Universal Wall-Mount Controller

BACnet Communication Module User Guide

 

www.neptronic.com

 

Page | 6 

 

Property 

Value 

Writable 

Proprietary property #1000 

  Programmable (default:0) 

  Represents the MS/TP MAC address in the range of 0 to 254  

  Values 128 to 254 represent MS/TP non-token passing slave devices 

Proprietary property #1001 

  Programmable (default: Auto) 

  Represents the MS/TP Baud rate (unsigned type) 

  Values are 0 (Auto), 9600, 19200, 38400, 76800 

  Reading this property always returns the actual Baud rate 

Proprietary property #1002 

  Programmable (default: 15 minutes) 

  Represents the period of time that an object in/out of service will automatically 

return to normal. Range = 0-120 minutes (unsigned type) 

  Writing 0 means no automatic return to normal 

Object Types Supported 

The following table lists all the BACnet properties supported for each object type. Most of the properties are locked. 
The exception is 

Present_Value

, which represents the dynamic operating values of the device, and the Status_Flag, 

Event_State

,

 and Reliability properties, which reflect the availability of the 

Present_Value

. Unless otherwise specified, 

properties are not changeable. 

Table 3 - Object Types Supported 

Object 

Type 

Enabled 

Optional Properties 

Supported 

Writable Properties 

Notes 

Note: Writable properties are different for some objects. Refer to the respective Object Table information to know the writable property for objects.

 

Analog 
Input 

 

  Reliability 

  Description 

  Min_Present_Value 

  Max_Present_Value 

  Resolution 

  Cov-increment 

  Out_of_Service 

  Cov-Increment 

  If "Out of Service" is true, Present_Value and 

Status_Flag become writable properties. Refer to 
Out of Service Property section on page 7 for more 
information.  

  Object will automatically return to Normal after a 

programmable period of time. Refer to Proprietary 
property #1002 of Device Object in Table 2 - 
Device Object Properties.

 

Analog 
Value 

 

  Reliability 

  Description 

  Cov-Increment 

  Priority_Array 

  Relinquish_Default

 

  Present_Value  

  Out_of_Service 

  Cov-Increment 

  Present_Value property is writable for every AV 

object except AV.20, AV.24, AV.35, AV.38, AV.50, 
AV.60, AV.78, AV.79, AV.87. 

  Out_of_Service property is writable for AV.1, AV.3, 

AV.4, AV.70, AV.95. 

  Refer to Out of Service Property section on page 7 

for more information.  

  Object will automatically return to Normal after a 

programmable period of time. Refer to Proprietary 
property #1002 of Device Object in Table 2 - 
Device Object Properties.  

Analog 
Output 

 

  Description 

  Reliability 

  Min-Pres-Value 

  Max-Pres-Value 

  Resolution 

  Cov-Increment 

  Present_Value  

  Cov-Increment 

 

Binary 
Input 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

Out_of_Service 

  If "Out of Service" is true, Present_Value and 

Status_Flag become writable properties. Refer to 
Out of Service Property section on page 7 for more 
information.  

  Object will automatically return to Normal after a 

programmable period of time. Refer to Proprietary 
property #1002 of Device Object in Table 2 - 
Device Object Properties. 

Binary 
Value 

 

  Reliability 

  Active_Text 

  Inactive_Text 

  Description 

  Priority_Array 

  Relinquish_Default

 

Present_Value 
Out_of_Service

 

 

  Present_Value property is writable for every Binary 

Value object except BV.36 and BV.42. 

  Out_of_Service property is writable for BV.30. 

  Some objects are commandable. In such case, the 

priority-array and relinquish-default properties are 
available for BV.30.

 

  Object automatically returns to Normal after a 

programmable time. Refer to Proprietary property 
#1002 of Device Object in Table 2 - Device Object 
Properties.  

 

 

 

 

 

Summary of Contents for TUCB24C6X2

Page 1: ...versal Wall Mount Controller TUCB TUHB Series BACnet Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humi...

Page 2: ...guration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7...

Page 3: ...nutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to the device...

Page 4: ...ually through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its d...

Page 5: ...t guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing u...

Page 6: ...iguration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5...

Page 7: ...Object Name and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 0...

Page 8: ...Property section on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Ob...

Page 9: ...5 Out_of_Service property is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Descript...

Page 10: ...o Units 0 Open 1 Close AI 2 AnalogInput2 Sensor reading value on analog input 2 Out of Service Cov Increment If a 10k type III sensor is used displays 0V Fault and Out of Service Status Flags are True...

Page 11: ...ocked to prevent the user from changing the setpoint BV 2 This object is commandable relinquish default will be saved to non volatile memory Present Value Relinquish_Default Cov Increment 50 F to 104...

Page 12: ...value must be bigger Present Value Cov Increment 0 to 250 seconds Resolution 5 seconds AV 46 Cfg_CoolingAntiCycleDelay Configuration value in mins to prevent the cooling outputs to cycle on and off Th...

Page 13: ...AV 81 Cfg_HumDeadBand Configuration value that represents the range at which the controller will not take action when below or above the humidity setpoint Present Value Cov Increment 0 RH to 5 RH Res...

Page 14: ...f demand at which the contact closes to energize the controlled element Present Value Cov Increment 15 to 80 Resolution 1 AV 116 Cfg_BinaryOutput1OpenPos Configuration value that indicates the percent...

Page 15: ...15 minutes Resolution 1 minute AV 165 CopyCfgStartAddress Represents the first address in the range of copied controllers while using the Copy Config option Present Value Cov Increment 0 to 254 Resol...

Page 16: ...t4 Contact status of the output 0 Open 1 Close Present Value 0 Open 1 Close BO 5 BinaryOutput5 Contact status of the output 0 Open 1 Close Present Value 0 Open 1 Close BO 6 BinaryOutput6 Contact statu...

Page 17: ...er internal or external Only available on model TUHB24C6X2 Present Value 0 Intern Sensor 1 Extern Sensor BV 26 Cfg_HumSetPointLock Configuration value to prevent the user from changing the relative hu...

Page 18: ...ed When set to 1 Reverse the contact is considered Normally Closed Present Value 0 Direct 1 Reverse BV 61 Cfg_BinaryOutput2Direction See BV 60 Present Value 0 Direct 1 Reverse BV 62 Cfg_BinaryOutput3D...

Page 19: ...at BV 3 BV 21 BV 98 and MSV 20 Auto Controller mode changes automatically between heating and cooling in operation when there is a cooling or heating demand Heating Controller is in heating in operat...

Page 20: ...s in night setback mode 3 Override Zone is in night setback mode but put back to day operation for a maximum pre determined time set at AV 85 Read Only 1 Day 2 Night 3 Override MSV 20 Cfg_Sequence Sel...

Page 21: ...lter Controller activates an alarm to indicate that the filter is dirty 15 Flow Switch Controller activates an alarm to indicate that there is no airflow 16 Overheat Controller activates an alarm to i...

Page 22: ...e 1 OFF 2 Change Over With Fan 3 Cooling1With Fan 4 Cooling2With Fan 5 Heating1With Fan 6 Heating2With Fan 7 Heating2 8 Cooling1Heating1With Fan 9 Humidify With Fan 10 CO2Alarm MSV 57 Cfg_AnalogOutput...

Page 23: ...demand 2 Display Setpoint Demand TUxB will display the actual setpoint and cooling heating demand 3 Display Temp TUxB will display the actual temp but no demand 4 Display Setpoint TUxB will display t...

Page 24: ...beau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm E...

Reviews: