      EX SERIES 

EX6K(L) EX10K(L) EX3110K(L)     

EX3115K(L) EX3120K(L)     

 

USER  

MANUAL 

Summary of Contents for EX series

Page 1: ...EX SERIES EX6K L EX10K L EX3110K L EX3115K L EX3120K L USER MANUAL...

Page 2: ...Thank you for using our product Observe the warnings on the machine and manual strictly and properly keep the manual Do not operate the UPS before read safety notes and operation instruction...

Page 3: ...ction correct before switch on the UPS 2 Before moving or re wiring the UPS please disconnect the mains source and make sure UPS shut down completely Or else the output terminal may carry with live vo...

Page 4: ...the battery short circuit otherwise it may cause electric shock or fire Maintenance 1 The operating environment and storage method are two main factors affecting the lifetime and reliability of the UP...

Page 5: ...e UPS 12 2 5 Connect to Computer interface 13 2 6 Parallel Card Optional Accessory 14 2 7 Installation of Intelligent Card 18 2 8 EPO 20 2 9 Maintenance Switch 20 2 10 Dust proof Optional Accessory 22...

Page 6: ...ill still work on battery mode This manual is applicable to the following models l EX6K Standard model with built in batteries l EX6KL Long backup time model it is able to connect with the external ba...

Page 7: ...3 1 1 Description of symbols Meaning Symbols Meaning Notice or Fault High voltage risk AC DC Earth protection Circle Do not place with sundries Overload Battery inspection Power on off UPS...

Page 8: ...4 1 2 Front View 1 3 Rear View EX6KL EX10KL EX6K EX10K EX3110KL EX3115KL EX3120KL EX10K EX6K...

Page 9: ...5 EX6KL EX10KL EX3110KL EX3115KL EX3120KL...

Page 10: ...nance switch please remove the cover of and and then you can see parallel card and maintenance switch 2 The appearances above are available for standard rev and professional rev 1 4 Product Specificat...

Page 11: ...to bypass and alarm Crest Factor 3 1 THD THD 2 Linear Load Battery High ambient temperature shortens the battery s lifetimes Backup Time4minutes Full Load Depend on the capacity of external battery 3m...

Page 12: ...the mains power switch before installation the battery breaker also need to be cut off if it is a long backup time model L model Note 1 Installation and wiring must be performed in accordance with the...

Page 13: ...6m 8AWG 10m 8AWG 10m 8AWG 10m 6AWG 25m 6AWG 25m L 10AWG 6m 10AWG 6m 8AWG 10m 8AWG 10m 8AWG 10m 6AWG 25m 6AWG 25m Ba tt er y 10AWG 6m 10AWG 6m 8AWG 10m 8AWG 10m 8AWG 10m 6AWG 25m 6AWG 25m 10AWG 6m 10AW...

Page 14: ...corresponding input and output terminal if need connect batteries then connect the battery cables to the battery input terminal 4 Lock input output and battery wire on self locking frame by self lock...

Page 15: ...t terminal is useless EX6KL EX10KL Three phase model terminal block EX3110KL EX3115KL EX3120KL 5 Install the terminal block on back panel and screw tighten it 6 After connecting wires turn on main pow...

Page 16: ...unter the hazardous of electric shock Please comply with below procedure 1 A DC breaker must be connected between the battery pack and the UPS The capacity of breaker must be not less than the data sp...

Page 17: ...sition The UPS begins to charge the battery packs at the time Note The battery protective earth ground of UPS is case ground on the right of terminal block of UPS The symbol is 2 5 Connect to Computer...

Page 18: ...highly depended on N X is the optimal mode 2 Parallel installation Parallel function is a selectable function user can buy parallel function component consist of parallel card and parallel cable then...

Page 19: ...difference between the wires of input output of the UPSs is required to be less than 20 When the distance between the UPSs in parallel and the breaker panel is greater than 20 meters the difference b...

Page 20: ...16...

Page 21: ...17...

Page 22: ...power mode Startup in battery mode press ON OFF key of every UPS shortly the power supply of UPS will be available then press ON OFF button of one UPS long all other UPS will startup simultaneously al...

Page 23: ...allowed by SNMP l AS400 Card Optional Accessory Installing AS400 card in intelligent slot can achieve monitor function through AS400 system pin introduction of AS400 card used as power supply monitor...

Page 24: ...howing as below UPS power off urgently when pin1 and pin2 are on Short pin1 and pin2 UPS power off urgently when pin3 and pin4 are off 2 9 Maintenance Switch Optional Accessory User can maintain UPS t...

Page 25: ...21...

Page 26: ...stall dust proof 3 Install front panel on UPS 2 11 Box of Insulating Transformer Optional Accessory Insulating transformer can filter interference and make current more steady it can prevent other equ...

Page 27: ...d hold over 2s UPS will test batteries automatically Confirm Only in valid when UPS parameter adjust mode press down and hold over 1S to confirm and save parameters Select When press down both Select...

Page 28: ...z AF Autosense 50 60 Display remaining battery capacity battery voltage battery capacity and voltage parameter automatically switch the display every ten seconds Display AC input voltage and frequency...

Page 29: ...Alarm beeps continually Please contact with manufacturer or dealer 05 BUS Short circuit fault Fault sign T6 light Alarm beeps continually Please contact with manufacturer or dealer 06 Inverter soft st...

Page 30: ...ntact with manufacturer or dealer 29 Rectifier fault Fault sign T6 light Alarm beeps continually Please contact with manufacturer or dealer 32 Communication cable not connected Fault sign T6 light Ala...

Page 31: ...Board abnormal warning Fault sign T6 flash every 1s Alarm beeps every 1s Please contact with manufacturer or dealer 62 ID repeat alarm Fault sign T6 flash every 1s Alarm beeps every 1s Please contact...

Page 32: ...as connecting with AC main power except the sign on UPS Screen is Battery Mode 3 Shut down UPS when connecting with AC main power 1 Press Power Off button continuously more than three seconds to shutd...

Page 33: ...29 4 2 Operate mode 1 AC mode AC Mode 2 Battery Mode Battery Mode...

Page 34: ...30 3 Standby Mode Standby Mode 4 Bypass Mode Bypass Mode...

Page 35: ...d charging is recommended at the interval of 3 months Normally the battery should be charged and discharged every 4 to 6 months Charging should be begun after the UPS shout down automatically in the c...

Page 36: ...arest service center and dealer The transportation charges shall be born by the buyer within the warranty period This limited warranty does not apply to conditions as following u Out of warranty valid...