2.0  Configuration and Modbus map 

 

User’s Manual GW-DLMS-485-ELSA15 

 

Page 9 

 

 

2.3  Modbus Mapping Area 

The data read from the meters are placed in the Holding Register area. 
A copy of the values is also present in the 4x20000 holding register area.  
Refresh time of the values is approximately: Time between readouts * N, where N is the number of 
energy meters connected to gateway and configured with a serial number different from zero in 
HomeDLMS.  
 
Modbus addresses in the table are base 1; depending on used Modbus master, sometimes is 
required to swap words to read data correctly. 
 

OBIS 

INDEX 

METER 1  METER 2  METER 3 

METER 4 

DATA 
TYPE 

OBIS 

TYPE 

NOTES 

4x40000 

UINT 

DI_00 

Digital Input 00 

4x40001 

UINT 

DI_01 

Digital Input 01 

4x40002 

UINT 

DO_00  Digital Output 00 

4x40003 

UINT 

DO_01  Digital Output 01 

4x40004 

4x40006 

4x40008 

4x40010 

UDINT  SERIAL  Energy meter's serial code to start communciation 

4x40014 

FLOAT  ERROR  Error number from gateway 

4x40016 

4x40216 

4x40416 

4x40616 

DINT 

0.9.1 

Time 

4x40018 

4X40218 

4x40418 

4x40618 

DINT 

0.9.2 

Date 

4x40020 

4x40220 

4x40420 

4x40620 

DINT 

F.F 

Error code 

4x40022 

4x40222 

4x40422 

4x40622 

DINT 

F.F.1 

Error code 

4x40024 

4x40224 

4x40424 

4x40624 

DINT 

F.F.2 

Error code 

4x40026 

4x40226 

4x40426 

4x40626 

DINT 

F.F.3 

Error code 

4x40028 

4x40228 

4x40428 

4x40628 

FLOAT 

C.1.0 

  

4x40030 

4x40230 

4x40430 

4x40630 

FLOAT 

0.2.1 

  

4x40032 

4x40232 

4x40432 

4x40632 

FLOAT 

C.3 

  

4x40034 

4x40234 

4x40434 

4x40634 

FLOAT 

C.4 

  

10 

4x40036 

4x40236 

4x40436 

4x40636 

FLOAT 

C.5 

  

11 

4x40038 

4x40238 

4x40438 

4x40638 

FLOAT 

1.8.0 

Sum Li Active  (QI+QIV) 

12 

4x40040 

4x40240 

4x40440 

4x40640 

FLOAT 

1.8.0* 

Sum Li Active  (QI+QIV) - prev. period 

13 

4x40042 

4x40242 

4x40442 

4x40642 

FLOAT 

1.6.1 

Max Active Power - Import - Tariff 1 (kW) 

14 

4x40044 

4x40244 

4x40444 

4x40644 

FLOAT 

1.6.1* 

Max Active Power - Import - Tariff 1 (kW) - previous period 

15 

4x40046 

4x40246 

4x40446 

4x40646 

FLOAT 

1.2.1 

Max Cumulative Active Power - Import - Tariff 1 (kW) 

16 

4x40048 

4x40248 

4x40448 

4x40648 

FLOAT 

1.2.1* 

Max Cumulative Active Power - Import - Tariff 1 (kW) - prev. period 

17 

4x40050 

4x40250 

4x40450 

4x40650 

FLOAT 

5.8.0 

Sum Li Reactive Energy QI 

18 

4x40052 

4x40252 

4x40452 

4x40652 

FLOAT 

5.8.0* 

Sum Li Reactive Energy QI - previous period 

19 

4x40054 

4x40254 

4x40454 

4x40654 

FLOAT 

8.8.0 

Sum Li Reactive Energy QIV 

20 

4x40056 

4x40256 

4x40456 

4x40656 

FLOAT 

8.8.0* 

Sum Li Reactive Energy QIV - previous period 

21 

4x40058 

4x40258 

4x40458 

4x40658 

FLOAT 

2.8.0 

Sum Li Active Energy- (QII+QIII) 

22 

4x40060 

4x40260 

4x40460 

4x40660 

FLOAT 

2.8.0* 

Sum Li Active Energy- (QII+QIII) - previous period 

23 

4x40062 

4x40262 

4x40462 

4x40662 

FLOAT 

2.6.1 

Max Active Power - Export - Tariff 1 (kW) 

24 

4x40064 

4x40264 

4x40464 

4x40664 

FLOAT 

2.6.1* 

Max Active Power - Export - Tariff 1 (kW) - prev. period 

25 

4x40066 

4x40266 

4x40466 

4x40666 

FLOAT 

2.2.1 

Max Cumulative Active Power - Export - Tariff 1 (kW) 

26 

4x40068 

4x40268 

4x40468 

4x40668 

FLOAT 

2.2.1* 

Max Cumulative Active Power - Export - Tariff 1 (kW) - prev. period 

27 

4x40070 

4x40270 

4x40470 

4x40670 

FLOAT 

7.8.0 

Sum Li Reactive Energy QIII 

Summary of Contents for GW-DLMS-485-ELSA15

Page 1: ...USER S MANUAL Gateway DLMS MODBUS for ELSTER A1500 with RS485 P N GW DLMS 485 ELSA15 Edition 2 0 MARCOM SRL Phone 390458204747 Email info marcomweb it Via Mezzacampagna 52 int 29 www marcomweb it ...

