602SB Type ‘A’ Sounder Base - Installation 
Instructions

Technical Specifications

Electromagnetic Compatibility

The 602SB complies with the following:

Product family standard EN50130-4 in 
respect of Conducted Disturbances, Radiated 
Immunity, Electrostatic Discharge, Fast Tran-
sients and Slow High Energy.

EN50081-1 for emissions. 

Introduction

The 602SB Intelligent Sounder Base provides an 
additional sounder function on the MXC detec-
tion circuit.

Fig. 1: 602SB Sounder Base

Parameter

Value

System Compatibility

Use only with MXC 
Fire Alarm Controllers

Environment

Indoor Application 
only

Operating Tempera-
ture

-25

o

 to +70

o

C

Storage Temperature

-40

o

 to +80

o

C

Operating Humidity

Up to 95% non-con-
densing

Height

37.5mm

Diameter

107.8mm

Weight

0.192kg

Table 1: Specifications

Yellow temporary

 

park plunger

Mounting Require-
ments 

Flat surface or electri-
cal backbox with 
50mm fixing centres 
with the 4" flange. 

Minimum Wire Size

1.5mm

2

Maximum Wire Size

2.5mm

2

Standby current 
(Dumb Mode)

<100μ

Standby current (Intel-
ligent Mode, for 
future use)

<1.5mA 

Alarm current full vol-
ume (90dBA)

6.8mA

Alarm Current low 
volume (68dBA)

1.2mA at low volume 

Protocol

Fulleon PIU and Tyco

CAUTION

Ensure that the site plan defines the 
polarity of polarity conscious bases

Parameter

Value

Table 1: Specifications