Moog ACV with CANopen bus interface
7 Servo valve functions
Spool position setpoint conditioning / demand value generator
B99224-DV018-D-211, Rev. A, October 2018
136
7.1.13.1 Object 0x3030: Basic sample frequency
This frequency is fixed to 10 kHz that corresponds to a sampling time of 0.1 ms.
7.2 Spool position setpoint conditioning / demand value
generator
Figure 55: Spool position demand value generator
7.2.1 Object 0x6310: Demand value
The demand value is generated from the #SpoolPositionSetpoint# by means of the functions in the demand
value generator and forwarded to the spool position controller.
Chapter "2.4.3 Units and prefix parameter", page 12
Hardware
Index
Sub-index
Parameter name
Data type
Access
Per-
sistence
Value range
Default
0x3030
1
BasicSampleFrequency
UINT16
ro
-
10000
10000
Spool position
demand value generator
Limit function
Scaling
Ramp
Directional
dependent gain
Characteristic
compensation
Dead band
compensation
Zero correction
#SpoolPositionSetpoint#
<DemandValue>
(0x6310)
The internal signal #SpoolPositionSetpoint# is used to link the spool position setpoint value to the
spool position demand value generator.
Chapter "6.2.3 Spool position setpoint value path", page 59
ValvePositionControl_DemandValueGenerator
Index
Sub-index
Parameter name
Data type
Access
Per-
sistence
Value
range
Default
0x6310
1
SplDemandValue
INT16
ro
-
INT16
None
0x6310
2
Unit
UINT8
ro
-
UINT8
0
0x6310
3
Prefix
INT8
ro
-
INT8
0