5.1.10 13-** Smart Logic
Par.
No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
13-0* SLC Settings
13-00 SL Controller Mode
[0] Off
1 set-up
TRUE
-
Uint8
13-01 Start Event
[39] Start command
1 set-up
TRUE
-
Uint8
13-02 Stop Event
[40] Drive stopped
1 set-up
TRUE
-
Uint8
13-03 Reset SLC
[0] Do not reset SLC
1 set-up
TRUE
-
Uint8
13-1* Comparators
13-10 Comparator Operand
[0] Disabled
1 set-up
TRUE
-
Uint8
13-11 Comparator Operator
[1] Approx.Equal (~)
1 set-up
TRUE
-
Uint8
13-12 Comparator Value
0.0 N/A
1 set-up
TRUE
-1
Int32
13-2* Timers
13-20 SL Controller Timer
0.0 s
1 set-up
TRUE
-2
uint_32
13-4* Logic Rules
13-40 Logic Rule Boolean 1
[0] False
1 set-up
TRUE
-
Uint8
13-41 Logic Rule Operator 1
[0] Disabled
1 set-up
TRUE
-
Uint8
13-42 Logic Rule Boolean 2
[0] False
1 set-up
TRUE
-
Uint8
13-43 Logic Rule Operator 2
[0] Disabled
1 set-up
TRUE
-
Uint8
13-44 Logic Rule Boolean 3
[0] False
1 set-up
TRUE
-
Uint8
13-5* States
13-51 SL Controller Event
[0] False
1 set-up
TRUE
-
Uint8
13-52 SL Controller Action
[0] Disabled
1 set-up
TRUE
-
Uint8
5.1.11 14-** Special Functions
Par.
No. #
Parameter description
Default value
2-set-up
Change
during
operation
Conver-
sion index
Type
14-0* Inverter Switching
14-01 Switching Frequency
ExpressionLimit
All set-ups
TRUE
-
Uint8
14-03 Overmodulation
[1] On
All set-ups
FALSE
-
Uint8
14-08 Damping Gain Factor
96.0 %
All set-ups
TRUE
0
uint_8
14-1* Mains On/Off
14-12 Function at Mains Imbalance
[0] Trip
1 set-up
TRUE
-
Uint8
14-2* Reset Functions
14-20 Reset Mode
[0] Manual reset
All set-ups
TRUE
-
Uint8
14-21 Automatic Restart Time
10.0 s
All set-ups
TRUE
0
uint_16
14-22 Operation Mode
[0] Normal operation
All set-ups
TRUE
-
Uint8
14-27 Action At Inverter Fault
[1] Warning
All set-ups
TRUE
-
Uint8
14-4* Energy Optimising
14-40 VT Level
90 %
All set-ups
FALSE
0
uint_8
14-41 AEO Minimum Magnetisation
66 %
All set-ups
FALSE
0
uint_8
14-5* Environment
14-50 RFI Filter
[1] On
1 set-up
FALSE
-
Uint8
14-51 DC-Link Voltage Compensation
[1] On
All set-ups
FALSE
-
Uint8
14-52 Fan Control
[0] Auto
1 set-up
TRUE
-
Uint8
14-53 Fan Monitor
[1] Warning
1 set-up
TRUE
-
Uint8
14-55 Output Filter
[0] No Filter
1 set-up
FALSE
-
Uint8
14-6* Auto Derate
14-63 Min Switch Frequency
1.0 kHz
1 set-up
FALSE
0
uint_16