Parameters and firmware blocks
98
20.04
NEG SPEED ENA
FW block:
(see above).
Selects the source of the negative speed reference enable command. See parameter
.
Bit pointer: Group, index and bit
20.05
MAXIMUM CURRENT
FW block:
(see above).
Defines the allowed maximum motor current.
0…30000 A
Maximum allowed motor current.
20.06
MAXIMUM TORQUE
FW block:
(see above).
Defines the maximum torque limit for the drive (in percent of the motor nominal torque).
0…1600%
Maximum torque limit.
20.07
MINIMUM TORQUE
FW block:
(see above).
Defines the minimum torque limit for the drive (in percent of the motor nominal torque).
-1600…0%
Minimum torque limit.
20.08
THERM CURR LIM
FW block: None
Enables the thermal current limitation. Thermal current limit is calculated by the inverter thermal
protection function.
(0)
ENABLE
The calculated thermal current value limits the inverter output current
(i.e. motor current).
(1)
DISABLE
The calculated thermal limit is not used. If the inverter output current is
excessive, alarm IGBT OVERTEMP is generated and eventually the
drive trips on fault IGBT OVERTEMP.
Summary of Contents for ACSM1 Series
Page 1: ...ACSM1 Firmware Manual ACSM1 Speed and Torque Control Program...
Page 2: ......
Page 4: ......
Page 12: ...Table of contents 12...
Page 49: ...Drive control and features 49...
Page 282: ...Standard function blocks 282...
Page 306: ...Application program template 306...
Page 312: ...Control chain block diagrams 312...
Page 331: ...331...
Page 332: ...332...
Page 333: ......