When the device is powered, display shows the counting cycle and the
main counter value. Press
to switch to the batch counter and
totalizer. Press
to select the decimal point position for the main
counter and totalizer (the batch counter does not use decimal points).
To access cycles with timed access, press and hold for 2 seconds,
which will provide access to the following upper cycle. Press and hold
to access the following upper cycles.
In any cycle you can use to go to the next parameter. Press
to change a parameter. Press to increment the flashing digit and
to go to the next digit. In screens with decimal point configuration,
it can be configured after passing through all the other digits. The
parameter changed is saved in nonvolatile memory when
is
pressed.
Keys to access, change and save configuration parameters
To change parameters
For 2 seconds to change cycle
Blink the most significant
digit
To increment the blinking digit
To change the blinking digit
To save and change parameter
again
PASSWORD
Depending on the protection level defined in
Prot
, the
PASS
screen
can be displayed before access to
Set points, Configuration or
Hardware setup Cycles
. If the wrong password is informed, all
parameters will be protected against changes, and could only be
viewed. Insert the right password to change parameters for a cycle.
Default password is
1111
, and can be changed in
Pass.C
parameter.
In case you enter the wrong password 5 consecutive
times, a new attempt will only be allowed after 10
minutes.
In case you have changed or forgotten the password,
see item “
Master Password
” to check how to
determine a master password for your device.
MASTER PASSWORD
The master password allows user to define a new password for the
NC400-6. It is the first four digits of the serial number.
Ex.: The master password for device with serial number
87123465
is:
8 7 1 2
How to use the master password:
1- Enter the master password value at
PasS
.
2- Go to
PAS.c
parameter and enter a new password.
3- Now you can use this new password.
COUNTING CYCLE
Indication of MAIN COUNTER value
Press to change the decimal point position
Indication of BATCH COUNTER value
Indication of TOTALIZER COUNTER value
Press to change the decimal point position.
SET POINTS CYCLE
SP1 C
S
et
P
oint
1
-
C
ounter
Set point 1 value of the main counter.
Values range from
0.00000
to
999999
with
configurable decimal point.
Sp2 c
S
et
P
oint
2
-
C
ounter
Set point 2 value of the main counter.
Values range from
0.00000
to
999999
with
configurable decimal point.
SP bat
S
et
P
oint –
Bat
ch
Batch counter Set point value.
Values range from
0
to
999999
.
SP tot
S
et
P
oint -
Tot
alizer
Set point 1 value of the totalizer counter.
Values range from
0.00000
to
999999
with
configurable decimal point.
CONFIGURATION CYCLE
Out1.t
Out1
T
ime
Duration in seconds of OUT1 pulse. Configurable
from
0.00
to
9999.99
s.
If OUT1 is configured to turn off after a period of time
(
Out1.E
) parameter) and the programmed time is
0
,
OUT1 will not be enabled.
Out2.t
Out2
T
ime
Duration in seconds of OUT2 pulse. Configurable
from
0.00
to
9999.99
s.
If OUT2 is configured to turn off after a period of time
(
Out2.E
parameter) and the programmed time is
0
,
OUT2 will not be enabled.
Off.c
Off
set -
C
ounter
Value assigned to the main counter when it is started
(
reset
).
May vary from
0
to
999999
.
Off.bat
Off
set -
Bat
ch
Value assigned to the batch counter when it is
started (
reset
).
May vary from
0
to
999999
.
Off.tot
Off
set -
Tot
alizer
Value assigned to the totalizer counter as soon as it
is started (
reset
).
May vary from
0
to
999999
.
f.func
F
Key
Func
tion
Function programmed to key.
0
: No function associated.
1
:
Hold
s input countings. Press once to hold
the counters. Press the key again to return
counting.
2
:
Reset
of counters configured to reset with
key. Leaves
Hold
state.
3
: Output
Reset
.
4
:
Reset
of counters configured to reset with
key. Outputs reset. Leaves
Hold
state.
Opt.tot
Opt
ions -
Tot
alizer
Define work modes for the totalizer.
1
: Totalizes pulses applied to the main counter
0
: Counts how many times the batch counter
reached
SPbAt
.
out1.e
Out1
–
E
nd
Condition for OUT1 to turn off.
0
: Set point 1 does not turn off
OUT1.
1
: Turns off when (see parameter
opt.sp.c
). For example: If OUT1
was enabled when the Set point 1
value was reached in a
progressive counting, OUT 1 will
be disabled when the counter
becomes lower than Set point 1.
0
: Set point 2 does not affect OUT1.
1
: Turns off when the counter
reaches Set point 2.
0
: External reset does not affect
OUT1.
1
: Turns off at the start of an external
reset pulse.
2
: Turns off at the end of an external
reset pulse.
3
: Turns off at the start of an external
reset pulse.
0
: OUT2 does not affect OUT1.
1
: Turns off when OUT2 is turned on.
2
: Turns off when OUT2 is turned off.
3
: Turns off when OUT2 is turned on
or off.
0
: OUT1 (
out1.t
) time does not
affect OUT1.
1
: Turns off after the time defined in
OUT1 Time parameter (
out1.t
)
has expired.