background image

PBM-04/U BI-STABLE VOLT FREE RELAY

 

SERVICE MANUAL

Zakład Mechaniki i Elektroniki 

ZAMEL 

sp.j.

J.W. Dzida, K. Łodzińska

ul. Zielona 27, 43-200 Pszczyna, Poland

Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04

www.zamelcet.com

, e-mail: marketing@zamel.pl

VER. 001_04.08.2010

APPEARANCE

FEATURES

TECHNICAL DATA

DESCRIPTION

PBM-04/U

Tripping terminal:

IN

Tripping terminals for illuminated switches:

IN’, IN’

Tripping rated voltage: 12 

÷

 230 V AC/DC

Supply voltage tolerance: -15 ÷ +10 %

Rated frequency: 50 / 60 Hz

Rated power consumption:

0 mA

Rated triggering power consumption: 11 mA

Relay contact parameters: 1NO - 10 A / 250 V AC1 2500 VA

Number of terminals: 7

Section of wire conductors: 0,2 ÷ 2,50 mm

2

Operating temperature: -20 

÷

 +45 

o

C

Operating position:  optional

Fixing of the casing: TH35 rail (in accordance with PN-EN 60715)

Protection degree of casing: IP20 (PN-EN 60529)

Protection class:

II

Overvoltage category:

II

Degree of pollution: 2

Surge voltage: 1 kV (PN-EN 61000-4-5)

Dimensions: single module (17,5 mm) 90x17,5x66 mm

Weight: 0,065 kg

Compliance with the following standards: PN-EN 60669-1

PN-EN 60669-2-1

PN-EN 61000-4-2,3,4,5,6,11

PBM-04/U  bi-stable  relay  is  used  to 

control lighting or any other device with 

the  help  of  unipolar  parallel  connected 

switches.  Another  push  of  any  switch 

causes  actuation  or  disengagement  of 

devices  connected  to  output  terminals 

(change  in  relay  status).  The  device 

enables to use typical unipolar switches 

connected to IN inlet and switches with 

illumination connected to IN’ inlets (trip

-

ping  only  from  L  line  for  230V  voltage). 

Structure of the relay enables to record 

the current status in case of loss of sup

-

ply  voltage. 

Zero  power  consumption 

stands as an important feature of the 

device.

This  device  must  be  in

-

stalled  in  one-phase  sup

-

ply  network,  according  to 

legally  binding    regulations 

and  standards.  Installation 

must  be  carried  out  accor

-

ding  to  this  instruction  ma

-

nual.  Procedures  such  as: 

installation,  connection  and  adjustment  of 

the device should be carried out by qualified 

electricians who are familiarised with this in

-

struction manual and device functions. If the 

casing  is  dismantled,  the  warranty  expires 

and there is the danger of an electric shock. 

Before  installation,  make  sure  that  voltage 

is not present on the conductors. Use cross 

screwdriver with diameter of 3.5 mm, for in

-

stallation. Transport, storage and use of this 

device influence its correct operation. Instal

-

lation  of  this  device  is  not  recommended  in 

the following situations: lack of parts, dama

-

ge or deformations of the device. In the case 

of incorrect functioning of the device, please 

contact the manufacturer.

NOTE

●  Bi-stable  (biconditional)  lighting  con

-

trol,

●  universal scope of 12 ÷ 230 V AC/DC 

supply voltage,

●  zero power consumption,

●  memory of relay status,

●  cooperation  with  numerous  unipolar 

switches, also the ones with illumina

-

tion,

●  two wire control installation,

●  relay output – one short circuiting con

-

tact with maximal capacity of 10 A.

Rela

y

 

o

u

t

pu

t

Trippi

ng

 

t

ermi

n

al (IN

)

Trippi

ng

 

t

ermi

n

als (IN’

)

P

ow

er suppl

y

 

t

ermi

n

al (A

2)

terminals (11, 11, 14)

The symbol showing a selective 

collection of electric and 

electronic equipment. 

Used up equipment must not be 

placed together with another kind 

of waste.

Reviews: