SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 1
ENGLISH
1.- INTRODUCTION
SNMP06 is a powerful and versatile communication LAN card for XMART online UPS. This card
includes functions as:
-
Communication for LAN Ethernet under protocols TCP/IP, UDP, SNMP, SMTP, SNTP, HTTP, HTTPS,
SSL, SSH, IPV4/IPV6, DHCP, etc.
-
Connection to external XMART environmental sensor to acquire and send temperature/humidity data
to the network.
-
10M/100M autodetection speed
-
Internal data logging up to 200.000 events/alarms
-
Interface to monitor and control main parameters of the UPS
2.- DESCRIPTION
A:
LAN Ethernet (10/100MB)
B:
Sensor
T/H
C:
Reset Jumper: To reestablish default values
1-2: Normal
2-3: Reset: Revise note 1
SNMP06 LAN CARD
REFERENCE MANUAL
_______________________________________________________
SNMP-06 (161212) 2
D:
LED green = ON: 100MB / OFF: 10MB
E:
LED yellow = ON: connection detected / OFF: connection not detected
NOTE 1: RESET:
Reset function reinitializes card with factory values. It also eliminates user passwords
To apply a reset follow next procedure:
1)
Remove card from UPS and set jumper between pins 2 & 3 (revise previous image)
2)
Insert card into the UPS and
wait during 5 minutes
meanwhile reset is performed.
3)
Remove card from UPS again and set jumper between pins 1 & 2.
4)
Reinsert card into the UPS and
wait during 5 minutes
meanwhile card restarts with factory
setting.
Factory setting after reset:
IP: 192.168.102.230 (STATIC IP) ;
Subnet Mask: 255.255.255.0 ; Default gateway: 192.168.102.1
Password: 12345678
3.- INSTALATION
1:
Remove cover from intelligent slot in the UPS
2:
Check jumper “C” is between pins 1 & 2 in the card
3:
Plug RJ45 cable in the Ethernet port of the card and connect other side to the network socket.
Check if yellow LED lights as expected.
If TH sensor is available, connect it to its related RJ11 port in the card according to next figure.
We strongly suggest to check TH sensor manual.
LAN
SENSOR TH
RJ11
RJ45