Access from the user program
KL3356
44
Version: 2.3.0
5.5
Register description
All registers can be read or written via register communication.
Registers R0 to R31 (direct access)
These registers are used to parameterize the KL3356.
R0: status word
The status word contains information about internal signals, and provides an indication of errors that have
occurred.
Bit
Name
Description
R0.15 GainError
1
bin
The deviation of the gain correction factor is greater than specified in register
.
R0.14 LowVoltageCh2
1
bin
The strain gauge reference signal is smaller than specified in register
.
R0.13 NoRefCh2
1
bin
The internal reference voltage for channel 2 (strain gauge reference signal)
is missing.
R0.12 NoRefCh1
1
bin
The internal reference voltage for channel 1 (strain gauge differential signal)
is missing.
R0.11 OverloadCh2
1
bin
The strain gauge reference signal is above the valid range (max. 0xFFFF)
R0.10 OverloadCh1
1
bin
The strain gauge differential signal is above the valid range (max. 0xFFFF)
R0.9
ADCError
1
bin
No communication with the A/D converter.
R0.8
TestError
1
bin
Actual value from the test is outside the specified tolerance range.
R0.7
-
reserved
R0.6
MapCaliCounter
1
bin
. The calibration counters are shown in
registers
R0.5
CaliDataMapped 1
bin
. The last test results are shown in
registers
R0.4
ManCheckDone
1
bin
The manual test that was started with
has been completed.
R0.3
TestActive
1
bin
Manual testing is in progress.
R0.2
CaliActive
1
bin
Calibration (manual or automatic) is active.
R0.1
NegSignalCh2
1
bin
The strain gauge reference signal is negative.
R0.0
NegSignalCh1
1
bin
The strain gauge differential signal is negative.
R1: measured value register 1
• Raw data of the converters:
is not set, then the weight calculated by means of
is displayed in register R1.
R2: measured value register 2
• Raw data of the converters:
is not set, register R2 shows the strain gauge measuring signal.
• Calibration data:
is set, register R2 shows the preload of the measuring signal input.
• Calibration counter 0:
is set, register R2 shows the number of measured values that were identical
to the first measured value.