background image

Parameter 19 (Ftc) – Floor Temperature Calibration

This  parameter  defines  the  offset  value  for  floor  temperature.  Should  the  external  floor 
temperature sensor not be correctly calibrated then temperature changes are able to be 
adjusted by up to +/- 9.5°C or +/- 17°F. This value will be added or subtracted from the floor 
temperature sensor reading.
Factory default value is 0.

Parameter 20 (HYS) – HYSTERESIS (HYS)

The hysteresis value for temperature control. The thermostat will stabilize the temperature 
with selected hysteresis. For example, if the SET POINT is set for 25°C and HYSTERESIS 
is set for 0.5°C the thermostat will change the state to HEATING if the temperature will be 
lower than 24.5°C and it will change the state to idle if temperature reaches 25.5°C. 
The hysteresis can be changed from 0.1°C up to a maximum of 9.5°C in Celsius mode and 
from 0.1°F to 17°F in Fahrenheit mode. 
Factory default values are 0.5°C or 0.9°F.

Parameter 21 (dIF) – Temperature difference to send to controller 

The thermostat will send a new temperature to the gateway only in case if the temperature 
change is greater or equal than the value specified in this parameter.
From 0.1C to 1.0C can be chosen.
Factory default value is 0.2C

Note:

 The thermostat is very sensitive to changes of ambient temperature and can often vary 

by ±0.1C, therefore it is recommended to set this parameter from 0.2 and above to reduce the 
load on your Z-Wave network.

DISPLAY BRIGHTNESS

The thermostat has two states of brightness. 
Active state – when press any key and commence adjustments. 
Inactive state – after five seconds of inactivity it will revert to inactive state. 
The display brightness in either state can be adjusted. 

Parameter 22 (brH) – Display brightness high level

The brightness level can be selected in the active state from values 1 (lowest brightness) to 4 
(highest brightness) but the level cannot be lower than the level of brightness for the inactive 
state (param 23).
Factory default value is 4.

Parameter 23 (brL) – Display brightness low level

This parameter defines the brightness level of the display in the inactive state. The level can 
be selected from values 1 to 4 but the level cannot be higher than the level of brightness for 
the active state (param 22).
Factory default value is 3.

Parameter 24 (Abr) – Auto brightness

The thermostat can adjust its display brightness automatically depending on the illumination 
of the ambient environment. The comfort brightness of the screen can be chosen depending 
on the room illumination in Parameters 25, 26 and 27. 
Value 1 = Active the function, Value 0 = Inactive the function
Factory default value is 1.

Note:

 The illumination of the environment can be checked at any time in the centre of the 

display (on time position) in the device MENU on Parameter 24 or via your Z-Wave gateway

Parameter 25 (Ab1) – Auto brightness level 1 max lumens

The value indicates the maximum level of ambient illumination during which the brightness of 
the display will be at level 1 (at the lowest level). For example if this parameter value is set 30 
and the ambient illumination is in range 0-30 the display will be in lowest brightness level. As 
soon as the illumination will be 31 or higher the display brightness will be changed to Level 2. 
Factory default value is 30.

Parameter 26 (Ab2) – Auto brightness level 2 max lumens

This parameter indicate the maximum illumination for display brightness level 2. In case if the 
illumination is in range Parameter 25 (Ab1) - Parameter 26 (Ab2) the display brightness will 
be on level 2. If the illumination drops below the value of parameter 25 the brightness of the 
display will be decreases to level 1, and if the illumination increases beyond the value of 
parameter 26 the display brightness will rise to level 3.
Factory default value is 200.

Parameter 27 (Ab3) – Auto brightness level 3 max lumens

This parameter indicate the maximum illumination for display brightness level 3. In case if 
ambient illumination raise above this value the display brightness will be changed to Level 4 
Factory default value is 3000.

Parameter 28 (bsA) – Basic Sat Action

This parameter defines to which mode the thermostat operating mode will be changed to if 
the Basic Set command is received.
If the received value of the Basic Set command is 0 (OFF state) the thermostat will go to MAN 
mode and switch off the heating element (IDLE mode).
If the received value of the Basic Set command is 1 or higher (ON state) the thermostat will 
change its mode regarding the value defined in this parameter.
If the parameter value is 1 the thermostat will go to the COM operating mode, value 2 is for 
the TIME mode, Value 3 is for the DRY mode, Value 4 is for the ECO mode, Value 5 is for the 
VAC, Value 6 is for the MAN.
If the parameter value is 6 (change to manual mode) and the Basic Set value is 1 or higher 
(ON) the thermostat will go to  the MAN mode and switch ON the HEAT mode. 
Factory default value is 6.

