AI-3502M/3504M/3506M 

人工智能温度控制器/工业调节器 

产品说明书 

 

 

Panel Mounting:

Remove the square anchor from the instrument. 

Insert the instrument from panel front. 

To fasten the instrument, put the anchor back 

before wiring. The screws may be used for 

further tightening.

48

48

95

10

45

45

75

75

INSTALLATION AND

OPERATION MANUAL

AI-710JM

 

Artificial Intelligent Temperautre Controller / Industrial Regulator

Software Version 8.2

Revise Date: May 2020

1. INSTALLATION

Dimensions and cut-out; panel mounting

2. TECHNICAL SPECIFICATIONS

Dimensions and cut-out; panel mounting

eEC

Display

2*4 digit LED, Red and Green

Keys

4 mechanical keys

Accuracy

0.1% full scale (FS)±1 digit

Input 

(adustable digital 

filter)

Pt100

Sampling time 80ms

Measurement 

Range

-100...+300°C

Cold Junction 

Error

0.05°C for each 1°C variation

Safety

Detection of opening of probe

Temperature Shift ≤35ppm/°C
Regulating 

Method

On/Off (adjustable hytersis)

Artificial Intelligent Regulating 

with auto-tuning 

Main Output

SSR Voltage output 12VDC/30mA 

(used to drive solid-state relay)

Action

Main output (OUTP) with direct 

(heating).

Configuration 

alarm

4 type of alarm, high limit, low lim-

it, deviation high limit and devia-

tion low limit compared to setpoint. 

Maximum 2 loops. Temporarily 

disable during first power on. 

Power Supply

100~240VAC, -15%, +10% / 

50~60Hz; 120~240VDC; or 

24VDC/AC, -15%, +10%.

 Power 

Consumption

≤0.5W (no output or alarm); 

≤4W (Maximum)

Opearating and 

Storage 

Environment

Temperature -10~60°C

Humidity ≤90%RH

Summary of Contents for AI-710JM

Page 1: ...cy 0 1 full scale FS 1 digit Input adustable digital filter Pt100 Sampling time 80ms Measurement Range 100 300 C Cold Junction Error 0 05 C for each 1 C variation Safety Detection of opening of probe Temperature Shift 35ppm C Regulating Method On Off adjustable hytersis Artificial Intelligent Regulating with auto tuning Main Output SSR Voltage output 12VDC 30mA used to drive solid state relay Acti...

Page 2: ...c 2 Lower display window Displays SV parameter value or alarm message 3 Setup key For accessing parameter table and conforming param eter modification 4 Cursor shifting or control operation 5 Value down key or switch between RUN HOLD 6 Value uo key or STOP These value down and up keys raise or lower the value of the displayed function The raising lowering speed is proportional to the time the key ...

Page 3: ...em Before activating the auto tuning set point value SV should be set at the commonly used value or mean value Set the SV to a maximum one if the heat isolation of a furnace is good SV value is not allowed to be changed during auto tuning The time required for this process may takes seconds to hours 3 Control Hysteresis CHYS affects the result of auto tuning too Generally the least the CHYS the hi...

Page 4: ...nE Loc 0 Example If fast access to high limit alarm high deviation alarm and auto tuning is needed set EP1 HIAL EP2 HdAL EP3 At EP4 EP8 nonE The default settings may vary due to minor firmware version update or order request Master password is stored in PASd By default PASd 808 There is no password reset feature If the password is lost only firmware reload in factory can reset the password loc def...

Page 5: ...an be assigned as absolute high limit and low limit alarms Details please refer to the description of parameter AF AHyS Alarm Hysteresis Also known as dead band or lag To avoid frequent alarm on off action caused by the fluctuation of PV Usage of AHYS is shown above 0 2000 units AdiS Alarm Display oFF Hide alarm messages in the lower display on Alternately display alarm message in the lower displa...

Page 6: ...turns off when PV SV CHYS output turns on 0 2000 inP Input Specification Code Select input specification Inut is fixed in this instrument with corresponding range of measurement 22 Pt100 100 300 00 C 22 dpt Display Resolution Four display formats 0 0 0 0 00 0 000 are selectable When inP 22 the internal resolution is 0 01 C Display format 0 0 or 0 00 are available 0 0 0 00 SCL Source Low Limit Defi...

Page 7: ...inear input is 3 200 units F 1 Wide range display mode which is selected when the required display value is larger than 3 200 G 0 When the sensor is broken PV value will increase and trigger the high limit alarm High limit alarm should be set below the input scale high limit G 1 When the sensor is broken PV value will increase and NOT trigger the high limit alarm Pleaes note that High Limit Alarm ...

Page 8: ... control mode The new edition approves default fine control mode when the displayed value range is below 3 000 char acters on most of industrial application occasions the value should not exceed 3 000 characters during linear input so as to get higher control accuracy and more stable output When the required display value range is larger than 3 000 AF F 1 User defined input specifications When INP...

Reviews: