514067-UAD-A-0509

APPLICATION GUIDE

OVERVIEW

The 

Simplicity

®

LINC Gateway operates as a Modbus® Client 

providing an interface between a BACnet® MS/TP control system 
and devices that communicate using the Modbus RTU protocol. 
The 

Simplicity

®

LINC allows monitoring and control by a third-party 

BACnet Building Automation System (BAS).

The 

Simplicity

®

LINC is preconfigured to provide an interface to UP 

products equipped with 

Simplicity

®

 controllers manufactured after 

4/2/2008 as well as prior 

Simplicity

®

Elite™ and 

Simplicity

®

 with 

Intelli-Comfort™ controllers.

The 

Simplicity

®

LINC mounts inside the control panel of the UP 

unit and utilizes 24 VAC power from the unit’s control transformer. 
One port is connected to the UP controller. The other port must be 
connected to the BACnet MS/TP network.

The 

Simplicity

®

LINC Gateway is preconfigured to obtain 

operational data points from the controller and expose them on a 
BACnet MS/TP network.

NOTE: 

Not all 

Simplicity

®

 operating parameters are controlled/

monitored by the 

Simplicity

®

LINC.

FIGURE 1: WIRE CONNECTIONS

24 — must be grounded
close to the 

Simplicity

   LINC

®

The shield must be
connected to ground at
each device.

R
C

24V power is polarity sensitive, incorrect
wiring could result in board damage.

Simplicity

®

LINC GATEWAY

Summary of Contents for LINC GATEWAY 514067-UAD-A-0509

Page 1: ...lli Comfort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The...

Page 2: ...is completed at the factory No further adjustment should be done If a problem arises with the Simplicity LINC or a parameter not exposed by the Simplicity LINC requires modification the UP controller...

Page 3: ...tion problems between the Simplicity LINC and the UP controller BI 84 MODBUS_ALARM is used to indicate Modbus communication problems between the Simplicity LINC Gateway and the UP controller When on t...

Page 4: ...essure Setpoint R W 2 AV 25 COM_V_LOW_SP 70 60 85 Comfort Ventilation LowerSetpoint degrees F R 5 BV 34 CVM_COOLING Comfort Ventilation Mode for Cooling Enabled R 5 BV 35 CVM_HEATING Comfort Ventilati...

Page 5: ...ult R 2 AV 42 E_C2_ACM_HRS Elite Compressor 2 Accumulated Run Time in hours R 5 BV 46 E_COMP2_STAT Elite Compressor 2 Output Status 0 out put is OFF 1 output is ON R 5 BV 49 E_C2_OVRLOAD Elite Compres...

Page 6: ...Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 52 E_LPS3 Elite Low Pressure Switch for Compressor 3 Input Status 1 closed 0 open fault R 5 BV 56 E_LPS4 Elite Low Pressure Switch fo...

Page 7: ...put is OFF 1 output is ON R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BV 72 I_FAN_OVER Intelli Comfort Fan Overload Switch Input Status 0 open...

Page 8: ...or Communication Input Enabled R 2 AV 17 OP_COOL_STPT Operating Cooling Setpoint R 2 AV 49 OP_HEAT_STPT 68 45 99 Operating Heating Setpoint R W 2 AV 69 OP_STPT_DIF 1 1 5 Operating Setpoint Differenti...

Page 9: ...2 SAT_HEAT_SP 135 100 180 Supply Air Temperature Limit for Heating Setpoint degrees F R 2 AV 34 SFAN_VFD_OUT Supply Fan VFD Output Status 0 100 R 2 AV 36 ALARM_1 System Alarm 1 R 2 AV 37 ALARM_2 Syste...

Page 10: ...DEMVENT_STPT 1000 0 5000 Demand Ventilation Setpoint R W 2 AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position R W 2 AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint R W 2 AV 21 ECO_2N...

Page 11: ...0 Supply Air Temperature Limit for Heating Setpoint degrees F R W 2 AV 53 SAT_ALM_HEAT 0 0 120 Supply Air Temperature Alarm Setpoint for Heating R W 2 AV 54 OAT_HEAT_L_O 75 0 100 Outdoor Air Temperatu...

Page 12: ...n Setpoint R W 2 AV 81 POP_HOURS 4 0 23 Pre Occupancy Purge Time hours R W 2 AV 82 POP_MINUTES 0 0 59 Pre Occupancy Purge Time minutes R W 2 AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy...

Page 13: ...OOL_STAT Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BV 33 COM_VENT_STA Comfort Ventilation Mode Status 1 control is in Comfort Vent mode 0 it is not R 5 BV 34 CVM_...

Page 14: ...ressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 57 E_HPS4 Elite High Pressure Switch for Compressor 4 Input Status 1 closed 0 open fault R 5 BV 58 E_C4_OVRLOAD Elite Compress...

Page 15: ...8 I_HPS2 Intelli Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BV 79 I_CFAN_STAT Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5...

Page 16: ...may also indicate incorrect polling parameters such as baud rate or parity If the TX and or RX LEDs do not flash it may represent a problem with the field wiring or confguration problems in the field...

Page 17: ...514067 UAD A 0509 Johnson Controls Unitary Products 17 FIGURE 3 SIMPLICITY LINC GATEWAY LED LOCATION PWR RS485 PWR BACnet GP105 BACnet LB BACnet RX RS485 TX RS485 LA BACnet TX BACnet RX BACnet...

Page 18: ...t to change without notice Printed in U S A 514067 UAD A 0509 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK...

Reviews: