background image

 

Verze 001 (21.1.2020) 

Stránka 

1

 z 

2

 

D-502-0167 

The Quick Manual will guide you through a quick installation of the 
product, but in no case could it replace the full operating manual. A 
complete operating manual is available on our website www.xvent.cz 
or can be downloaded using a QR code. 

Xvent s.r.o.

                           

Poděbradská 289                             

53009 Pardubice-Trnová                               

office@xvent.cz 

Terminal clamp for regulator power supply 

clamp +10V intended for regulator power supply 
Max. current capacity of regulator: 10mA 

Recommended cross-section of conductors: 

from 0.5 mm

2

to 1.5mm

2

.

 

EC-fan connection terminals 

-

 

terminals for connecting the control voltage from the EC fan 0-
10VDC (+);

 

GND (-) with 10kΩ resistor. Regulator control range 2-10V

 

Contact load: max 0.3mA

 

Description of controls and connecting terminals 

2.      Technical parameters 

- Input voltage                                    10VDC        - Current                              10mA  

- Output voltage - fan contro      l 0-10VDC       - Dimensions     85 x 85 x 30 mm  
- Protection                                              IP20       - Weight                              0.12kg  

 

  

 

 

 

 

 

 

 

 

 

 

1.

 

Description of regulator 

The regulator is used to continuously control the speed of the EC-motors with the control input 0-10VDC without connection to the mains 
power supply. The motor speed is controlled continuously by the control element (a knob) on the front panel of the regulator. For information 

on the operation of the connected equipment, the operating signal diode is located in the upper part of the front panel. The regulator is 
supplied with direct voltage of 10 VDC from the EC-motor. The maximum recommended distance of the regulator from the regulated EC-

motor is 100 m, with conductor cross-section of 1 mm

2

. Possible increase or reduction of the distance according to the selected conductor 

cross section and calculation of real voltage loss. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                                                                    

 

 

QUICK MANUAL FOR USE AND INSTALLATION

 

Use the smart device (mobile phone, 
tablet, etc.) equipped with this 
technology to read the QR code.

 

Signalling diode 

–signals operation of the entire 

regulator. If the diode is lit, the regulator is on. If not, the 
regulator is off. 

Continuous fan speed regulator –

allows continuous fan speed 

setting in any position from minimum to maximum speed as 
required by the user. The "OFF" position allows the entire 
regulator to be switched off. The "OFF" position does not 
provide disconnection of the controlled device from the supply 
voltage –it must be performed separately on the supply voltage 
of the controlled device. 

B - MARK I 

The regulator may only be 
mounted and connected by a 
trained person with the 
appropriate authorization to 
connect electrical equipment 
with suitable tools and 
means.

 

Reviews: