background image

Installation Sheet 

No.: 1774 iss 03 

ZP755R-2 Addressable Room Sounder 

Installation sheet 

501-1774ZE-1-03 

ZP755R-2 Addressable Room Sounder 

Page 1 

14/11/2006 

 

Product Description 

Description 

The  ZP755R-2  is  an  addressable,  sounder,  designed 
for use on Ziton analogue addressable fire detection 
and  alarm systems.  Conforming  to  EN54  Part 3,  the 
ZP755R-2  is  developed  for  applications  in  individual 
rooms, 

sleeping 

accommodation 

or 

small 

compartments. 

Application 

Installed directly onto the wiring loop - the ZP755R-2 
enables  the  system  designer  to  offer  a  complete 
analogue  addressable  system  on  a  single  pair  of 
wires.  Installation  costs  are  greatly  reduced,  whilst 
system  integrity,  sounder  options  and  programmed 
alarm organisation are significantly increased. 

The  ZP755R-2  features  the  wide  sound  distribution 
design, with an 'all around' sound output of 70 dBA. 
The  units  high  efficiency  acoustic  design  and  sound 
transducer,  enables  up  to  60  Addressable  Sensor 
Base  Sounders  to  be  connected  to  a  one  kilometre 
loop  of  1.5  mm

2

  cable.  A  plug-in  base  accepts  all 

loop  and  screen  connections,  prior  to  the  room 
sounder connection. A volume control is included for 
areas where a reduced sound output is required, but 
this  control  must  be  fully  clockwise  to  conform  to 
EN54 Part 3 sound output levels. 

The  ZP755R-2  range  features  a  unique  self  test 
facility  -  automatically  activated  during  routine 

sounder  testing.  A  built  in  microphone  circuit 
measures  sound  output  level  and  automatically 
signals  the  sounder  address  and  location  to  the 
control  panel,  should  volume  fall  below  the 
expected test level. 

In  systems  where  loop  lengths  or  current 
requirements  are  excessive,  ZP755R-2  sounders  can 
be  powered  directly  from  an  external  power  supply. 
All  ZP755R-2  sounders  incorporate  switch  settings 
enabling them to be assigned a unique address, which 
is polled by the panel every two seconds. 

Continuous,  intermittent  and  two-tone  outputs  are 
available,  from  which  any  combination  can  be 
chosen  to  provide  alert  and  evacuate,  two  stage 
alarms.  All  sound  types  comply  with  BS  5839  Part 
1:1988  recommended  frequencies  (in  accordance 
with EN54 Part 3). 

Moulded  in  high  impact  thermoplastic, the  sounder 
is available in either red or white. 

Specifications 

Design Specification:  EN54 Part 3 
Designation: 

Addressable Room Sounder 

Model No./Part No. 
ZP755RB-2R (red): 

177401 

ZP755R-2W (white):  177501 
Compatibility: 

Ziton analogue addressable systems 

Mounting: 

Surface - with plug-in base 

SPB-2R (red): 

180801 

SPB-2W (white): 

180901 

Addressing method:  7-way Dipswitch 
Wiring: 

2-core loop 

Monitoring: 
ZP loop - open and short circuit fault 
Sound output level - self test facility 
Sound output 
Tone 1 

continuous 980 Hz 

Tone 2 

intermittent 980 Hz (0.5 sec on/off) 

Tone 3 

two tone warble 980 Hz/670 Hz 

Sound distribution: 

Wide 