372 Fault tracing
6681
EFB comm loss
Programmable fault:
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the XD2D
connector on the control unit.
6682
EFB config file
Embedded fieldbus (EFB)
configuration file could not be
read.
Contact your local ABB representative.
6683
EFB invalid
parameterization
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
Check the settings in parameter group
.
6684
EFB load fault
Embedded fieldbus (EFB)
protocol firmware could not be
loaded.
Contact your local ABB representative.
Version mismatch between
EFB protocol firmware and
drive firmware.
6881
Text data overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6882
Text 32-bit table
overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6883
Text 64-bit table
overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
6885
Text file overflow
Internal fault.
Reset the fault. Contact your local ABB
representative if the fault persists.
7080
Option module comm
loss
Communication between drive
and an option module is lost.
See
(page
).
7081
Control panel loss
Control panel (or PC tool) has
stopped communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
Check the auxiliary code. The code
specifies the I/O port used as follows:
0:
Panel,
1:
Fieldbus interface A,
2:
Fieldbus interface B,
3:
Ethernet,
4:
D2D/EFB port).
7083
Panel reference
conflict
Use of saved control panel
reference in multiple control
modes attempted.
The control panel reference can only be
saved for one reference type at a time.
Consider the possibility of using a copied
reference instead of saved reference
(see the reference selection parameter).
7084
Panel/PC tool version
conflict
The current version of the
control panel and/or PC tool
does not support a function.
(For example, older panel
versions cannot be used as a
source of external reference.)
Update control panel and/or PC tool.
Contact your local ABB representative if
necessary.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...