5292157-UIM-B-0317

VARIABLE SPEED ECM SINGLE PIECE 
MULTI-POSITION AIR HANDLERS WITH 
FACTORY INSTALLED ELECTRONIC 
EXPANSION VALVE (EEV)

MODELS: AVV SERIES

INSTALLATION MANUAL

ISO 9001

Certified Quality

Management System

LIST OF SECTIONS

GENERAL  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
DUCT WORK AND CONNECTIONS   . . . . . . . . . . . . . . . . . . . . . . . . .6
COIL METERING DEVICES   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
REFRIGERANT LINE CONNECTION  . . . . . . . . . . . . . . . . . . . . . . . . .8
CONDENSATE DRAIN CONNECTIONS   . . . . . . . . . . . . . . . . . . . . . .9
ELECTRIC HEATER INSTALLATION   . . . . . . . . . . . . . . . . . . . . . . .10
LINE POWER CONNECTIONS  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
LOW VOLTAGE CONTROL CONNECTIONS   . . . . . . . . . . . . . . . . .11

REQUIRED CONTROL SET-UP   . . . . . . . . . . . . . . . . . . . . . . . . . . .  13
AIRFLOW AND COMFORT SETTING SELECTION  . . . . . . . . . . . .  15
UNIT DATA   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  16
MAINTENANCE  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  23
AIR SYSTEM ADJUSTMENT   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  23
INSTALLATION VERIFICATION  . . . . . . . . . . . . . . . . . . . . . . . . . . .  24
INSTRUCTING THE OWNER   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24
WIRING DIAGRAM   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  25
START UP SHEET  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  29

LIST OF FIGURES

“A” Coil Return Air Duct Attachment & Component Location  . . . . . . . .3
“N” Coil Return Air Duct Attachment & Component Location . . . . . . . .3
Pressure Check  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Dimensions & Duct Connection Dimensions  . . . . . . . . . . . . . . . . . . . .4
Typical Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Coil Blow Off Wing Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Horizontal Suspension  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Duct Work Transition  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Vapor Line Grommet   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Line Power Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

Accessory Control Wiring  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Main Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  11
Electronic Expansion Valve (EEV) Control Board   . . . . . . . . . . . . . .  12
Air Handler with Communicating AC or HP   . . . . . . . . . . . . . . . . . . .  13
Multi-wire Terminal Connection   . . . . . . . . . . . . . . . . . . . . . . . . . . . .  13
Duct Static Measurements  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  23
Drain Traps  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  24
Location of Coil Trapped and Plugged Drain Connections . . . . . . . .  24
Wiring Diagram - ECM - Single Phase Heat Kits (Sheet 1 of 2)  . . . .  25
Wiring Diagram - ECM - Single Phase Heat Kits (Sheet 2 of 2)  . . . .  26
Wiring Diagram - Three Phase Heat Kits 208-230V  . . . . . . . . . . . . .  27

LIST OF TABLES

Dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
EEV Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Fault Codes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Heat Relays  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Physical and Electrical Data - Cooling Only  . . . . . . . . . . . . . . . . . . . .16
Electrical Data - Cooling Only   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Electrical Heat: Minimum Fan Speed  . . . . . . . . . . . . . . . . . . . . . . . . .16

KW & MBH Conversions - For Total Power Input Requirement  . . . .  17
Electric Heat Performance Data: 208/230-1-60 & 208/230-3-60   . . .  17
Electrical Data For Single Source Power Supply: 208/230-1-60   . . .  17
Electrical Data For Multi-source Power Supply: 208/230-1-60  . . . . .  20
Electrical Data For Single Source Power Supply: 208/230-3-60   . . .  21
Electrical Data For Multi-source Power Supply: 208/230-3-60  . . . . .  22
Air Flow Data (CFM)1, 2, 3, 4  (When operating with 
electric heat section.)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  22

SECTION I: GENERAL

The single piece air handler series provides the flexibility for installation
in any position. This unit may be used for upflow, downflow, horizontal
right, or horizontal left applications.
These units may be located in a closet, utility room, attic, crawl space,
or basement. These versatile models may be used for cooling or heat
pump operation with or without electric heat.
Top or side power and control wiring, color coded leads for control
wiring, easy to install drain connections, and electric heaters all
combine to make the installation easy and minimize installation cost.
Electric heat kits are available as field installed accessories. Single
phase kits are available from 2.5 kW to 25 kW. 208-230 volt three
phase kits are available from 10kW to 25kW.

