LucidControl DI4DO4, User Manual (1.0)
2022/02/03
Page 41 of 47
3.4.2.4
outDi1CycleTime
This IO Configuration Parameter specifies the cycle time T
Cycle
of an output in Duty-Cycle
Mode.
Parameter
outDi1CycleTime
Access
Read / Write
Address
0x1910
Values
T
Cycle
in µs (micro seconds)
T
Res
≤
T
Cycle
≤
1 h
Default Value
1,000,000 (1 s)
Parameter Type
4 Bytes unsigned
LucidIoCtrl Command Line Tool
Parameter Name
outDi1CycleTime
Parameter Values
Time [µs]
Call (Set)
LucidIoCtrl
–
d[COMx]
–
c[Channel]
–
soutDi1CycleTime=[Time]
{-p} {--default}
Call (Get)
LucidIoCtrl
–
d[COMx]
–
c[Channel]
–
goutDi1CycleTime
LucidIoCtrl Command Line Tool Example
Set T
Cycle
of output channel 4 to 1.5 s and make the setting persistent.
LucidIoCtrl
–
dCOM4
–
c4
–
soutDi1CycleTime=1500000
–
p [ENTER]
Read T
Cycle
parameter of output channel 4
LucidIoCtrl
–
dCOM4
–
c4
–
goutDi1CycleTime [ENTER]
outDi1CycleTime=1500000
Note
Timing limits for T
Res
(see 3.2.2) have to be considered.
3.4.2.5
outDi1DutyCycle
This IO Configuration Parameter specifies the Duty-Cycle of an output in Duty-Cycle mode.
Parameter
outDi1DutyCycle
Access
Read / Write
Address
0x1911
Values
Duty Cycle in
‰
(1 / 1000)
Default Value
500 (50%)
Parameter Type
2 Bytes unsigned
LucidIoCtrl Command Line Tool
Parameter Name
outDi1DutyCycle
Parameter Values
Duty Cycle [
‰
]
Call (Set)
LucidIoCtrl
–
d[COMx]
–
c[Channel]
–
soutDi1DutyCycle=[Value] {-p} {--default}
Call (Get)
LucidIoCtrl
–
d[COMx]
–
c[Channel]
–
goutDi1DutyCylce
LucidIoCtrl Command Line Tool Example
Set Duty Cycle of output channel 4 to 20% and make the setting persistent.
LucidIoCtrl
–
dCOM4
–
c4
–
soutDi1DutyCycle=200
–
p [ENTER]
Read Duty Cycle setting for output channel 0
LucidIoCtrl
–
dCOM4
–
c4
–
goutDi1DutyCycle [ENTER]
outDi1DutyCycle=200
Note
Timing limits (see 3.2.2) have to be considered.