Ziton Wireless Manual Call Point Installation Guide
General
The Ziton wireless manual call point is available under
the following part number:
PART NO
VARIANT TYPE
ZPR485-3
Ziton wireless manual call point
The address of the unit is set when programming the
device to the system (see commissioning manual for
details). The installation must conform to BS5839:Part 1
(or applicable local codes).
Installation of Ziton wireless manual call point
Remove the back plate fixing screw. Retain this for future
use. Insert flat bladed instrument into the removal slot
and remove the back plate from the transmitter/battery
section. (See Figure 1).
Mount the back box 1.4m from the floor, using suitable
fixings and fasteners. A minimum of two mounting holes
must be used. Countersunk head screws must be used to
avoid the possibility of damage to the internal
components. (See Figure 2).
© 2015 EMS Security Group Ltd. All rights reserved
1 / 4
4 / 4
MK106 Iss7 24/07/15 AJM
© 2015 EMS Security Group Ltd. All rights reserved
Figure 1
Power jumper
Figure 2
Figure 3
Wall mounting positions
To ensure correct operation, connect the power jumper
across the PIN header on the battery PCB located on the
rear of the call point as shown in Figure 3.
Specification
Operating
Temperature
-10 to +70°C (ambient)
Storage
Temperature
0 to +35°C
Humidity
Up to 95% non-condensing
Supply
6x AA Alkaline (Panasonic LR6AD
Powerline / Varta 4006 Industrial)
IP Rating IP24
Operating
Frequencies
868 MHz
Output Transmitter
Power
Variable 0-14 dBm
Dimensions
89mm (W) 92mm (H) 70mm (D)
Weight 0.40kg
Regulatory information
Manufacturer
EMS Security Group Ltd.
Technology House, Sea Street,
Herne Bay, Kent, CT6 8JZ,
United
Kingdom
Year of
manufacture
See serial number on unit
Certification
Certification body
CPD Certificate
DOP
0359-CPR-0168
Approved to
EN54-11
EN54-25
Application
Intended for use in fire detection
and fire alarm systems in and
around buildings. Indoor use only.
European Union
directives
EMS Security Group Ltd hereby
declares that this device is in
compliance with the essential
requirements and other relevant
provisions of Directive 2014/53/EU
(R&TTE
directive).
2012/19/EU (WEEE directive):
Products marked with this symbol
cannot be disposed of as unsorted
municipal waste in the European
Union. For proper recycling, return
this product to your local supplier
upon purchase of equivalent new
equipment, or dispose of it at
designated collection points.
For more information see
www.recyclethis.info
Dispose of your batteries in an
environmentally friendly manner
according to your local regulations.
Contact information
For contact information, see ww.utcfireandsecurity.com
MK106 Iss7 24/07/15 AJM
12
0359