background image

Step

1

Z1000 Model  

Identification and Mounting 

Connect Motor and  

Line Power 

Step

2

Step

3

Z1000 Control Wiring 

The following 
procedure is a 
supplement to 
other 
documentation 
supplied with this 
equipment and 
will guide the user 
in properly wiring 
the Z1000 and 
motor. It will also 
show the user 
how to configure 
the Z1000 for a 
Hand and Auto 
operation.
      
DANGER!
Improper wiring 
can and will cause  
bodily harm as 
well as damage to 
the equipment.

When installing 
the system be 
sure to follow 
good wiring 
practices and all 
applicable codes. 
Ensure that the 
mounting of the 
various 
components are 
secure and that 
the environment, 
such as extreme 
dampness, poor 
ventilation etc. will 
not  cause system 
degradation. 

Please read this 
procedure and the 
Z1000 User 
Manual

 (TOEP 

C710616 45) 

provided with the 
Z1000 thoroughly 
before attempting 
any installation. 

 

Page 1 of 2 

WARNING  DO NOT CONNECT ANY OF THE 

FOLLOWING TERMINALS TO EARTH GROUND

+M

-M

-

+1

+3

Fig.1 & 2 below show the electrical connections for the input 
power and motor terminals for various Z1000 models.

 Select the 

proper diagram for the model you are installing 

(see Step 1). 

WITH POWER OFF make the appropriate connections.
Make sure to follow good wiring practices and all applicable 
codes. Ensure that the equipment is grounded properly as 
shown in fig. 1

DANGER; 

LETHAL VOLTAGES ARE PRESENT- Before 

applying power to the Z1000, ensure that the terminal cover 
is fastened and all wiring connections are secure. After the 
power has been turned OFF, wait at least five minutes until 
the charge indicator extinguishes completely before touching 
any wiring, circuit boards or components. 

!

For best performance, the drive input supply voltage must be at least 
equal to or greater than the motor rated voltage.

DC Bus 

terminals 

location 

varies by 

model.

Use L1, L2, L3 for

3Ø Input Power

To change 
direction of 

motor rotation 
swap any 

two 

of the

 three 

motor leads 

(See Step 2)

Fig. 1 Input Power and Output Motor Electrical Connections for 
Models: 2_0011 - 2_0273, 4_0005 - 4_0302

3Ø Induction 

motor

Input

Protection

(Fuse or Circuit 

Breaker)

L1

L2

L3

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to chassis 

ground

*

Connect 
frame to 

ground

3Ø Induction 

motor

Connect 
frame to 

ground

Input

Protection

(Fuse or Circuit 

Breaker)

To change direction of motor 

rotation swap any 

two of the 

three motor leads 

(See Step 2)

Fig. 2 Input Power and Output Motor Electrical Connections for 
                  Models: 2_0343 & Larger and 4_0361 & Larger

(R/L1)

(S/L2)

(T/L3)

(U/T1)

(V/T2)

(W/T3)

Connect to 

chassis 
ground

Use L1, L2, L3 for

3Ø Input Power

L1 L2 L3

BUS TERMINALS:
DO NOT CONNECT TO GROUND

To make sure you received the correct model, it is essential to 
verify the Z1000 nameplate with your order and make sure the 

Z1000 has the correct rating so it can be used with your motor. 

Please check the nameplate information as shown in the 

example below. 

·

Check that the available power will meet the 

input power 

requirements. 

 

·

Ensure that the 

output power from the Z1000 is 

compatible with the motor requirements.

Mounting the Z1000

·

In the case of systems with more than one Z1000, follow 
the above procedure for each Z1000 and motor.

The mounting of the Z1000 is extremely important regarding 
environment and accessibility. Depending on your system, 
there are various models available and the mounting 
dimensions (footprint) may be different. Because the 
mounting procedure is fairly extensive, it is beyond the scope 
of this document; the user is referred to the Z1000 User 
Manual (Document No. TOEP C710616 45) received with the 
Z1000, 

Section 2.2 Mechanical Installation. Match the model 

that you received and follow the procedure described in the 
manual to ensure a safe and functional installation. In cases 
where the system has more than one Z1000, refer to the 
proper clearances required for adequate ventilation.  

Please 

pay particular attention to:   

·

The clearances to be maintained around the enclosure 
for adequate ventilation.

 

·

The environmental specifications such as avoiding 
excessive dampness, extreme temperatures, chemical 
exposure, corrosive areas, etc. to avoid damage to the 
equipment and to maintain safety. 

 

Removing and Attaching the Terminal Cover

Improper removal of the Z1000 terminal cover as well as 
front cover can cause extensive damage to the Z1000. To 
avoid damage to these items, please pay particular attention 
to the Z1000 User Manual, Document No. TOEP C710616 
45, Section 3.5, R

Removing and Attaching the Terminal 

Cover.

NEMA 1

Open Chassis

Drive Model 

Number

Input Power

Rating

Output Power

Rating

Serial 

Number

UL File 

Number

Drive Spec Number

Weight

Software 

Version

This step shows how to set up the sequence and reference method of the Z1000. The sequence method determines how the 
Z1000 drive receives its start and stop command and the reference method determines how the speed of the motor is controlled. 
Make sure all protective covers have been re-attached and power is turned on.  

DO NOT RUN THE MOTOR

This section may require you to change one or more Z1000 parameters. Please refer to Step 5 for a detailed explanation 
on how to change parameters.

SELECT START / STOP CONTROL METHOD

1.

Start / Stop Control from Digital Operator, use

See step 6
Hand / Auto Mode Operation

b1-02

2.

Start / Stop Control from external terminals (switch or relay contact)

Go to parameter
b1-02, set value to

( Factory Default)

NOTE: It is beyond the scope of this document to program the Z1000 drive for network communication control. Please 
refer 

to the Z1000 Technical Manual, (Document No. SIEP C710616 45) 

for this selection.  

SELECT SPEED METHOD

b1-01

1.

Adjust motor speed / frequency from the Digital Operator

Go to parameter b1-01, set value to

2.

Adjust motor speed / frequency from external terminals (0 - 10V / 4 - 20mA Signal)

Go to parameter b1-01, set value to                                     

(Factory Default)

+

To adjust frequency press              from the operation screen and use              /              to change frequency and press              .

+V

AC

A1

A2

FM

AM

AC

Potentiometer

2K Ohm

TB3 User Terminals

Wiring Diagram: 2-Wire Control

Forward

Reverse

Wiring Diagram: 3-Wire Control

Use for 

momentary 

contacts

Use for 

maintained 

contacts

(Set Parameter 

A1-03 to 3330)

Link

Start

Switch

Reverse

Stop 

Switch

Normally 

Open

Normally 

Closed

+V

AC

A1

A2

FM

AM

AC

0 ~ 10Vdc

+V

AC

A1

A2

FM

AM

AC

4 ~ 20mA

+

2 Wire / 4 ~ 20mA

Transducer

-

-

S1

S2

S3

S4

S5

S6

S7

SN

SC

SP

+P

FE

Link

S1

S2

S3

S4

S5

S6

S7

SN

SC

SP

+P

FE

TB1 User Terminals

FE

FE

Cable

Shield

Cable

Shield

+V

AC

A1

A2

FM

AM

AC

+

Brown or Red: 
+Power (1)

Black: Output

 20mA (2)

FE

Cable

Shield

SN

Install wire link 
(AC-SN) when 
using transducer.

+P

Z1000 AC Drive 
Quick Start Procedure 