P91 / P91g Lead Acid Online UPS

1000VA, 2000VA, 3000VA Models

User & Installation Manual

www.xpcc.com

 

| © 2020 Xtreme Power Conversion Corporation. All rights reserved. (Rev 8/13/20)

Summary of Contents for P91-1000

Page 1: ...P91 P91g Lead Acid Online UPS 1000VA 2000VA 3000VA Models User Installation Manual www xpcc com 2020 Xtreme Power Conversion Corporation All rights reserved Rev 8 13 20 ...

Page 2: ...principle 6 2 3 Install the UPS 6 2 4 Setup the UPS 7 2 5 Battery Replacement 11 2 6 Battery Kit Assembly 12 3 Operations 15 3 1 Button operation 15 3 2 LCD Panel 15 3 3 Audible Alarm 16 3 4 LCD display wordings index 17 3 5 UPS Setting 18 3 6 Operating Mode Description 22 3 7 Faults Reference Code 23 3 8 Warning indicator 23 4 Troubleshooting 24 5 Storage and Maintenance 25 6 Specifications 26 7 ...

Page 3: ...s Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked for P91g models or UL ma...

Page 4: ...erify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors To avoid electrical shock turn off the unit and unplug it form the AC power source before servicing the battery Only persons adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized p...

Page 5: ... to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful i...

Page 6: ...sure that nothing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view P91g models 1500 Model 2000 Model 3000 Model P91 models 1000 1500 Model 2000 Model 3000 Model 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Network Fax Modem surge protection ...

Page 7: ...uptible Power Supply Xtreme Power Conversion Corporation Page 5 5 USB communication port 6 RS 232 communication port 7 SNMP intelligent slot 8 Emergency power off function connector EPO 9 External battery connection 10 Output circuit breaker ...

Page 8: ...ter Inverter Rectifier PFC Input Output Dynamic Bypass The UPS is composed of mains input EMI RFI filters rectifier PFC inverter battery charger DC to DC converter battery dynamic bypass and UPS output 2 3 Install the UPS This UPS can be either displayed on the desk or mounted in the 19 rack chassis Please choose proper installation to position this UPS Rack mount Installation Step 1 Step 2 UPS To...

Page 9: ...m clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Place UPS It s equipped with fan for cooling Therefore place the UPS in a well ventilated area It s required to maintain minimum clearance of 100mm in the front of the UPS and 300mm in the back and two sides of the UPS for heat dissipation and easy maintenance Step 1 External battery connection For safety considerat...

Page 10: ...attery pack s Note If you have multiple battery packs available connect them serially An example is shown in the diagram below connecting the second battery connector of the first battery pack to the first battery connector of the second battery pack 5 Stabilize the connector to the UPS and the battery pack s by fixing screws as shown below diagram 6 Connect internal battery connector and put the ...

Page 11: ...connection There are two kinds of outputs programmable outlets and general outlets Please connect non critical devices to the programmable outlets and critical devices to the general outlets During power failure you may extend the backup time to critical devices by setting shorter backup time for non critical devices Step 4 Communication connection Communication port USB port RS 232 port Intellige...

Page 12: ...nable EPO function This UPS is equipped with EPO function By default the UPS is delivered from factory with Pin 1 and pin 2 closed a metal plate is connected to Pin 1 and Pin2 for UPS normal operation To activate EPO function remove two screws on EPO port and metal plate will be removed Note The EPO function logic can be set up via LCD setting Please refer to program 16 in UPS setting for the deta...

Page 13: ...ter restarts the monitoring software will appear as an orange plug icon located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is sounding every 2 seconds it s time to replace batteries Contact your service representative to replace batteries Do not disconnect battery connectors under load If you prefer to remove input power to...

Page 14: ...ct the battery wires Step 7 Put the front panel back to the unit 2 6 Battery Kit Assembly NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells...

Page 15: ...ery packs on one side of plastic shells as below chart Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is a...

Page 16: ...ration Page 14 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of plastic shells Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well Tapes Tapes ...

Page 17: ...ng this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input current battery voltage battery current battery capacity ambient temperature output voltage output frequency load current and load percent Setting mode Press and hold this button for 3 se...

Page 18: ... frequency load current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Ind...

Page 19: ...ings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shutdown OK OK ON ON BL Battery Low OL Over Load OI Over input current NC Battery No Connect OC Over Charge SF Site wiring fault EP EPO TP Temperature CH Charger BF Battery Fault BV Bypass Out Range FU B...

Page 20: ...0Vac For P91 models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac Default 125 presents output voltage is 125Vac 02 Frequency Converter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two opti...

Page 21: ...tting range in parameter 3 is from 7V to 24V of the nominal voltage Default 12V For P91 models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass voltage range set...

Page 22: ...dels 55 59Hz setting the frequency low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 10 Programmable outlets setting Interface Setting Parameter 2 Set up backup time limits for programmable outlets 0 999 setting the backu...

