55
Configuration and adjustment variables
The following parameters (page
and
) do not revert to their factory setting when using the "Return to factory settings" function.
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
3120
2001 / 15
rPr
R/WS
Operating time reset to zero
Factory setting: 0
0 = "nO": No
2 = "rtH": Operating time reset to zero
The rPr parameter automatically falls back to nO as soon as the reset to zero is performed.
6001
201E / 2
Add
R/WS
Modbus: Drive address
Unit: 1
Factory setting: 1
Adjustment range: 1 to 247
6003
201E / 4
tbr
R/WS
Modbus: Transmission speed
Factory setting: 32
24 = "4.8" : 4800 bps
28 = "9.6" : 9600 bps
32 = "19.2": 19200 bps (Note: The remote display terminal can only be used with this value.)
6004
201E / 5
tFO
R/WS
Modbus: communication format
Factory setting: 3
2 = "8O1": 8 data bits, odd parity, 1 stop bit
3 = "8E1": 8 data bits, even parity, 1 stop bit (Note: The remote display terminal can only be
used with this value.)
4 = "8n1": 8 data bits, no parity, 1 stop bit
5 = "8n2": 8 data bits, no parity, 2 stop bits
6005
201E / 6
ttO
R/WS
Modbus: Time-out
Unit: 0.1 s
Factory setting: 100
Adjustment range: 1 to 100
6051
201E / 34
AdCO R/WS
CANopen: Drive address
Unit: 1
Factory setting: 0
Adjustment range: 0 to 127
6053
201E / 36
bdCO R/WS
CANopen: Transmission speed
Factory setting: 52
30 = "10.0": 10 kbps
34 = "20.0": 20 kbps
38 = "50.0": 50 kbps
52 = "125.0": 125 kbps
60 = "250.0": 250 kbps
68 = "500.0": 500 kbps
76 = "1000": 1000 kbps
8431
2036 / 20
FLO
R/WS
Forced local mode
Factory setting: 0
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
In forced local mode, the terminal block or display terminal regains control of the drive.
8432
2036 / 21
FLOC R/WS
Selection of the reference and control channel in forced local mode
Active only if LAC = 3
Factory setting: 1
In forced local mode, only the speed reference is taken into account. PI functions, summing
inputs, etc. are not active.
1 = "AI1": Analog input AI1, logic inputs LI
2 = "AI2": Analog input AI2, logic inputs LI
3 = "AI3": Analog input AI3, logic inputs LI
16 = "AIV1": Potentiometer, RUN, STOP buttons
163 = "LCC": Remote display terminal: LFr reference page
, RUN, STOP, FWD/REV buttons.