Section 1—Modbus Protocol
This manual is for use with maintenance board firmware version 3.05.
Introduction
The communications protocol for CamCor CT Series and PRO Series is in accordance with Modicon, Inc. RTU Mode
Modbus as described in
Modicon Modbus Protocol Reference Guide
, PI-MBUS-300 Rev. J, June 1996. All registers are
implemented as 4X or holding registers. Reading of registers is implemented via Function Code (03H) (Read Holding
Registers). Writing to registers is implemented via Function Code 16 (10H) (Preset Multiple Registers).
Communications
CamCor’s Modbus communications allow host devices (PC, sequencer, etc.) to connect to slave devices via RS-485 con
-
nection. Modbus communication is based on the Master-Slave system, where host devices are designated as “master”
and the Coriolis meter(s) is designated as “slave.” The system is Modbus-protocol compliant. Contact the host device
service provider for assistance with host software.
Caution
If the CamCor meter is installed in a control system, place the control system in manual operating
mode before making changes to the CamCor meter configuration. Failure to do so may cause er
-
ratic and undesired responses from valves or other devices controlled by the system.
Table 1.1—Communication Specifications
below for CamCor Coriolis meter communication specifications.
Table 1.1—Communication Specifications
Specification
Description
Communication System
RS-485 Multidrop-compliant Master/Slave System
Full-duplex/Half-duplex
Half-duplex
Baud Rate
9600, 19200, 38400 (shipped from Factory at 9600)
Slave Address
1
Data Bits
8
Parity
Odd
Stop Bit
1 Bit
Flow Control
None
Communication Timeout
200 ms
Transmission Length (Maximum)
0.75 miles (1.2 km) (depending on service environment)
Number of Devices on Each Node
(Maximum)
32
Optional Modbus Communication Baud Rate Setting
A CamCor meter purchased with the Modbus Communication option is shipped with the baud rate set to 9600. The baud
rate is adjustable using the SW3-1 and SW3-2 switches on the maintenance board (
) located in the
transmitter body. (For more information about maintenance board access and switch locations, see the CamCor Hardware
Table 1.2—Baud Rate Switch Settings
below to identify baud rate settings based on switch position:
Table 1.2—Baud Rate Switch Settings
Baud Rate
SW3-1 Setting
SW3-2 Setting
9600
Off
Off
19200
On
Off
38400
Off
On
5
CamCor
™
Modbus Protocol
Section 1
Summary of Contents for CamCor
Page 1: ...CamCor Modbus Protocol Manual Manual No 50284150 Rev 01 ...
Page 4: ...This page is left blank intentionally iv Table of Contents CamCor Modbus Protocol ...
Page 8: ...This page is left blank intentionally 8 Section 2 CamCor Modbus Protocol ...
Page 10: ...This page is left blank intentionally 10 Section 2 CamCor Modbus Protocol ...
Page 22: ...This page is left blank intentionally 22 Section 3 CamCor Modbus Protocol ...