Parameter 29 (nEt) – INCLUSION / EXCLUSION MODE

If the thermostat is included in the z-wave network the antenna will be indicated in the main 
display and Inc will be indicated in the Param value. If the thermostat is not included in the 
network, no antenna will be indicated in the main display and the Param value will be ECL.
To  include  or  exclude  the  thermostat  into/from  your  home  automation  gateway,  activate 
inclusion or exclusion mode on your gateway then go to Param 29 in the device Menu and 
press “+” key for inclusion and the “-” key for exclusion.
For more details go to point “Z-Wave Functions” – “Network“of this manual.

Parameter 30 (Prr) – Power Meter values & reset

The Heltun thermostat monitors the load and total power consumption. The current load is 
indicated in this Param values in the center of display (time position) in W. The data of total 
consumption in kWh is indicated in the top right corner of the display. 
If the device is included to the Z-Wave network it will also send the data of the current load 
and total consumption to the main controller.
The  thermostat,  even  when  the  electricity  is  disconnected,  maintains  the  electric 
consumption record in its memory. 
To  reset  the  consumption  memory  press  and  hold  “+”  key  (about  3  seconds)  until  the 
parameter total consumption value will be changed to 0.

Z-WAVE DEVICE TYPE:

GENERIC_TYPE_THERMOSTAT
SPECIFIC_TYPE_SETPOINT_THERMOSTAT

Supported Command Classes:

COMMAND_CLASS_BASIC,
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE,
COMMAND_CLASS_THERMOSTAT_MODE, 
COMMAND_CLASS_THERMOSTAT_SETPOINT,
COMMAND_CLASS_SENSOR_MULTILEVEL,
COMMAND_CLASS_METER, 
COMMAND_CLASS_CLOCK, 
COMMAND_CLASS_ZWAVEPLUS_INFO,
COMMAND_CLASS_TRANSPORT_SERVICE,
COMMAND_CLASS_SECURITY,
COMMAND_CLASS_SECURITY_2, 
COMMAND_CLASS_VERSION, 
COMMAND_CLASS_ASSOCIATION, 
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION,
COMMAND_CLASS_ASSOCIATION_GRP_INFO, 
COMMAND_CLASS_MANUFACTURER_SPECIFIC 

,

COMMAND_CLASS_DEVICE_RESET_LOCALLY, 
COMMAND_CLASS_POWERLEVEL, 
COMMAND_CLASS_SUPERVISION, 
COMMAND_CLASS_CONFIGURATION, 
COMMAND_CLASS_FIRMWARE_UPDATE_MD

THERMOSTAT SETTINGS USING Z-WAVE PROTOCOL (GATEWAY)

All configuration parameters are accessed through 
COMMAND_CLASS_CONFIGURATION

6) PA – Power reg Air sensor: Regulation is based on the time set by Params 05 and 
06  but  also  controlled  by  the  internal  air  temperature  sensor  ensuring  that  the  room 
temperature remains within the set limits. The air temperature limits are specified in Params 
13 and 14.
7) PF – Power reg Floor sensor parameters: Regulation is based on the time set by 
Params 05 and 06 but also controlled by the floor temperature sensor ensuring that the floor 
temperature  remains  within  the  set  limits.  The  floor  temperature  limits  are  specified  in 
Params 15 and 16.

For example: 
In FA mode the SET POINT is set to 30°C, AtL is set to 24°C and AtH is set to 27°C:
a) If floor temperature is lower than 30°C and the room temperature is lower than 27°C the 
thermostat will operate in HEATING mode.
b) If the floor temperature is higher than 30°C or the room temperature is higher than 27°C 
then the thermostat will go to IDLE mode which switches off the heater. 
c) If the room temperature is lower than 24°C the thermostat will operate in HEATING mode 
even though the floor temperature is higher than 30°C.

Attention: 

Be careful when setting the lower limitation (Param 13 - AtL and Param 15 – FtL) 

to be sure that the value is not too high and it can be reached. Otherwise the thermostat will 
always operate in the HEATING mode.

Note: 

For safety reasons the thermostat will go to the IDLE mode if the floor temperature 

reaches 40°C despite the parameter settings.

Note: 

If there is no floor sensor installed or it becomes damaged (indicated by ” – “ in the 

“FLOOR  TEMP”)  the  regulation  mode  (A)  will  be  automatically  selected  as  the  source 
sensor. This can only be changed to (P) or (PA). Regulation modes (F), (FA), (AF) and (PF) 
will not be able to be selected. 
Factory default value is F.

