376 Fault tracing
80A0
AI supervision
Programmable fault:
An analog signal is outside the
limits specified for the analog
input.
Check the auxiliary code (format XXXX
XYZZ). “Y” specifies the location of the
input (
0:
Control unit). “ZZ” specifies the
limit (
01:
AI1 under minimum,
02:
AI1
above maximum,
03:
AI2 under
minimum,
04:
AI2 above maximum).
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group
.
80B0
Signal supervision
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 1 function.
Check the source of the fault (parameter
).
80B1
Signal supervision 2
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 2 function.
Check the source of the fault (parameter
).
80B2
Signal supervision 3
(Editable message text)
Programmable fault:
Fault generated by the signal
supervision 3 function.
Check the source of the fault (parameter
).
9081
External fault 1
(Editable message text)
Programmable fault:
Fault in external device 1.
Check the external device.
Check setting of parameter
.
9082
External fault 2
(Editable message text)
Programmable fault:
Fault in external device 2.
Check the external device.
Check setting of parameter
.
9083
External fault 3
(Editable message text)
Programmable fault:
Fault in external device 3.
Check the external device.
Check setting of parameter
.
9084
External fault 4
(Editable message text)
Programmable fault:
Fault in external device 4.
Check the external device.
Check setting of parameter
.
9085
External fault 5
(Editable message text)
Programmable fault:
Fault in external device 5.
Check the external device.
Check setting of parameter
.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...