background image

H0548500_REVF - 2021/02

More documents on:

www.zodiac.com

Z200 Defrost

Z200

PI20 Defrost

PI20

Instructions for installation and use

 - 

English

Heat pump

Translation of the original instructions in French

EN

Summary of Contents for Z200

Page 1: ...H0548500_REVF 2021 02 More documents on www zodiac com Z200 Defrost Z200 PI20 Defrost PI20 Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Page 2: ...sed for any purpose other than that for which it was designed This appliance is not intended for use by individuals including children with impaired physical sensorial or mental abilities or persons l...

Page 3: ...on the appliance with wet hands or if the appliance is wet Before connecting the appliance to the source of supply ensure that the terminal block or supply socket to which the appliance will be conne...

Page 4: ...designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated s...

Page 5: ...rinciple 12 3 2 User interface presentation 12 3 3 I Operating 13 3 4 I User functions 14 Maintenance 15 4 1 I Winterizing 15 4 2 I Maintenance 15 Troubleshooting 18 5 1 I Device behaviour 18 5 2 I Er...

Page 6: ...A Z200 PI20 B Joint x2 C Screw in connector x2 D 40 adaptation x2 E 50 reduction x2 F Condensation evacuation kit 15 G Winterizing cap x2 H Winterizing cover Heating priority I Remote control J PAC N...

Page 7: ...cable section mm 3x2 5 3G2 5 Proof pressure bar 6 Service pressure bar 1 5 Max Discharge Suction Pressure bar 42 1 2 Max high pressure low pressure side pressure bar 42 1 2 Head loss mCE 1 1 5 1 1 5...

Page 8: ...on valve and user interface Ventilator Technical access door Pool water intake Pool water output Evaporator Grommet for heating priority cable run Location for drilling for remote control cable run de...

Page 9: ...und The device must not be installed In a closed and unventilated room In a location subject to high winds With the blowing towards a permanent or temporary obstacle window wall hedge awning etc less...

Page 10: ...o make it easier to work on the device water entry valve by pass valve water exit valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum distance To e...

Page 11: ...hnical specifications with a 30 mA dedicated differential circuit breaker circuit breaker or switch at the head of the line The electricity supply must correspond to the voltage indicated on the devic...

Page 12: ...p power contactor coil filtration timer power contactor tripolar or bipolar for the filtration system pump motor separate cable for the heating priority function heat pump terminal see wiring diagram...

Page 13: ...ing range sufficient to heat Cover the basin with a sheet bubble canopy canvas etc to prevent heat loss Take advantage of a period with mild outdoor temperatures on average 10 C at night your heat pum...

Page 14: ...adually so that the filter pressure is increased by 150g 0 150 bars Open valves A C and D fully then valve E by half the air which has built up in the heat pump condenser and the filtration circuit wi...

Page 15: ...the setpoint temperature is displayed fixed To read the water temperature it is imperative that the filtration is in operation and that the water flow indicator is fixed 3 4 2 Locking unlocking the k...

Page 16: ...nd other personnel working in the surrounding area must be made aware of the work carried out Work conducted in enclosed areas must be avoided Check for the presence of refrigerant The area must be an...

Page 17: ...nd intensity for the equipment being used Typically safe components are the only types on which work can be carried out in the presence of a flammable atmosphere when live The test appliance must fall...

Page 18: ...ll a manifold in order to be able to remove the refrigerant from various locations within the system 6 Make sure that the cylinder is located on the scales before starting recovery operations 7 Start...

Page 19: ...your heat pump cannot manage to deice its evaporator it will stop itself this means that the outdoor temperature is too low below 5 C for standard models 5 C for Defrost models The device is not worki...

Page 20: ...temperature too high 32 C maximum Wait until the temperature falls Flow controller blocked Check the flow controller Water condenser scaled up or blocked Clean the water condenser Outside temperature...

Page 21: ...p relay Earth KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor E1 High pressure switch SD2 Air temper...

Page 22: ...KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor HP High pressure switch SD2 Air temperature sensor...

Page 23: ...rty of their respective owners Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d informations enregistrement produit et support client For more in...

Reviews: