075-0

60706-209

INSTALLATION AND 

OPERATORS MANUAL

PACKAGED STANDBY

SYSTEM

ULPSS12H2W/E

Summary of Contents for ULPSS12H2E

Page 1: ... 11075 01 60706 209 INSTALLATION AND OPERATORS MANUAL PACKAGED STANDBY SYSTEM ULPSS12H2W E ...

Page 2: ...ous situ ation which if not avoided will result in death or serious injury This signal word is to be limited to the most extreme situations WARNING WARNING inducates a potentially hazardous situ ation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a potentially hazardous situ ation which if not avoided may result in minor or moderate injury It may also be us...

Page 3: ...led These packaged standby systems consist ot two major components 1 AUTOMATIC TRANSFER SWITCH A wall mounted ASCO 165 Automatic Transfer Switch ATS designed for inside installation The transfer switch is UL1008 approved A fourteen day electronic exerciser circuit is installed in the ATS as standard equipment The ATS also contains the power failure sensing circuitry necessary to start and stop the...

Page 4: ... line that is required to supply the engine with a constant fuel pressure and volume LIQUID PROPANE VAPOR LP Refer to the tables below for fuel line size and rec ommended tank size For distances of 100 feet or over a two regulator fuel system is recommended This is accomplished by installing a primary regula tor at the tank which will reduce the tank pressure down to 10 to 15 lbs A low pressure re...

Page 5: ...other metal objects 2 Use tools with insulated handles 3 Check both the battery cable ends and the bat tery posts to be sure they are free of corrosion 4 Always connect the battery positive cable first and then connect the battery negative cable When removing the battery cables from the bat tery reverse the procedure disconnect the nega tive cable first and then the positive cable 5 Be sure all co...

Page 6: ...100 amps If you have a 125 150 200 amp or larger system and want to use a 100 amp transfer switch you will not be able to transfer the complete electrical system In this case it will be necessary to install a secondary emergency distribution panel NOTE THE MAXIMUM OUT PUT OF THE GENERATOR IS 50 AMPS AT 240 VOLTS AC ELECTRICAL CONNECTIONS NOTICE CLASS 1 WIRING METHODS ARE TO BE USED FOR ALL FIELD W...

Page 7: ...ected to the terminals L2 L6 The normal line power terminals in the ATS are marked PREFERRED L1 L5 The hot line power leads are L1 and L3 from your normal power supply are connected to terminals L1 and L5 The load terminals in the ATS are marked LOAD L3 L7 The leads to the load distribution panel are connected to terminals L3 L7 The neutral leads from all three locations are con nected to the isol...

Page 8: ... off mode the engine generator set will not start or run automatically GENERATOR EXERCISER CIRCUIT The automatic generator exerciser is configured to automatically exercise the generator for 20 minutes once every 14 days In order to set and test the exercise circuit the engine control module must be set in the auto mode SETTING THE EXERCISER CIRCUIT Press and release the Automatic Generator Exer c...

Page 9: ...ompatible engine ECU PAGE Pressing this button scrolls the display to show the various instruments FRONT PANEL CONFIGURATION 1 2 3 4 This configuration mode allows the operator limited customizing of the way the module operates Use the module s navigation buttons to traverse the menu and make value changes to the parameters ACCEPT button 2 NEXT PAGE button DECREASE VALUE NEXT ITEM 4 INCREASE VALUE...

Page 10: ...larger are rec ommended In addition you should consider install ing an oil heater kit and a battery warmer for reliable starting during cold weather MAINTENANCE LOG DATE WORK PERFORMED 225 S CORDOVA AVE LECENTER MN 56057 507 357 6821 SERVICE DEPT 507 357 6831 DESCRIPTION AUXILIARY INPUTS Auxiliary inputs can be user configured and will display the message as written by the user FAIL TO START The e...

Page 11: ...11075 01 20 60706 209 21 11075 01 60706 209 ENGINE GENERATOR SET LAYOUT ULPSS12H2W E ENGINE GENERATOR SET PAD LAYOUT ...

Page 12: ... in the bottom of air cleaner from crankcase breather 10 Defective starter fuel solenoid relay s ENGINE STARTS AND THEN STOPS AND FAULT ICON COMES ON 1 Engine is low on oil 2 No AC output from generator to engage stop crank circuit ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS 1 Insufficient fuel volume getting to the unit a Fuel line too small b Low fuel pressure 2 AC short circuit 3 Wiring to...

Page 13: ...and fitness for a particular purpose are limited to 12 months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or conse quential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations may not app...