7 Communication Profile Area
The section describes the general layout of the EtherCAT
communication area which is supported. The process data
objects are defined in this area.
7.2 1000-1FFF Communication Object Area
7.2.1 1000 - 1FFF Communication Object Overview
Index (hex) Object (Symbolic Name) Name
Type
Read/Write
1000
VAR
Device type
UNSIGNED32
ro
1001
VAR
Error register
UNSIGNED8
ro
1002
VAR
Manufacturer status register
UNSIGNED32
ro
1003
ARRAY
Pre-defined error field
UNSIGNED32
ro
1008
VAR
Manufacturer device name
VISIBLE_STRING
constant
1009
VAR
Manufacturer hardware version
VISIBLE_STRING
constant
100A
VAR
Manufacturer software version
VISIBLE_STRING
constant
1010
ARRAY
Store parameters
UNSIGNED32
rw
1011
ARRAY
Restore default parameters
UNSIGNED32
rw
1018
RECORD
Identity object
Identity (23h)
ro
1100
VAR
EtherCAT address
UNSIGNED16
ro
1110
ARRAY
Virtual MAC address
UNSIGNED8
ro
1111
ARRAY
Virtual IP address info
UNSIGNED8
rw
1616
ARRAY
Receive PDO parameter
UNSIGNED32
rw
1A16
ARRAY
Transmit PDO parameter
UNSIGNED32
rw
1C00
RECORD
Sync manager type
UNSIGNED8
ro
1C12
RECORD
RxPDO assign
UNSIGNED16
rw
1C13
RECORD
TxPDO assign
UNSIGNED16
rw
2000-5FFF
Vendor specific area
See
7.3.1 2000h-5FFFh Danfoss Specific Object Area
6040
VAR
Control word
UNSIGNED16
rw
6041
VAR
Status word
UNSIGNED16
ro
6042
VAR
Vl_target_velocity
SIGNED16
rw
6043
VAR
Vl_velocity_demand
SIGNED16
ro
6044
VAR
Vl_actual_value
SIGNED16
ro
6046
ARRAY
Vl_velocity_min_max_amount
UNSIGNED32
ro
6048
RECORD
Vl_velocity_acceleration
See description
ro
6049
RECORD
Vl_velocity_acceleration
See description
ro
604C
ARRAY
Vl dimension factor
UNSIGNED32
rw
6060
VAR
Modes of operation
UNSIGNED8
rw
6061
VAR
Modes of operation display
UNSIGNED8
ro
6502
VAR
Supported frequency converter mode UNSIGNED32
ro
6504
VAR
Frequency converter manufacture
VISIBLE_STRING
ro
Table 7.1 Communication Object Overview
Communication Profile Area
MCA 124 EtherCAT Operating Instruction
MG92A302 - VLT
®
is a registered Danfoss trademark
25
7
7