background image

date / name

20.12.1999  Wl/Fz

Z. Nr.: 642 0720.1

sheet  1  of 4

Type: TMS 400

22.12.1999

Subject to technical modifications.

EA - Nr.:

9710.1

MINIPAN

®

 digital panel meters, temperature-   and   mains   controlling, 

special purpose instruments for customer requirements     www.ziehl.d

e

   

          

ZIEHL industrie-elektronik GmbH+Co, Daimlerstr.13, D-74523 Schwäbisch Hall, Tel.: +49 791 504-0, Fax: -56, e-mail: info@ziehl.de

O

O

p

p

e

e

r

r

a

a

t

t

i

i

n

n

g

g

 

 

m

m

a

a

n

n

u

u

a

a

l

l

T

T

M

M

S

S

 

 

4

4

0

0

0

0

Application

Thermostats of the TMS series are temperature controllers. The thermostat switches

operate when the value of the preset is exceeded.

TMS thermostats and thermcouples sensors are a reliable  monitoring  system. Possible

damage by excess temperature in machines and plants are positively avoided.

ZIEHL thermostats of the TMS series are  electronic two- position controllers. Modern

circuitry, well- proved components as well as function and routine tests ensure high

repeat accuracy and a long service life.

Function

As standard, the TMS 400 thermostats operate according to the closed- circuit current

principle. If a temperature sensor is connected, the installed relay picks up.

The relay always switches off in the case of a sensor breakdown.

Features

exact temperature sensing and precise switching operations with high repeatability

1 sensor, 1 adjustable limits, 1 relay

LED display for state of the relay

internal reference with temperature sensor

option: operating current design

easy to install and service as the cables are wired directly to the plug  base  and  the

upper electronic part can easily be replaced

housing can be snapped onto a mounting rail according to DIN EN 50 022 or fixed

with M4 screws

gold- coated contact springs and plugs ensure a perfect contact and a long  service

life

Summary of Contents for TMS 400

Page 1: ...ats of the TMS series are electronic two position controllers Modern circuitry well proved components as well as function and routine tests ensure high repeat accuracy and a long service life Function As standard the TMS 400 thermostats operate according to the closed circuit current principle If a temperature sensor is connected the installed relay picks up The relay always switches off in the ca...

Page 2: ...ased LED off Relay output 1 relay 1 x CO contact Switching voltage max AC 415 V Switching current max 6 A Switching power consumption max 1100 VA Rated operational current 2 5 A 400 VAC 15 4 A 250 V AC 15 3 A 24 V DC 13 Testing conditions VDE 0660 VDE 0160 Rated insulation voltage Ui according to VDE 0110 AC 415 V Isolation VDE 110 Gr C Transformer VDE 0550 Test voltage between supply voltage rela...

Page 3: ... recommended mininum clearance 2 cm Wiring directly to plug base Connect wires as per wiring scheme Plug in electronics and fix with knurled screw Attention Do not plug in device alive nor detach it from socket Before switching on make sure that the operational voltage Us of the lateral type plate and the mains voltage are the same Put into operation the thermostat as follows Connect thermocouple ...

Page 4: ...Wiring scheme 1 2 4 5 6 7 8 9 10 11 12 3 analog output option TMS 400 K1 Us Design S12 5 104 5 82 36 23 5 AA AA AA 38 34 80 61 5 17 5 7 5 41 5 17 41 10 82 1 1 2 3 4 5 7 6 8 9 10 11 12 11 5 16 5 2 3 1 14 27 5 116 AA AA 41 5 Base 1 2 3 Cable bushing Mounting bore hole Unlatching only with rail mounting 2 6 Jacks for coding pins 1 ...

Reviews: