Communication registers cont.
address
description
func.
type
atr.
259
Read current and write new
number of stop bits:
0:1 bit/1:1,5 bita/2:2 bity
03
06
int
R/W
260
Restore the factory settings:
Set the value 1.
06
int
W
Note!
Changes in communication parameters (baud rate, number of stop bits,
parity) are only taken into account only after the power is restarted.
1024
÷
1025
Module working time [s]
R1024×256²+R102
03
int
R
1026
÷
1027
Serial number
R1026×256²+R1027
03
int
R
1028
Production date: 5 bits – day;
4 bits – month; 7 bits – year
(without 2000)
03
int
R
1029
Software version
03
int
R
1030
Execution: 0 – Lo; 1 – Hi
03
int
R
1031
÷
1035
Identifier:
F& | F | MB | -4 | LI
03
int
R
1039
Configuration jumper:
0 – open; 1 – close
03
int
R
Converter does not support broadcast commands (address 0).