Page 23: ...ity as following table for reference Battery capacity AH Total charging current A 7 20 2 20 40 4 40 60 6 60 8 14 Charger boost voltage setting Interface Setting Parameter 2 Set up the charger boost voltage 2 25 2 40 setting the charger boost voltage from 2 25 V cell to 2 40V cell Default 2 36V cell 15 Charger float voltage setting Interface Setting Parameter 2 Set up the charger float voltage 2 20...

Page 24: ...ting mode Description LCD display Online mode When the input voltage is within acceptable range UPS will provide pure and stable AC power to output The UPS will also charge the battery in online mode ECO mode Energy saving mode When the input voltage is within voltage regulation range UPS will bypass voltage to output for energy saving The UPS will also charge the battery at ECO mode Frequency Con...

Page 25: ...14 x Over input current 49 x 3 8 Warning indicator Warning Icon flashing Code Alarm Low Battery Sounding every 2 seconds Overload Sounding every second Over input current Sounding 2 beep every 10 seconds Battery is not connected Sounding every 2 seconds Over Charge Sounding every 2 seconds Site wiring fault Sounding every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding ever...

Page 26: ...attery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icons and and the warning c...

Page 27: ...ler to replace the battery Fault code is shown as 2A on LCD display and alarm is continuously sounding The short circuit occurs on the charger output Check if battery wiring of connected external pack is in short circuit status Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output and battery voltage is less than 10V PC Contact yo...

Page 28: ...nt Charger current 2A default Max 8A Adjustable Charger voltage Frequency 50 60Hz 0 1Hz Efficiency Overload capacity MODEL CAPACITY INPUT OUTPUT Voltage 100 110 115 120 125 Vac selectable Waveform P91g models P91g 1500 P91g 2000 P91g 3000 1500VA 1500W 2000VA 2000W 3000VA 3000W 3 12V 9AH 4 12V 9AH 6 12V 9AH 41 1VDC 54 8VDC 82 1VDC 17 2 x 15 1 x 3 5 17 2 x 19 x 3 5 17 2 x 23 8 x 3 5 34 2 43 60 6 C14...

Page 29: ...A 1930W 16A 125Vac input 2000VA 1850W 16 7A 120Vac input 2000VA 1740W 17 4A 115Vac input 2000VA 1640W 18 2A 110Vac input 1800VA 1500W 18A 100Vac input P91 3000 100 125Vac 50 60Hz 24A 1Ø 100 110 115 120 125Vac 50 60Hz 1Ø 3000VA 2850W 24A 125Vac input 3000VA 2740W 25A 120Vac input 3000VA 2650W 26 1A 115Vac input 3000VA 2500W 27 3A 110Vac input 2700VA 2300W 27A 100Vac input Runtime Chart internal bat...

Page 30: ...8 P90 BP72 Used with UPS Models P91 1500 P91g 1500 P91 2000 P91g 2000 P91 3000 P91g 3000 Battery Type 12V 9Ah 12V 9Ah 12V 9Ah 12V 9Ah Battery Numbers 6 12 8 12 Dimensions WxDxH 17 2 x 18 9 x 3 5 in 17 2 x 23 6 x 3 5 in 17 2 x 18 9 x 3 5 in 17 2 x 23 6 x 3 5 in Net Weight 58 1 lbs 104 4 lbs 74 6 lbs 104 4 lbs NOTE Battery pack should be used with corresponding UPS ...

Page 31: ...technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Material Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer av...

Page 32: ... the equipment is repaired or modified by anyone other than XPC Corporation or a XPC Corporation approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifications or c the equipment has been used or stored in a manner contrary to the equipment s operating m...

Page 33: ...in the United States or d the total amount of all payment s you have or are entitled to receive from insurance other warranties extended warranties a legal liability claim or from other sources or persons for the damaged Connected Equipment 5 Purchaser means the person or entity that originally purchased the Product from an authorized reseller or distributor of XPC Products The Purchaser of this P...

Page 34: ...evice may be connected to the output sockets of the Product The installation must comply with all applicable electrical and safety codes set forth pursuant to the NEC 4 The Product must have undeniable physical evidence of a Power Disturbance that directly and proximately caused the damage 5 The Connected Equipment must have been damaged by a Power Disturbance on a properly installed grounded and ...

Page 35: ...BILITY OF SUCH DAMAGE SUCH DAMAGES INCLUDE BUT ARE NOT LIMITED TO LOSS OF PROFITS LOSS OF SAVINGS OR REVENUE LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR ANY ASSOCIATED EQUIPMENT LOSS OF SOFTWARE COST OF CAPITAL COST OF ANY SUBSTITUTE EQUIPMENT FACILITIES OR SERVICES DOWNTIME THE CLAIMS OF THIRD PARTIES INCLUDING CUSTOMERS AND INJURY TO PROPERTY Submitting a Load Protection Policy Clai...

Page 36: ...ent to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment XPCs maximum liability shall be reduced to reflect all such other payments or sources of recovery whether applied for or not 4 If XPC issues payment to the Purchaser to have the Connected Equipment repaired the repair must be performed at a service center that is authorized by the manufacturer ...