20
2nd output group
1012H
Output value read and write of
Output 1
Unit is 0.1%, write operation is valid under manual tuning mode only.
1013H
Output value read and write of
Output 2
Unit is 0.1%, write operation is valid under manual tuning mode only.
1016H
Temperature regulation value
-99.9 ~ +99.9. Unit is 0.1
1017H
Analog decimal setting
0 ~ 3
101CH
PID parameter selection
0~5/AUTO
101DH
SV value corresponded to PID
value
Only valid within available range, unit: 0.1 scale
1020H
Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail
1021H
Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail
1022H
Alarm 3 type
Please refer to the contents of the “Alarm Outputs” for detail
1024H
Upper-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1025H
Lower-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1026H
Upper-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1027H
Lower-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1028H
Upper-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
1029H
Lower-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
102AH
Read LED Status
b0: ALM3, b1: ALM2, b2:
℃
, b3:
℉
, b4: ALM1, b5: OUT2, b6:OUT1, b7: AT
102BH
Read Pushbutton Status
b1: F2, b2: Up, b3: Loop, b5: F1, b6: Down, b7: Set, 0: press down key
102CH
Setting lock status
102FH
Software version
V1.00 indicates 0x100
1030H
Start pattern number
0 ~ 15
1032H
Remaining time of the executed
step (second)
Only read
1033H
Remaining time of the executed
step (minute)
Only read
1034H
No. of currently executed step
Only read
1035H
No. of currently executed pattern Only read
1036H
Read dynamic value in
programmable control
Only read
1039H
Communication write
0: Disable (default), 1: Enable
103AH
Temperature unit display
selection
0: , 1: /
℉
℃
linear input (default)
103BH
AT setting
0: OFF (default), 1: ON
103CH
Control RUN/STOP setting
0: STOP, 1: RUN (default), 2:END (program mode), 3: HOLD (program mode)
101FH
Start step number
0 ~ 15
1200H~13FFH
Pattern 0~15 temperature set
point setting (Even number)
Pattern 0~15 execution time
setting (Odd number)
-999 ~ 9999
Time: 0 ~ 900
(
1 minute per scale
)
1400H~140FH Actual number of step setting
inside the corresponding pattern
0 ~ 15 = N, indicate that this pattern is executed from step 0 to step N
1410H~141FH
Cycle number for repeating the
execution of the correspond
pattern
0 ~ 99 indicate that this pattern has been executed for 1 ~ 100 times
1420H~142FH Link pattern number setting of
the correspond pattern
0 ~ 15, 16 indicates the program end and keep in present step. 17 indicates the
program end and execution end. 0~15 indicates the next execution pattern
number after executing the current pattern
Address
Content
Definition
1100H
Adjust Temperature Gain
1101H
Temperature Filter Range
Range of temperature filter: 10~1000, unit: 0.01
℃
, default: 100(1.0
℃
)
1102H
Temperature Filter Factor
Setting range: 0~50, default: 8
1103H
Reverse Output
Bit1: output 2, Bit0: output 1
1104H
Slope of Temperature Increase
Unit: 0.1 /
℃
min or 0.1
℃
/sec (refer to CommunicationAddress 1124H)
1105H
Remote Input Type Selection
0: 0~20m A , 1: 4~20m A, 2: 0~5V, 3: 1~5V, 4: 0~10V