FS-8704-07 Allen Bradley PCCC (TCP/IP) Driver Manual
Page 8 of 15
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
: support@fieldserver.com
5.3
Client Side Map Descriptors Client Side Map Descriptors
5.3.1
FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is
to be stored in the FieldServer
One of the Data Array names from Section 4.
Data_Array_Offset
Starting location in Data Array
0 to (Data_Array_Length -1) as specified in
Section 4
Function
Function of Client Map Descriptor
Rdbc, Wrbc, Wrbx
5.3.2
Driver Related Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from One of the Node Names specified in Section 5.2
File_Type
File type in PLC
N, B, F, I, O, S
3
File_Number
File Number in PLC
0-65535
4
Address
Starting address of read block
0-255
Data_Array_Low_Scale*
Scaling zero in Data Array
-32767 to 32767,
0
Data_Array_High_Scale* Scaling max in Data Array
-32767 to 32767,
100
Node_Low_Scale*
Scaling zero in Connected Node
-32767 to 32767,
0
Node_High_Scale*
Scaling max in Connected Node
-32767 to 32767,
100
AB_Command
Override the default command
Unprotected Command Typed
3
Not all PLC’s can support all File_Types. Refer to DFS for further information.
4
Other device might not be supporting the full range, e.g. SLC5 supports only 0-255 and latest PLC5 till now supports only 0-1999