Page 2: ...t User s Manual GW DLMS 485 LG Page i Revision Sheet Release No Date Revision Description Rev 0 10 05 14 User s Manual Template and Checklist Rev 1 10 06 16 Conversion to new format Rev 2 30 01 17 New HomeDLMS page ...

Page 3: ...1 1 System Overview 3 1 2 Features 4 1 2 1 Connections 4 1 2 2 Digital Input connection 4 1 2 3 Serial port connections 5 2 0 CONFIGURATION AND MODBUS MAP 6 2 1 Web Visualization 6 2 2 Gateway Settings 7 2 3 Modbus Mapping Area 9 3 0 COMMUNICATION ERRORS 11 3 1 Type of error 11 4 0 MECHANICAL FEATURES 12 ...

Page 4: ... services which permit to read objects OBIS defined Inside these objects are mapped running meter values using standard profiles By Gateway DLMS MODBUS is possible to read DLMS energy meter s data using MODBUS RTU or MODBUS TCP protocol The gateway is completely transparent to DLMS protocol so user must know only Modbus protocol This Gateway version reads data from up to four counters through the ...

Page 5: ...ster Modbus RTU 1 x Serial RS485 port to connect up to four energy meter 1 x Ethernet port to read Energy meter s data by client Modbus TCP 1 screw connector to supply gateway 10 30 VDC min 2 W Front Signal LED for communication diagnostic 2 x Digital Input 2 x Digital Output Their status is mapped in Modbus registers 1 2 2 Digital Input connection The schema of two digital input output connection...

Page 6: ...2 0 Configuration and Modbus map User s Manual GW DLMS 485 ELSA15 Page 5 1 2 3 Serial port connections The schema of serial port connection is ...

Page 7: ... data read from the counter you need to connect to the network using the Ethernet RJ45 port available on the gateway By a web browser just type the default address 192 168 0 122 In case of connection failure ensure that you have on your network card address on a subnet 192 168 0 X This brings us to the main screen of the Gateway with the values common to all Meter ...

Page 8: ...an force the gateway to reboot The confirmation of the changes is recorded using the Submit button You can also change the energy meter s serial number connected to the Gateway This step is required to enable communication between Gateway and the meter 2 2 Gateway Settings To change the gateway settings such as IP address you need access to the configuration pages through the appropriate link Syst...

Page 9: ...5 ELSA15 Page 8 While going on hardware setup you can change RS232 serial port communication settings COM 2 port changes don t serve because they are forced by the program specific settings MODBUS node number to communicate with the MODBUS RTU and MODBUS TCP ...

Page 10: ...3 9 4x40034 4x40234 4x40434 4x40634 FLOAT C 4 10 4x40036 4x40236 4x40436 4x40636 FLOAT C 5 11 4x40038 4x40238 4x40438 4x40638 FLOAT 1 8 0 Sum Li Active Energy QI QIV 12 4x40040 4x40240 4x40440 4x40640 FLOAT 1 8 0 Sum Li Active Energy QI QIV prev period 13 4x40042 4x40242 4x40442 4x40642 FLOAT 1 6 1 Max Active Power Import Tariff 1 kW 14 4x40044 4x40244 4x40444 4x40644 FLOAT 1 6 1 Max Active Power ...

Page 11: ...IV Current avg 50 4x40116 4x40316 4x40516 4x40716 FLOAT 2 5 0 Sum Li Active power QII QIII Last avg 51 4x40118 4x40318 4x40518 4x40718 FLOAT 2 4 0 Sum Li Active power QII QIII Current avg 52 4x40120 4x40320 4x40520 4x40720 FLOAT 0 3 0 53 4x40122 4x40322 4x40522 4x40722 FLOAT 0 3 3 54 4x40124 4x40324 4x40524 4x40724 FLOAT C 70 Some systems have problem with float number so we have created a copy of...

Page 12: ... check cable connection and if energy meter s serial number is correct and written in the right modbus address 2 error in extracting ID code from meter s message please check cable connection 7 message from energy meter is too big for gateway s buffer this error does not compromise gateway s normal functionality but last part of obis list will be lost 8 message from energy meter is empty please ch...

Page 13: ...7 0 Mechanical features User s Manual GW DLMS 485 ELSA15 Page 12 4 0 MECHANICAL FEATURES The size of the gateway are the following ...

Reviews: