background image

LED Behavior for the Nodes

Nodes do not sample inputs until they are communicating with the Gateway. The radios and antennas must be a minimum distance

apart to function properly. Recommended minimum distances are:

900 MHz 150 mW and 250 mW radios: 6 feet

900 MHz 1 Watt radios: 15 feet

2.4 GHz 65 mW radios: 1 foot

LED 1

LED 2

Node Status

Flashing green

Radio Link Ok

Flashing red

Flashing red

Device Error

Flashing red, 1 per 3 sec

No Radio Link

Sure Cross

®

 User Configuration Software

The User Configuration Software offers an easy way to link I/O points in your wireless network, view I/O register values, and set

system communication parameters when a host system is not part of the wireless network. The software runs on any computer

with the Windows Vista, Windows 7, Windows 8, or Windows 10 operating system.

Use a USB to RS-485 adapter cable to connect a standalone DX80 Gateway to the

computer. For DXM Controllers with an internal DX80 radio, connect a computer to the

DXM Controller using a USB or Ethernet connection. Download the most recent revisions

of the configuration software from Banner Engineering's website: 

www.bannerengineering.com/wireless

.

The USB to RS-485 adapter cable is not required for the DXM Controller. For standalone

DX80 Gateway devices use:

USB to RS-485 adapter cable model BWA-UCT-900 for 1 Watt radios

USB to RS-485 adapter cable model BWA-HW-006 for all other radios

Clearing the Event Counter

When using a host-controlled system, clear the counter by sending a control message on Node register 15. Control messages on

Node register 15 are acknowledged with the same value echoed to Node register 7.

1. Write 5121 (0x1401) to clear counter 1.
2. Write 5122 (0x1402) to clear counter 2.
3. Write 5123 (0x1403) to clear counters 1 and 2.

When you are not using a host-controlled system, a transition from 0 to 1 on the Node's output registers is needed to clear the

counter. Use this method on Gateway IO mapping to map inputs, such as a push button, to clear counter values.

1. Write output register 13 from 0 to 1 to clear counter 1.
2. Write output register 14 from 0 to 1 to clear counter 2.

Event Counter Presets from a Host-Controlled System

The event counter input can be preset from a host system using Advanced Control Messages. From the host system, each device

has allocated Node registers 7, 15, and 16 that send preset data to the event counter. When power is applied to the Node, the

counter value is reset to the last saved value. Setting the counter using the preset or clear functions saves the preset value or

zeroes.
The event counter input is a 32-bit value that can be preset using the parameter control codes 143 (0x8F) and 144 (0x90).

Parameter control code 143 writes the lower half [15:0] of the counter and code 144 writes the upper half [31:16] of the counter.
Defining the Counter Select Mask using the second bit position selects the counter. Set Modbus register 16 to the high or low data

value. Read Modbus register 7 for the transfer acknowledgment.

Node Reg 15

143 or 144 (0x8F or 0x90)

Counter Select Mask

Node Reg 16

Low or High Value

Node Reg 7

Acknowledge Code 143 or 144

Acknowledge Counter Select Mask

Preset the Counter to 20,567,001

To preset the counter to the value 20,567,001 (hex 0139 D3D9), follow these steps:
1. Write the upper word to the counter using control code 144 (0x90).

Node Reg 15

0x90

2

Node Reg 16

0139

Node Reg 7

0x90

2

Sure Cross

®

 Performance Universal Counter P16E Node

 

 

P/N 199134 Rev. D

www.bannerengineering.com - Tel: + 1 888 373 6767

5

Summary of Contents for Sure Cross P16E Series

Page 1: ...mentation technique complète des Performance Gateway or Node sur notre site www bannerengineering com pour les détails sur leur utilisation correcte les applications les notes de sécurité et les instructions de montage WARNING Do not use this device for personnel protection Using this device for personnel protection could result in serious injury or death This device does not include the self chec...

Page 2: ...to the Gateway 4 Form the wireless network by binding the Nodes to the Gateway If the binding instructions are not included in the datasheet refer to the product manual for binding instructions 5 Observe the LED behavior to verify the devices are communicating with each other For housed models the Gateway s LED 1 is solid green and the Node s LED 1 flashes green to indicate it is communicating wit...

Page 3: ...e Input Type PNP OFF ON Counter Discrete Value Input Type Float 1 V Threshold ON OFF Counter Discrete Value Input Type Float 300 mV Threshold ON ON Sample Report Rate 64 Seconds OFF OFF Sample Report Rate 16 Seconds OFF ON Sample Report Rate 4 Seconds ON OFF Sample Report Rate Modbus or UCT Configured ON ON Debounce Enabled OFF Debounce Disabled ON Counter 2 Input Type Event OFF Counter 2 Input Ty...

Page 4: ... for 2 4 GHz is fixed at about 65 mW EIRP 18 dBm making the 2 4 GHz Performance models automatically compatible with older 2 4 GHz models Wire for Power and I O XD4 XC4 CT2 PWR DO2 GND DO6 XC4 XC3 GND PWR DO5 DO1 XD3 XC3 CT1 CT1 Counter input 1 CT2 Counter input 2 DO1 NMOS output 1 DO2 NMOS output 2 DO5 NMOS output 5 DO6 NMOS output 6 PWR Power for sensors Counter Input Wiring for PNP Sensors Coun...

Page 5: ...21 0x1401 to clear counter 1 2 Write 5122 0x1402 to clear counter 2 3 Write 5123 0x1403 to clear counters 1 and 2 When you are not using a host controlled system a transition from 0 to 1 on the Node s output registers is needed to clear the counter Use this method on Gateway IO mapping to map inputs such as a push button to clear counter values 1 Write output register 13 from 0 to 1 to clear count...

Page 6: ... Node 8 Instance 112 N14 NMOS OUT 1 0 1 0 1 10 10 Node 16 1 Node 8 NMOS OUT 2 0 1 0 1 11 11 Node 16 2 Node 8 NMOS OUT 5 0 1 0 1 12 12 Node 16 3 Node 8 NMOS OUT 6 0 1 0 1 13 13 Node 16 4 Node 8 Clear Counter 1 0 1 0 1 14 14 Node 16 5 Node 8 Clear Counter 2 0 1 0 1 15 15 Node 16 6 Node 8 Control Message 16 16 Node 16 7 Node 8 Reserved Installing or Replacing the Battery DX80 E Models To replace the ...

Page 7: ...rete Input OFF Condition PNP Less than 5 V NPN Greater than 2 V or open Counter Input Event counter Input rating 1 Hz to 10 kHz For battery powered devices the recommended input rating is less than 1 kHz Rate frequency counter 1 Hz to 10 kHz Debounce select will filter the higher frequencies Thresholds PNP NPN See Discrete Input Conditions Float Selectable 1 V 300 mV Wiring Access Two 1 2 inch NPT...

Page 8: ... OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROFITS OR ANY INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE US...

Reviews: