MODBUS
FC013 Fancoil controller
Release 18.12.2014 ver. 01900
program Monday
Event 6 time
64 LSB
64 MSB
R,W
EEPROM
time schedule, Monday, time of
event No. 6, in mins since 0:00
(midnight)
(default = 06:00 h, 0x0168)
e.g. 121 ... 2h 1min
program Monday
Event 6 value
65 LSB
65 MSB
R,W
EEPROM
time schedule, Monday, event No.
6, value
(default = disabled, 0x8000)
0 ... day/comfort
1 ... night/standby
2 ... off/depression
bit 15 = 1 ... event is
disabled
program
Tuesday Event 1
time
66 LSB
66 MSB
R,W
EEPROM
time schedule, Tuesday, time of
event No. 1, in mins since 0:00
(midnight)
(default = 06:00 h, 0x0168)
e.g. 121 ... 2h 1min
...
...
...
...
...
program Sunday
Event 6 value
137 LSB
137 MSB
R,W
EEPROM
time schedule, Sunday, event No.
6, value
(default = disabled, 0x8000)
0 ... day/comfort
1 ... night/standby
2 ... off/depression
bit 15 = 1 ... event is
disabled
uptime
1000 LSB
1000 MSB
1001 LSB
1001 MSB
R
uptime (s)
number of seconds after
last power on / reset
SW reset
1002 LSB
1002 MSB
R, W RAM
If a non-zero value is written and
SW reset is enabled (see Status
LSB bit 1), the device is restarted.
Real time table
Commissioning mode: when powered on with pushbutton pushed, after several seconds the
commissioning mode is activated with manual control over outputs and indication of inputs. After 10
mins after last push or after reboot the controller goes to normal (control) mode. In the commissioning
mode, all Modbus data are read-only.
Addr.
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
Function
Range
49 LSB
secs
00-59
49 MSB
0
mins
00-59
10xhours
hours
00-23
50 MSB
0
0
0
0
0
day
01-07
51 LSB
0
0
date
01-31
51 MSB
0
0
0
10xmonth
month
01-12
52 LSB
year
00-99
52 MSB
0
0
0
0
0
0
0
0
not used
00
10xsecs
seconds
10xmins
minutes
year
10xyear
50 LSB
day
date
10xdate
month
hours
10xhours
0