10164-L Sampler Control Cable for use with Isco and Sigma Autosamplers
'CR1000 Series Datalogger
'Declare Public Variables
Public Events
'Define Data Tables
DataTable (Sampler,1,1000)
Totalize (1,Events,FP2,False)
EndTable
'Main Program
BeginProg
Scan (1,Sec,0,0)
PulseCount (Events,1,1,0,0,1.0,0)
'Call Output Tables
CallTable Sampler
NextScan
EndProg
4.1.3 Inhibit Sampler’s Program
To inhibit a sampler’s onboard program, use the
PortSet()
instruction.
Whether the port should be set low or high depends on the onboard program’s
logic. For samplers such as the products manufactured by Isco, the onboard
program is inhibited by setting the control port low.
TABLE 4-3. Wiring for Example of Inhibiting an
Isco Onboard Program
Color Description CR800, CR850, CR1000, or CR3000
Purple Ground
G
Green Control
Port C1
Clear Shield
G
For example, if the cable is wired as shown in TABLE 4-3, a datalogger
program that includes the following CRBasic instruction will inhibit an Isco
sampler’s onboard program:
PortSet(
1,0
)
Above is only a portion of the CRBasic program.
NOTE
After an Isco sampler’s program has been inhibited, it can be allowed to run by
setting the port high.