background image

© Zennio Avance y Tecnología S.L. 

Edition 1 

Further information 

www.zennio.com

 

Page 1/2 

 

Lumento DX4 v2 

4-channel constant voltage PWM dimmer in DIN rail for DC LED loads 

ZDILDX4V2 

TECHNICAL DOCUMENTATION 

 

FEATURES 

 

constant 

voltage 

configurable 

channels 

(combinable 

independent  channels,  RGBW  channel,  RGB+W  channels  and 
combinable TW channels) 

 

1 relay to control the LEDs power supply or for independent use 

 

Supports KNX Data Secure 

 

Master Light control 

 

External 12-40 VDC power supply 

 

Manual output operation with push button and LED status indicator 

 

Total data saving on KNX bus failure 

 

Integrated KNX BCU (TP1-256) 

 

Dimensions 67 x 90 x 79 mm (4.5 DIN units) 

 

DIN rail mounting according to IEC 60715 TH35, with fixing clamp 

 

Conformity with the CE, UKCA, RCM directives (marks on the right 
side) 

 
 

 

 

Figure 1: Lumento DX4 v2 

GENERAL SPECIFICATIONS 

CONCEPT 

DESCRIPTION 

Type of device 

Electric operation control device 

KNX supply 

Voltage (typical) 

29 VDC SELV 

Voltage range 

21-31 VDC 

Maximum 
consumption 

Voltage 

mA 

mW 

29 VDC (typical) 

6.2 

179.2 

24 VDC¹ 

10 

240 

Connection type 

Typical TP1 bus connector for 0.8 mm Ø rigid cable 

External power supply 

12-40 VDC 

Operation temperature 

0 .. +55 °C 

Storage temperature 

-20 .. +55 °C 

Operation humidity 

5 .. 95% 

Storage humidity 

5 .. 95% 

Complementary characteristics 

Class B 

Protection class / Overvoltage category 

II / III (4000 V) 

Operation type 

Continuous operation 

Device action type 

Type 1 

Electrical stress period 

Long 

Degree of protection 

IP20, clean environment 

Installation 

Independent device to be mounted inside electrical panels with DIN rail (IEC 
60715) 

Minimum clearances 

Not required 

Response on KNX bus failure 

Data saving according to parameterization 

Response on KNX bus restart 

Data recovery according to parameterization 

Operation indicator 

The programming LED indicates programming mode (red) and test mode 
(green). Color shift LEDs show the current color. Each output LED indicates 
its status. 

Weight 

200 g 

PCB CTI index 

175 V 

Housing material 

PC FR V0 halogen free 

¹ Maximum consumption in the worst-case scenario (KNX Fan-In model). 

Programming/Test button: short press to set programming mode. If this button is held while plugging the device into the KNX bus, it enters the safe mode. 
If this button is held for more than 3 seconds, the device enters the test mode. In order to perform a KNX Secure factory reset, while the device is in safe 
mode, press the button for 10 seconds until the programming LED changes its state. 
 
Programming/Test LED: programming mode indicator (red). When the device enters the safe mode, it blinks (red) every half second. The test mode is 
indicated by the green color. During the start-up (reset or after KNX bus failure) and if the device is not in safe mode, it emits a red flash. 

 

1. Power Supply LED 

2. Colour shift control buttons 

3. External power supply 

4. Colour output LEDs  

5. TW selection button  

6. (not used) 

7. Relay status LED  

8. Relay control button  

9. Power Supply Relay  

10. Output channels 

11. KNX connector 

12. Programming/Test LED  13. Programming/Test button 

14. Channel status LED 

15. Channel control button 

 

3  4  5 

15 

14  10 

10 

13 12  11 

Reviews: