MZX Fire detection system
602SB
Fixing instructions Doc. version 5.0
1/6
602SB Type ‘A’ Sounder Base - Installation
Instructions
Technical Specifications
Electromagnetic Compatibility
The 602SB complies with the following:
Product family standard EN50130-4 in
respect of Conducted Disturbances, Radiated
Immunity, Electrostatic Discharge, Fast Tran-
sients and Slow High Energy.
EN50081-1 for emissions.
Introduction
The 602SB Intelligent Sounder Base provides an
additional sounder function on the MXC detec-
tion circuit.
Fig. 1: 602SB Sounder Base
Parameter
Value
System Compatibility
Use only with MXC
Fire Alarm Controllers
Environment
Indoor Application
only
Operating Tempera-
ture
-25
o
to +70
o
C
Storage Temperature
-40
o
to +80
o
C
Operating Humidity
Up to 95% non-con-
densing
Height
37.5mm
Diameter
107.8mm
Weight
0.192kg
Table 1: Specifications
Yellow temporary
park plunger
Mounting Require-
ments
Flat surface or electri-
cal backbox with
50mm fixing centres
with the 4" flange.
Minimum Wire Size
1.5mm
2
Maximum Wire Size
2.5mm
2
Standby current
(Dumb Mode)
<100μ
Standby current (Intel-
ligent Mode, for
future use)
<1.5mA
Alarm current full vol-
ume (90dBA)
6.8mA
Alarm Current low
volume (68dBA)
1.2mA at low volume
Protocol
Fulleon PIU and Tyco
CAUTION
Ensure that the site plan defines the
polarity of polarity conscious bases
Parameter
Value
Table 1: Specifications