ZENNER ZSU Stealth Ultrasonic Meters 

Installation Manual 

Product Description 

ZENNER ZSU Ultrasonic Bulk Water Meters are 

designed for cold water applications up to 122°

F.

 

 

Intended purpose 

 

For the consumption measurement of drink-

ing water up to 122°F. 

 

For the consumption measurement of non-

potable water up to 122°F. 

 

Comment 

This installation manual is intended for qualified 

meter installers only. Basic installation steps are 

therefore  not  described.  In  order  to  ensure  a 

proper  flow  measurement,  the  meter  must  be 

completely filled with water at all times.  

Permissible installation positions 

 

Summary of Contents for ZSU02

Page 1: ... cold water applications up to 122 F Intended purpose For the consumption measurement of drink ing water up to 122 F For the consumption measurement of non potable water up to 122 F Comment This installation manual is intended for qualified meter installers only Basic installation steps are therefore not described In order to ensure a proper flow measurement the meter must be completely filled wit...

Page 2: ...t extend into the pipe If necessary the meter should be protected by a strainer This will keep foreign matter such as stones or debris from entering the meter and potentially cause damage The meter is designed for use in a frost proof location with ambient temperature not to exceed 130 F and with water tempera tures not to exceed 122 F To prevent damage during the installation process ensure that ...

Page 3: ...after the deci mal place 10 to 12 9 digit with no decimal place Unit of consumption display CF Consumption value Cubic Meters 2 to 4 9 digit with 3 digits after the deci mal place 6 to 10 9 digit with 2 digits after the deci mal place 12 9 digit with 1 digit after the decimal place Unit of consumption display m Consumption value US Gallons 2 to 4 9 digit with 1 digit after the deci mal place 6 to ...

Page 4: ...L Inches 10 12 14 18 20 17 3 4 19 11 16 Height H Inches 5 5 8 7 1 2 8 3 4 10 5 8 12 5 8 15 3 16 18 1 8 Height H1 Inches 2 3 5 16 4 3 32 5 5 16 6 5 16 7 5 8 9 1 16 Flange diameter also width D Inches 6 7 1 2 9 11 13 1 2 16 19 Bolt circle diameter D1 Inches 4 1 2 6 7 1 2 9 1 2 11 3 4 14 1 4 17 Number of bolts per flange Pcs 2 4 8 8 8 12 12 Bolt size Inches 5 8 5 8 5 8 3 4 3 4 7 8 7 8 Weight approx P...

Page 5: ...ding Example for Maximum LCD Display LCD Display Shown at Left Registration 5 8 to 1 ZSUR Residential 1 2 3 4 5 6 7 8 9 123 456 789 Cubic Feet 999 999 999 Cubic Feet 1 1 2 ZSUR Residential 2 to 3 ZSU 1 2 3 4 5 6 7 8 9 1 234 567 89 Cubic Feet 9 999 999 99 Cubic Feet 4 to 8 ZSU 1 2 3 4 5 6 7 8 9 12 345 678 9 Cubic Feet 99 999 999 9 Cubic Feet 10 to 12 ZSU 1 2 3 4 5 6 7 8 9 123 456 789 Cubic Feet 999...

Page 6: ...Example for Maximum LCD Display LCD Display Shown at Left Registration 5 8 to 1 ZSUR Residential 1 2 3 4 5 6 7 8 9 12 345 6789 Cubic Meters 99 999 9999 Cubic Meters 1 1 2 ZSUR Residential 2 to 4 ZSU 1 2 3 4 5 6 7 8 9 123 456 789 Cubic Meters 999 999 999 Cubic Meters 6 to 10 ZSU 1 2 3 4 5 6 7 8 9 1 234 567 89 Cubic Meters 9 999 999 99 Cubic Meters 12 ZSU 1 2 3 4 5 6 7 8 9 12 345 678 9 Cubic Meters ...

Page 7: ... Example for Maximum LCD Display LCD Display Shown at Left Registration 5 8 to 1 ZSUR Residential 1 2 3 4 5 6 7 8 9 1 234 567 89 US Gallons 9 999 999 99 US Gallons 1 1 2 ZSUR Residential 2 to 4 ZSU 1 2 3 4 5 6 7 8 9 12 345 678 9 US Gallons 99 999 999 9 US Gallons 6 to 8 ZSU 1 2 3 4 5 6 7 8 9 123 456 789 US Gallons 999 999 999 US Gallons 10 to 12 ZSU 1 2 3 4 5 6 7 8 9 1 234 567 890 US Gallons 9 999...

Reviews: