OBJ 1...10
WD Out
OBJ 1...10
WD in
OBJ 1...10
WD Bad
OBJ 1...10
Open Request On
OBJ 1...10
Open Fail
OBJ 1...10
Open Request Off
OBJ 1...10
Open Command On
OBJ 1...10
Open Command Off
OBJ 1...10
Close Request On
OBJ 1...10
Close Fail
OBJ 1...10
Close Request Off
OBJ 1...10
Close Command On
OBJ 1...10
Close Command Off
OBJ 1...10
Status Change On
OBJ 1...10
Status Change Off
5.5.3. Indicator object monitoring (CIN)
Indicator function takes care of circuit breaker and disconnector status monitoring. Indicator function is
only for indication purposes which means it doesn’t have any control functionality. For circuit
breaker/disconnector controlling use objects. Monitoring is based into the statuses of the con gured
IED binary inputs. In the relay the number of monitored indicators is dependent of available IO. For
status monitoring, typically 2 binary inputs are utilized per monitored indicator. Alternatively, indicator
status monitoring can be performed with single digital input using rising and falling edge monitoring and
logic virtual inputs. Selection of the type of object is selected in the mimic editor.
Outputs of the function are monitored indicator statuses Open/Close. Setting parameters are static
inputs of the function which are changed only by user input in the setup phase of the function.
Inputs for the function are binary status indications. The function generates general time stamped
ON/OFF events to the common event buffer from each of the open, close, bad and intermediate event
signals. Time stamp resolution is 1ms.
Input signals for indication status monitoring
Function uses available hardware and software digital signal statuses. These input signals are also
setting parameters for the function.
Table. 5.5.3. - 190. Monitor digital signal inputs used by the CIN function.
Signal
Range
Description
IndicatorX
Open
Input
DI1 …
DIx
(SWx)
Link to the physical binary input. Monitored indicator OPEN status. “1” means active open state of the
monitored indicator. Position indication can be done among binary inputs and protection stage signals
by using IEC-61850, GOOSE or logical signals.
IndicatorX
Close
Input
DI1 …
Dix
(SWx)
Link to the physical binary input. Monitored indicator CLOSE status. “1” means active close state of the
monitored indicator. Position indication can be done among binary inputs and protection stage signals
by using IEC-61850, GOOSE or logical signals.
Status change of the signals will always cause recorded event also in the indicators continuous status
indications. Events can be enabled or disabled according to the application requirements.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
216