SECTION II: SAFETY

This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.

Understand and pay particular attention to the signal words 

DANGER

,

WARNING

, or 

CAUTION

DANGER 

indicates an 

imminently

 hazardous situation, which, if not

avoided, 

will result in death or serious injury

.

WARNING 

indicates a 

potentially

 hazardous situation, which, if not

avoided, 

could result in death or serious injury

.

IMPORTANT

The electronic expansion valve (EEV) in this unit is shipped in the closed position to protect the valve during transportation. Prior to brazing, line
power must be applied to the air handler field wiring terminals for 1 minute. The initial power causes the EEV to open allowing nitrogen to flow
through the system during the brazing process.
If power cannot be applied to the EEV control board prior to brazing refrigeration piping, a tool is available to manually operate the EEV.  An EEV
manual operating tool can be purchased from Source 1 as part number S1-02649686000. Six revolutions of the tool open the valve fully.

Summary of Contents for AVV25B

Page 1: ...source Power Supply 208 230 1 60 20 Electrical Data For Single Source Power Supply 208 230 3 60 21 Electrical Data For Multi source Power Supply 208 230 3 60 22 Air Flow Data CFM 1 2 3 4 When operati...

Page 2: ...requirements and conform to existing national standards and safety codes In some instances these instructions exceed certain local codes and ordinances especially those who have not kept up with chan...

Page 3: ...Attachment Component Location XFW ZRUN PD EH IDVWHQHG FDXWLRXVO ZLWK VFUHZV WR WKH VLGHV DQG UHDU RI XQLW RQO 35 0 5 5 1 137 9 325 5 5 5 17 1 211 7 21 48 5 5 5 17 1 211 7 21 25 217 5 1 3 1 6 21 5 5 1...

Page 4: ...wer and verify that it is within the normal operating voltage range for the unit The accept able voltage range for these units is as follows FIGURE 4 Dimensions Duct Connection Dimensions 7 5 66 5 1 2...

Page 5: ...ulation with vinyl vapor barrier should be used AIR HANDLER CONFIGURATION These air handler units are supplied ready to be installed in an upflow or horizontal left position Refer to Figure 5 If the u...

Page 6: ...is advisable to design the duct work so that the grille is not in direct line with the opening in the unit One or two elbows and acoustical duct liner assures a quieter system Operation where return a...

Page 7: ...turbulence inside the plenum This turbulence can change the air flow patterns across the electric heater limit switches If the factory suggested transition cannot be fabricated it is recommended that...

Page 8: ...lly to prevent air leak age In some units the vapor line grommet may be shipped as a loose part with the unit Refer to Figure 10 CAUTION Equipment should never be operated without filters CAUTION COIL...

Page 9: ...be plugged Instruct the owner that the evaporator coil drain pan should be inspected and cleaned regularly to prevent odors and assure proper drainage If a secondary drain is not used it must be plugg...

Page 10: ...t connection of aluminum wiring to air handlers is not approved If aluminum conductors are present all applicable local and national codes must be followed when converting from aluminum to copper cond...

Page 11: ...ted hole and keep low voltage wiring as short as possible To further minimize air leakage seal the wiring entry point at the out side of the unit The field wiring is to be connected with wire connecto...

Page 12: ...C 24 VAC System Common Pin 2 3 R 24 VAC System Power Pin 3 4 A RS 485 Input Pin 4 5 PR1 5V VCC Pressure Transducer Indoor Pressure Transducer Pin 1 6 PR1 0 5 4 5V Pressure Transducer Signal Pin 2 7 P...

