Parameter address (Offset)
Data type
Function
Value range and coding
0042H
Byte
Mathematical functions
00H = off
01H = Addition
02H = Subtraction
0043H
Byte
Logic channel 1
00H = Channel 1
02H = Channel 2
03H = Channel 3
04H = Channel 4
05H = Channel 5
06H = Channel 6
0044H
Byte
Logic channel 2
00H = Channel 1
02H = Channel 2
03H = Channel 3
04H = Channel 4
05H = Channel 5
06H = Channel 6
0046H
Float
Threshold 1
-999...9999; 1,00E-9...9,99E+9 for logarithmic
display range
004AH
Float
Threshold 2
-999...9999; 1,00E-9...9,99E+9 for logarithmic
display range
004EH
Byte
Effective direction threshold 1
00H = min
01H = max
004FH
Byte
Effective direction threshold 2
00H = min
01H = max
0050H
Byte
Relay output for threshold 1
00H = off
01H = DO 1
...
14H = DO 20
0051H
Byte
Relay output for threshold 2
00H = off
01H = DO 1
...
14H = DO 20
0052H
Byte
Text line for threshold 1
00H = none
01H = Text line 1
...
0AH = Text line 10
0053H
Byte
Text line for threshold 1
as for threshold 1
0056H
Byte
Accounting: Mode
00H = off
01H = Mean
02H = Sum
03H = Sum and threshold
0057H
Byte
Accounting: External control
00H = off
01H = DI 1
...
0EH = DI 14
0058H
Byte
Accounting interval
00H = 15 min
01H = 30 min
02H = 1 h
03H = 2 h
04H = 6 h
05H = 8 h
06H = 12 h
07H = 1 d
08H = 7 d
09H = 1 month
0059H
Word
Synchronisation time = start
time interval
Hour (high byte)
00...17H = 0...23
Minute (low byte)
00...3BH = 0...59
Parameters