Web Console Configuration
4-7
Parameter
Value
Default
Description
manufacturer. Based on this response time, the master can be
configured to wait a certain amount of time for a slave’s response. If
no response is received within the specified time, the master will
disregard the request and continue operation. This allows the
Modbus system to continue the operation even if a slave device is
disconnected or faulty. On the MGate 5111, the Response timeout
field is used to configure how long the gateway will wait for a
response from a Modbus slave. Please refer to your device
manufacturer’s documentation to manually set the response
timeout
Add Modbus Commands
Parameter
Value
Default
Description
Name
(an alphanumeric string)
Command1
Max. 32 characters
Slave IP address
0.0.0.0 -
255.255.255.255
0.0.0.0
The IP address of a remote slave
device.
Port
1 - 65535
502
The TCP port number of a remote
slave device.
Slave ID
1 - 255
1
The Modbus slave ID
Function
1 – Read Coils
2 – Read Discrete Inputs
3 – Read Holding Registers
4 – Read Input Registers
5 – Write Single Coil
6 – Write Single Register
15 – Write Multiple Coils
16 – Write Multiple Registers
23 – Read/Write Multiple
Registers
When a message is sent from a Client
to a Server device, the function code
field tells the server what kind of
action to perform.
Trigger
Cyclic
Data Change
Disable
Disable: The command is never sent
Cyclic: The command is sent
cyclically at the interval specified in
the Poll Interval parameter.