Page 13: ...jumper to be changed from NO to YES 3 Set the MODE jumper to A C Air Conditioner or HP Heat Pump position depending on the outdoor unit included with the system 4 Set HEAT airflow jumper to proper po...

Page 14: ...is connected to the heater relays using pins 4 5 and 6 of connector P1 The relay outputs are 24 VAC The control energizes the heat relays as shown in Table 4 Depending on the heat kit installed in th...

Page 15: ...wer in conjunc tion with the outdoor unit compressor speed To Set Heat Pump Airflow The modulating outdoor AC or HP operate the indoor blower in conjunc tion with the outdoor unit compressor speed To...

Page 16: ...Refer to the latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing TABLE 7 Electrical Heat Minimum Fan Speed Heater K...

Page 17: ...HK46502025 19 2 14 4 17 6 49 2 60 2 7 2 8 8 14 4 17 6 6HK46502525 24 18 22 61 5 75 2 9 11 18 22 1 0 1 0 no service disconnect OR 1 with service disconnect 2 1 2 1 with service disconnect no breaker ju...

Page 18: ...3 128 3 125 150 AVV50C 6HK 0 1 6500206 10 9 1 8 8 25 25 6HK 0 1 6500506 20 9 1 8 8 35 35 6HK 0 1 6500806 32 9 1 8 8 45 50 6HK 0 1 6501006 40 9 1 8 8 60 60 6HK 1 2 6501306 52 9 1 8 8 70 80 6HK 1 2 650...

Page 19: ...ybe 0 no service disconnect or 1 with service disconnect 2 1 2 maybe 1 with service disconnect no breaker jumper bar or 2 with service disconnect breaker jumper bar 3 MOP Maximum Overcurrent Protectio...

Page 20: ...5 41 5 30 40 30 45 6HK16501506 60 30 8 43 3 32 7 47 9 35 45 35 50 6HK16501806 72 48 1 39 0 51 9 43 1 50 40 60 45 6HK16502006 80 52 5 43 3 56 7 47 9 60 45 60 50 6HK16502506 100 52 5 43 3 21 7 56 7 47 9...

Page 21: ...3 55 5 55 60 6HK465020253 46 2 56 3 61 0 60 70 37C 6HK36501025 23 1 31 3 33 3 35 35 6HK36501525 34 6 43 7 47 1 45 50 6HK36501825 41 6 51 3 55 5 55 60 6HK465020253 46 2 56 3 61 0 60 70 38B TBD TBD TBD...

Page 22: ...eat Tap2 AVV25B AVV37B AVV37C AVV38B AVV38C AVV49C High Low High Low High Low High Low High Low High Low A 1225 1020 1225 1020 1425 1150 TBD TBD 1430 1200 1650 1200 B 1150 950 1150 950 1150 1000 TBD T...

Page 23: ...y drain SECTION XV AIR SYSTEM ADJUSTMENT To check the Cubic Feet per Minute CFM measure the external duct static using a manometer and static pressure tips To prepare coil for static pressure drop mea...

Page 24: ...p sheet showing the critical readings of the unit at the time of commissioning must be uploaded as part of the online registration process FIGURE 18 Drain Traps 3 MINIMUM HANDMADE TRAP PREMADE TRAPS S...

Page 25: ...5292157 UIM B 0317 Johnson Controls Unitary Products 25 SECTION XVIII WIRING DIAGRAM FIGURE 20 Wiring Diagram ECM Single Phase Heat Kits Sheet 1 of 2 6KHHW RI...

Page 26: ...5292157 UIM B 0317 26 Johnson Controls Unitary Products FIGURE 21 Wiring Diagram ECM Single Phase Heat Kits Sheet 2 of 2 6KHHW RI...

Page 27: ...N BLUE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE...

Page 28: ...5292157 UIM B 0317 28 Johnson Controls Unitary Products NOTES...

Page 29: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Page 30: ...oting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat...

Reviews: