Read Only Registers
– These are 16-bit read only registers. They can be read with Modbus
opcode 0x03 or 0x04 (Read Discrete Input and Holding Registers, respectively). The register
map can be found below.
If the gateway has a large total number of registers approaching 4700, register 2008 should be
monitored to ensure that free registers are available before adding a new node.
Register
Number
Register
Address
(Offset)
Description
42001
2000
Upper 16 bits of SFTS GW node address (the radio ID)
42002
2001
Lower 16 bits of SFTS GW node address (the radio ID)
42003
2002
Upper 16 bits of Radio Firmware version number
42004
2003
Lower 16 bits of Radio Firmware version number
42005
2004
Upper 16 bits of gateway firmware version number
42006
2005
Lower 16 bits of gateway firmware version number
42007
2006
Number of slave nodes that data is cached for this gateway
42008
2007
Total number of registers allocated to slave devices
42009
2008
Total number of free registers available for slave devices
42010
2009
Bitmask for active slave IDs 15-0 (LSB is 0)
42011
2010
Bitmask for active slave IDs 31-16 (LSB is 16)
42012
2011
Bitmask for active slave IDs 47-32 (LSB is 32)
42013
2012
Bitmask for active slave IDs 63-48 (LSB is 48)
42014
2013
Bitmask for active slave IDs 79-64 (LSB is 64)
42015
2014
Bitmask for active slave IDs 95-80 (LSB is 80)
42016
2015
Bitmask for active slave IDs 111-96 (LSB is 96)
42017
2016
Bitmask for active slave IDs 127-112 (LSB is 112)
42018
2017
Bitmask for active slave IDs 143-128 (LSB is 128)
42019
2018
Bitmask for active slave IDs 159-144 (LSB is 144)
42020
2019
Bitmask for active slave IDs 175-160 (LSB is 160)
42021
2020
Bitmask for active slave IDs 191-176 (LSB is 176)
42022
2021
Bitmask for active slave IDs 207-192 (LSB is 192)
42023
2022
Bitmask for active slave IDs 223-208 (LSB is 208)
42024
2023
Bitmask for active slave IDs 239-224 (LSB is 224)
42025
2024
Bitmask for active slave IDs 255-240 (LSB is 240)
42026
2025
Gateway power supply voltage in mV
42027
2026
Radio packets received count
42028
2027
Radio packets sent count
42029
2028
RS-485 messages received count
42030
2029
RS-485 messages sent count
42031
2030
Total Modbus errors from master and slaves
42032
2031
Modbus exceptions from slave nodes
42033
2032
Radio packets received/transmitted per minute. Recommended to be less