background image

SmartZone

 

 TM

                      

SPC (Static Pressure Controller) 

 

 

Air Pressure Sensing Switch 

 

For use with POC and RPOC Dampers 

 

Adjustable Air Switch Set Point Range 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GENERAL DESCRIPTION 

 

The 

SPC

 is a static pressure switch designed to sense positive pressure 

in the plenum for the purpose of controlling modulating bypass position. 

 

The  plated  housing  contains  a  diaphragm,  a  calibration  spring  and  a 

snap-acting SPDT switch. The barbed sample line connections located on 

each  side  of  the  diaphragm  accept  flexible  tubing.  The  enclosure  cover 

guards against accidental contact with the live switch terminal screws and 

the  set  point  adjusting  screw.  The  enclosure  cover  will  accept  a  ½" 

conduit connection. 

 

Pitot tube

 (air-probe) for mounting in plenum and 12 inches of flexible ¼” 

I.D. poly tubing included with each SPC. 

Specifications  

Mounting

 

Mount with the diaphragm in any 

vertical plane. (See Figure 3) 

Set Point

 

 

0.05 ± 0.02" w.c. to 2.0"w.c. 

Range

 

Field Adj.

 

 

0.07”w.c. to 2.0"w.c. 

Operate Range

 

Field Adj.

 

 

0.04”w.c. to 1.9"w.c. 

Release Range

 

Field Adj.

 

 

0.07”w.c. to 2.0"w.c. 

Operate Range

 

Approx. Switching

 

Progressive, increasing from 

Differential  

0.02 ± 0.01”w.c. at minimum set 

 

 

 

set point to 0.1w.c. at maximum  

 

 

 

set point. 

Measured Media

 

Air or combustion by-products  

 

 

 

that will not degrade silicone 

Maximum Pressure

 

½ psi (0.03 bar) 

Operating

 

 

-40ºF to 180ºF (-40ºC to 82ºC) 

Temperature

   

 

Electrical

 

 

300VA pilot duty at 115 to  

Rating 

 

 

277 VAC, 15 Amps non-inductive 

 

 

 

277 VAC @ 60Hz 

Contact

 

 

SPDT 

Arrangement

   

Sample Line

   

¼” Barbed connectors for  

Connections

   

flexible tubing 

Approval

 

 

UL, FM, CSA, CE 

 

 

Mounting 

Select  a  mounting  location  which  is  free  from  vibration.  The 

SPC 

must be mounted with the diaphragm in any vertical plane 

in order to obtain the lowest specified operating set point. Avoid 

mounting with the sample line connections in the "up" position. 

Surface mount via the two 3/16" diameter holes in the integral 

mounting  bracket.  The  mounting  holes  are  3-7/8"  apart.  (See 

Figure 3

)

 

 

 
 
 
Air Sample Connection 

The 

SPC 

is designed to accept flexible tubing by means of 

barbed 1/4” slip-on connections. A 12” piece of ¼” ID Flexible 

tubing is included with the SPC as well as a Pitot Tube for 

mounting in the plenum.  Locate the sampling probe a minimum 

of 2 feet downstream from the air source. Install the sampling 

probe as close to the center of the airstream as possible. Do not 

allow supply pressure to blow directly into the Pitot Tube.  

Connect the provided flexible tubing to the 

High-Pressure Inlet

 

as shown in 

Figure 2

.

 

 

 

Pitot Tube (Included) 