SM-ASB Instruction Manual V1.0- 2/4/08
100.00
mm
29.0 mm
36.0 mm
1
2
3
45
6
7
8
Mechanical Specification
Weight
Base Sounder - 100 g
including Lid - 120 g
including electronic circuits
and fixings
Enclosure Construction Material
Flame Retardant rating 94V0
White ABS - Transparent PC
Technical Specifications
Operating Voltage
Sounder Output
Flash Colour
Flash Rate
Alarm Tone
Current Consumption
Quiescent
Sounder Only
Flasher Only
Combined Sounder Flasher
Compatible Detectors
800-970Hz (0.5s each)
17-30V DC
85 dB @ 1 metre
Red
0.3 Hz
(Add 12 mA when conventional detector is in alarm)
1.2 mA + conventional detector quiescent current
4 mA
2.5 mA
5.5 mA
FEOE2000, FEOH2000, FEHE2000, FEFHE2000
The Securetone Micro Addressable sounder
flasher base is the latest innovative product
from GLT Exports Ltd. It is available as an
addressable sounder, or combined sounder
flasher, to which can be connected a
conventional detector, either smoke, heat, or
opto-heat. This can allow for considerable
cost savings in locations where a sounder &
detector are required. It is designed to work
with Zeta Analogue addressable control
panels only.
The Securetone Micro sounder has an 8 way
D.I.L. switch to set the address. Switch 8
MUST be to the ON position. Switches 1 to 7
are used to set a binary address, with OFF
being a binary 1, and ON being a binary 0 (or
see setting chart on page 3)
There is a jumper to tell the sounder whether a
conventional Optical smoke detector, or
conventional heat detector has been fitted.
This makes the sounder reply as OPTICAL, or
HEAT.
There is also a potentiometer which may be
used to adjust the sound level if required. It is
supplied set to it`s maximum volume.
Normally the
will be used
in conjunction with a conventional heat/
smoke detector. However, if the MODE
selection jumper is removed, it will behave as
a normal addressable sounder. (NOTE: in this
configuration, the conventional detector input
will be inoperative.)
The sounder flasher version also includes a
loop short circuit isolator, which minimises
the number of devices which would be
inoperative in the case of a short circuit on the
loop.
Securetone Micro
Low current consumption.
5.5 mA for combined Sounder/Beacon
Address setting is in the base for easy
Detector head replacement
Can work as a stand alone sounder.
Complies with EN-54 pt.3
Allows use of Conventional Detectors
Loop Isolator option
Compatible with all Zeta addressable panels
Features
ORDER CODE PRODUCT DESCRIPTION
SECURETONE MICRO ADDRESSABLE SOUNDER BASE
SECURETONE MICRO ADDR. SOUNDER FLASHER BASE with ISOLATOR
LID FOR SOUNDER BASE (WHITE)
LID FOR SOUNDER BASE (TRANSPARENT-CLEAR)
LID FOR SOUNDER BASE (TRANSPARENT-RED)
SM-ASB
SM-ASFIB
V2 L
V2 LT
V2 LTR
Addressable
Sounder/Flasher Base
to
e
cu
r
e
S
e
n
Micro
Loop Out
LoopIn
Mode
-V
ol
+
Sounder Flasher
with Short Circuit
Loop Isolator
Sounder
to
e
cu
r
e
S
e
n
Micro
Heat
Detector
Smoke
Detector
Addressable
Sounder/Flasher Base
|S
Address
MODEL
SM-ASFIB
SM-ASB
SWITCH
8
M
UST
BE
IN
ON
POSITION
1