Parameter 05 (POn) – Power regulation ON time

This parameter defines floor HEATING time in minutes when Power Regulator (P, PA or PF) 
is selected as the source sensor in Param 04. Time can be changed in range 10 – 90 minutes.
Factory default value is 15 minutes.

Parameter 06 (POf) – Power regulation OFF time

Floor IDLE time in minutes when Power Regulator (P, PA or PF) is selected as the source 
sensor. Time can be changed in range 10 – 90 minutes.
Factory default value is 15 minutes.

Parameter 07 (dry) – Dry Time

This parameter specifies how long in minutes the thermostat will be in HEATING mode when 
the DRY mode is selected. After this time the thermostat will go to the TIME mode. The time 
range is 5-90 minutes.
Factory default time is 30 minutes.

Parameter 08 (tCr) – Time correction by main controller

If  this  parameter  value  is  1  and  the  thermostat  is  connected  to  Z-Wave  gateway  the 
thermostat time and weekday will be periodically polled and corrected from the gateway. To 
switch off the auto correction set the parameter value 0.
Factory default value is 1.

Parameter 09 (tfo) – Time format

24-hours or 12-hours time indication format can be chosen.
0 = 24 hours format. 1 = 12 hours (AM/PM) format
Factory default value is 0.

Parameter 10 (day) – Week day

This parameter allows manually adjustment of the day of the week in case the thermostat is 
not connected to any gateway or Parameter 08 (auto correction) selected as 0.

Parameter 11 (tIH) – Hour

This parameter allows manual adjustment of the hours.

Parameter 12 (tIL) – Minute

This parameter allows manual adjustment of the minutes.

Parameter 13 (AtL) – Air Temperature Minimum (Lowest level)

Room temperature low limit. Reading of internal temperature sensor. It has effect only if FA or 
PA is selected as the source sensor in Param 04
Factory default value is 21°C or 70°F.

Note: 

AtL value cannot be higher than AtH value - 1°C

Parameter 14 (AtH) – Air Temperature Maximum (Highest level)

Room temperature high limit. Reading of the internal temperature sensor. It has effect only if 
FA or PA is selected as the source sensor.
Factory default value is 27°C or 81°F.

Note:

 AtH value cannot be lower than AtL value + 1°C

Parameter 15 (FtL) – Floor Temperature Minimum (Lowest level)

Floor temperature low limit. Reading of external NTC temperature sensor. It has effect only if 
AF or PF are selected as the source sensor. 
Factory default value is 18°C or 64°F.

Note: 

FtL value cannot be higher than FtH value - 1°C

Parameter 16 (FtH) – Floor Temperature Maximum (Highest level)

Floor temperature high limit. Reading of the external NTC temperature sensor. It has effect 
only if AF or PF are selected as the source sensor. 
Factory default value is 32°C or 90°F.

Note: 

FtH value cannot be lower than FtL value + 1°C

Parameter 17 (FSr) – Floor sensor resistance

If the external floor NTC temperature sensor is used it is necessary to select the correct ohm 
value (resistance) of the sensor. 1 – 100 kΩ is available to select. In the box is included one 
floor NTC 10kΩ temperature sensor with a three metre connection wire.
Factory default value is 10kΩ.

Note:

 If the floor sensor is disconnected or damaged “–” will indicate on the display FLOOR 

TEMP field.

Parameter 18 (Atc) – Room Air Temperature Calibration

This  parameter  defines  the  offset  value  for  room  air  temperature.  If  the  internal  air 
temperature  sensor  is  not  correctly  calibrated  changes  of  temperature  can  be  made  by 
adjusting the values by up to +/- 9.5°C or +/- 17°F. This value will be added or subtracted from 
the internal air temperature sensor reading.
Factory default value is 0

Security:

 S0, S2 unauthorized and S2 authorized inclusion modes are supported. If you use 

S2 authorized inclusion mode the security key should be used in inclusion process.

NOTE:

 Be sure to save this key. Without the key it is impossible to perform an inclusion in S2 

authorized mode.

Exclusion 

To exclude the thermostat from the Z-Wave network
1. Go to “SETTINGS” mode by pressing and holding the      key for 3 seconds
2. Go to “Parameter 29 – nEt” of the menu
3. In the value position the current state of network state will be displayed. It should be “Inc”. if 
the “ECL” is indicated the device is already excluded.
4. Start the exclusion from the gateway. 
5. Press the “–” key to start the exclusion process 
6. Lines will be moving in the value position.
7. The “Ecl” should appear with successful deletion.
8. If the “Err” appear then start the exclusion process again. 

