10
5.4 MP 204 control register block
Registers in this block can be read by means of function codes 0x03 and/or 0x04. They can be written as holding registers with function
codes 0x06 and 0x10. The MP 204 will react to its last received command, no matter whether this command was triggered via Modbus,
with the R100 remote control or on the MP 204 operator buttons.
Address
Register name
Description
00101
ControlRegister
Bit 0: ResetAlarm
Control bit that resets alarms and warnings.
0 = No resetting
1 = Resetting alarm.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.
ControlRegister
Bit 1: CommandedTrip
Control bit that command-trips the MP 204.
Status is obtained from OperationMode (register 00202).
0 = No trip
1 = Trip.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.
ControlRegister
Bit 2: OnOffReq
Control bit that switches the pump on and off.
Status is obtained from OperationMode (register 00202).
0 = Off (stop)
1 = On (start).
ControlRegister
Bit 3: ProtectionEnabled
Control bit that enables/disables the general protection.
Status is obtained from StatusRegister (register 00201, bit 1).
0 = Protection disabled
1 = Protection enabled.
ControlRegister
Bit 5: ResetStartCounter
Control bit that resets the NumberOfStartsTripCounterHI/LO (registers 00342 and 00343).
0 = No resetting
1 = Resetting.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.
ControlRegister
Bit 6:
ResetRestartCounter
Control bit that resets the AutoRestartsTripCounterHI/LO (registers 00344 and 00345).
0 = No resetting
1 = Resetting.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.
ControlRegister
Bit 7: ResetLogs
Control bit that resets the maximum/minimum voltage and current logs and maximum number of
starts per hour log (registers 00348, 00349, 00350, 00351 and 00352).
0 = No resetting
1 = Resetting.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.
ControlRegister
Bit 8: ResetHourCounter
Control bit that resets the OperationTimeTripCounterHI/LO (registers 00338 and 00339).
0 = No resetting
1 = Resetting.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.
ControlRegister
Bit 9: ResetEnergyCounter
Control bit that resets the EnergyTripCounterHI/LO (registers 00332 and 00333).
0 = No resetting
1 = Resetting.
This control bit is triggered on rising edge only, i.e. setting logical 0 to 1.
See section
5.2 CIM configuration register block
, address 00005, for acknowledgement
behaviour.