverberant Per UL 464 

Anechoic dBA @ 10 Ft. Per CAN/ULC-S525-99 

 

Description 

 

Volume 

16.0VDC 24VDC 

33.0VDC 

20.0VDC  24VDC  31.0VDC 

 Low 

80  83 86 88  90 

91 

Continuous Horn 

Medium 

85 

88 

91 

93 

95 

97 

 High  88  91 93 97  99  100 
 Low 

75  79 82 88  90 

91 

Code 3 Horn 

Medium 

80 

84 

86 

93 

95 

97 

 High  84  87 89 97  99  100 

 

Figure 1:  ULC Directional Characteristics 

81dB

83dB

-6dB

-3dB

95dB

-3dB

-6dB

85dB

-3dB

-3dB

-6dB

95dB

-6dB

20° 30°

80°

30°

27°

60°

48°

 

NOTES:   

1.

 

The strobe will produce 1 flash per second over the "Regulated Voltage" 
range.   

2.

 

This horn/strobe model meets the required light distribution patterns 
defined in UL 1971 and ULC-S526-02.   

3.

 

This model is UL/ULC Listed for indoor use with a temperature range of 
+32

°

F to +120

°

F (0

°

C to +49

°

C) and maximum humidity of 93% 

±

 2% 

RH.  The effect of shipping and storage temperatures shall not adversely 
affect the performance of the appliance when it is stored in the original 
cartons and not subjected to misuse or abuse. 

When calculating the total current:  Use Tables 3 & 3A to determine the highest value of “RMS Current” for an individual HS4 then multiply the value by the total 
number of HS4 Appliances.  Be sure to add the currents for any other appliances powered by the same source and to include any required safety factors. 

NOTE:  

The maximum number of strobes on a single notification appliance circuit shall not exceed 50. 

CAUTION:  

These notification appliances are UL Listed as “Regulated”.  They are intended to be used with FACPs whose notification circuits are UL Listed as 

“Regulated.”  These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the 
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.

 

 

Summary of Contents for HS4-24MCW Series

Page 1: ...nce with the Canadian Standard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is subject to authorities having jurisdiction AHJ WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION CANDELA SETTING ...

Page 2: ... R STR J3 AUD T B 1 3 J2 C O E D J1 H L M B P83511 AH C1 R5 TOP 75 30 15 110 CANDELA SELECTOR CANDELA POINTER 3 J2 C O E D J1 H L M Factory setting is on 15 candela Medium dB and Code 3 WARNING THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING T...

Page 3: ...r easy installation and minimum stress on the product from wiring MOUNTING PROCEDURES 1 This HS4 model can be flush mounted to a 100mm backbox Figure A or double gang backbox Figure B It can also be surface mounted to a indoor outdoor backbox Figures C D Mounting hardware for each mounting option is supplied 2 Conduit entrances to the backbox should be selected to provide sufficient wiring clearan...

Page 4: ... at the time of installation and at least twice a year or more often and in accordance with local state and federal codes regulations and laws Specification application installation operation maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association NFPA Underwriters Laboratories UL Underwriters L...