If the thermostat is included in the network, in the bottom right corner of the main screen the 
antenna  icon  will  be  displayed  with  connection  lines        .  If  not  on  the  network  it  will  be 
displayed without lines     .

Association

Association enables the thermostat to control other Z-Wave products from the network.
Up to ten other products from different manufacturers can be within the association grouping.
The thermostat has two association groups:
Group 1 is for Life Line and used to connect Z-Wave gateway.
Through Group 2 the thermostat sends Basic Set command. It sends Basic Set command 
with value 0 (Off state) when thermostat goes to IDLE mode and sends 255 (ON state) when 
the thermostat goes to HEATING mode.

CHILD LOCK – LOC

To activate the child lock mode, press and hold the        key till the icon      will be indicated in 
the bottom center of the display (about 5 seconds). To deactivate the child lock press the key 

dddd

until the icon      disappears.

FACTORY RESET – RES

By pressing and holding the “MODE” key for 6 seconds, the thermostat will enter the Factory 
Reset mode and “Res” will appear in left bottom corner, “y” in top left corner and “n” in top right 
corner. Press “+” key if reversion to factory reset is required or the key        to cancel. The 
factory  reset  will  change  all  the  parameters  to  the  original  factory  defaults  and  will  also 
exclude from the Z-Wave network.

Z-WAVE NETWORK

Inclusion

 

To include the thermostat in the Z-Wave network 
1. Go to the “SETTINGS” mode by pressing and holding the      key for 3 seconds
2. Go to “Parameter 29 – nEt” of the menu by using the         key for scrolling up and the 
“MODE” key for scrolling down in parameters.
3. In the value position will be seen the current state of the network. It should be ECL. If Inc is 
indicated, anexclusion must be first performed.
4. Start the inclusion mode from the gateway 
5. Press “+” key to start inclusion process 
6. Lines will be moving in value position.
7. The “Inc” should appear in the value position if the inclusion has been successful. The “Err” 
will appear if the inclusion was not completed.

Note:

 In case the device has been part of the Z-Wave network before and not excluded 

since, inclusion is not possible. In this case, exclusion must be performed before inclusion.

If the thermostat is included in the network, in the bottom right corner of the main screen the 
antenna icon will be displayed with connection lines      . If not on the network then it will be 
displayed without lines     .

2-YEAR LIMITED WARRANTY

Heltun warrants this product to be free from defects in the workmanship or materials, under 
normal  use  and  service,  for  a  period  of  two  (2)  years  from  the  date  of  purchase  by  the 
consumer. If at any time during the warranty period the product is determined to be defective 
or malfunctions, Heltun shall repair or replace it (at Heltun's option).
If the product is defective,
(i) return it, with a bill of sale or other dated proof of purchase, to the place from which you 
purchased it; or
(ii) contact Heltun Customer Care at support@heltun.com. Customer Care will make the 
determination whether the product should be returned or whether a replacement product can 
be sent to you.

THIS  WARRANTY  DOES  NOT  COVER  REMOVAL  OR  REINSATLLATION  COSTS. 
THIS  WARRANTY  SHALL  NOT  APPLY  IF  IT  IS  SHOWN  BY  HELTUN  THAT  THE 
DEFECT  OR  MALFUNCTION  WAS  CAUSED  BY  DAMAGE  WHICH  OCCURRED 
WHILE  THE  PRODUCT  WAS  IN  THE  POSSESSION  OF  A  CONSUMER  THIS 
WARRANTY SHALL NOT OBLIGATE HELTUN FOR ANY LABOR COSTS AND SHALL 
NOT  APPLY  TO  DEFECTS  IN  WORKMANSHIP  OR  MATERIALS  FURNISHED  BY 
YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE THERMOSTAT ITSELF. 
IMPLIED WARRANTIES OF MERCHANTABILITY OF FITNESS FOR A PARTICULAR 
PURPOSE  SHALL  BE  LIMITED  IN  DURATION  TO  THE  AFORESAID  TWO  YEAR 
P E R I O D.  H E LT U N'S  L I A B I L I T Y  F O R  I N C I D E N TA L  O R  C O N S E Q U E N T I A L 
DAMAGES,  OTHER  THAN  DAMAGES  FOR  PERSONAL  INJURIES,  RESULTING 
FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE 
LIMITED WARRANTY IS EXPRESSLY EXCLUDED. THIS LIMITED WARRANTY IS 
VOID  IF  DEFECT(S)  RESULT  FROM  FAILURE  TO  HAVE  THIS  THERMOSTAT 
INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR. IF 
THE  LIMITED  WARRANTY  IS  VOID  DUE  TO  FAILURE  TO  USE  A  QUALIFIED 
CONTRACTOR,  ALL  DISCLAIMERS  OF  IMPLIED  WARRANTIES  SHALL  BE 
EFFECTIVE UPON INSTALLATION. 

HELTUN SOLUTIONS LLC

82-84 ARAM STR. #46, 0002, YEREVAN, ARMENIA

WWW.HELTUN.COM    SUPPORT@HELTUN.COM

Parameter 

Number

Default 

Value

Available 

Values

Parameter

Size

Description

01

1 byte

Degree Mode

°C, °F

0

02

1 byte

EXT input mode

0, 1, 2

1

03

1 byte

Mode number for EXT input action

1, 2, 3, 4, 5, 6

2

04

1 byte

Source Sensor: 1=A, 2=AF, 3=F, 4=FA, 

5=P, 6=PA, 7=PF

1, 2, 3, 4, 5, 

6, 7

3

05

1 byte

Power Regulation ON time, min

10 - 90

15

06

1 byte

Power Regulation OFF time, min

10 - 90

15

07

1 byte

Dry Time, min

5 - 90

30

08

1 byte

Time correction by controller

0, 1

1

09

1 byte

Time format 

0, 1

0

10

1 byte

Week Day

1 - 7

1

11

1 byte

Time Hour

0 - 23

0

12

1 byte

Time Minute

0 - 59

0

14

2 bytes

Air Temperature Maximum in °C, x10

50 - 370

270

13

2 bytes

Air Temperature Minimum in °C,

 value X 10, e.g. 22.5°C=225

40 - 360

210

15

2 bytes

Floor Temperature Minimum in °C, x10

40 - 360

180

16

2 bytes

Floor Temperature Maximum in °C, x10

50 - 370

320

17

1 byte

Floor Sensor Resistance, kΩ

1 - 100

10

19

1 byte

Floor Temperature Calibration in °C, x10

-95 - 95

0

18

1 byte

Air Temperature Calibration in °C, x10

-95 - 95

0

20

1 byte

Temperature Hysteresis in °C, x10

1 - 95

5

21

1 byte

Temperature difference to send to 

controller, value X 10

1 -10

2

22

1 byte

Active display brightness level 

1 - 4, but 

>=Param23

4

23

1 byte

Inactive display brightness level

1 - 4, but 

<=Param22

3

24

1 byte

Auto LCD brightness control

0, 1

1

25

2 bytes

Auto brightness level 1 max lumens

0 - 5000

30

26

2 bytes

Auto brightness level 2 max lumens

0 - 5000

200

27

2 bytes

Auto brightness level 3 max lumens

0 - 5000

3000

28

1 byte

Basic Set Action

1, 2, 3, 4, 5, 6

6

29-50

Reserved by manufacturer

51

1 byte

Touch buttons sensitivity. 20=Supper 

sensitive. 70=lowest sensitivity.

20 - 70

50

52

2 bytes

Morning start time. Format: HHMM. 

e.g.08:00 should be sent as 0800

0000 - 2359

0600

53

2 bytes

Day start time. Format: HHMM.

0000 - 2359

0900

55

2 bytes

Night start time. Format: HHMM.

0000 - 2359

2300

54

2 bytes

Evening start time. Format: HHMM.

0000 - 2359

1800

56

2 bytes

Monday Morning temperature, valueX10

40 - 370

240

57

2 bytes

Monday Day temperature, valueX10

40 - 370

200

58

2 bytes

Monday Evening temperature, valueX10

40 - 370

230

59

2 bytes

Monday Night temperature, valueX10

40 - 370

180

60 - 63

2 bytes

Tuesday schedule temperatures: 

P60=morning t°C, P61=day t°C, 

P62=evening t°C, P63=night t°C

40 - 370

64 - 67

2 bytes

Wednesday schedule temperatures

40 - 370

68 - 71

2 bytes

Thursday schedule temperatures

40 - 370

72 - 75

2 bytes

Friday schedule temperatures

40 - 370

76 - 79

2 bytes

Saturday schedule temperatures

40 - 370

80 - 83

2 bytes

Sunday schedule temperatures

40 - 370

Reviews: